Beruflich Dokumente
Kultur Dokumente
Problematic:
- A standard waveshape (1,2 µs ± 30% x 50 µs ± 20%) is specified. For most of the cases,
there is no problem to meet this required waveshape with most of the actual test laboratory
equipment available;
- For some transformers (large MVA and/or relatively low winding voltage and/or low leakage
impedance), the tail time can not be obtained easily and for some cases, impossible to
achieve even with the most powerful impulse generators ( 400 kJ).
- The tail time achieved during the impulse tests is an important factor to demonstrate that the
transformer is capable to withstand its rated BIL level;
Problematic (continued):
- The tail time is function of the capacitance used in the impulse generator together with the
leakage impedance (for low leakage impedance); t2 (LTCG). To get the required waveshape,
options are to have the proper impulse generator capacitance and to use alternative
methods as stated in IEEE C57.98.
- IEEE C57.12.90, clause 10.3.1.1 does permit the use of a shorter waveshape provided that
the impulse generator capacitance is equal to or greater than 0,011 µF; How short can be the
waveshape to get a meaningful test (30 µs, 20 µs, 10 µs…)?
- During previous meetings, it has been a general consensus that the capacitance value
(0,011 µF) given in IEEE C57.12.90 is totally inadequate and shall be replaced by
something else.
Problematic (continued):
- The concept of a "minimum impulse generator energy" has been proposed and
discussed in several occasions since Leon (Mexico) meeting (November 1998).
- Some manufacturers are equipped with more powerful impulse generators than others;
- Two identical transformers made by two different manufacturers may be tested with
different severities depending of the manufacturer laboratory capabilities.
- Category IV (10 MVA to 600 MVA, single phase rating) has to be split in at least three
sub-categories (IVa, IVb and IVc) because this is a too wide power range. This will
give lower energy requirements for mid-band of that power range.
- Reconsider the minimum energy value for the class covering the highest MVA ratings
(part of the actual class IVb). The proposed value of 100 kJ seems to be too
restrictive.
"After observing the discussions and in personal talks, I come to the conclusion that
there is a conflict of interest with the transformer manufacturers that can not be
solved.
I think a solution we all could live with would look like this:
- On your last slide you wrote: "If the calculated impulse generator energy is such
that the minimum time... can not be achieved, the manufacturer shall mention it
during the bidding stage. The manufacturer shall also state the strategy...." I would
make this mandatory.
"- Based on this information, the customer (utility) can make an informed decision. If
they think that a restricted test and increased risk of lower reliability is worth the
money they save with a lower bid, so be it.
On the other hand, a manufacturer with a powerful enough impulse generator has a
competitive advantage. And if manufacturers with weak generators are loosing too
much business, it would give them an incentive and justification for upgrading their
generator.
- The minimum energy tables could be used to explain the limitations in the test to
the customer. It is certainly easier for a manufacturer to argue and explain why he
cannot fulfill the tail time requirements if he has a generator with IEEE recommended
energy level than for a manufacturer without. In the later case the customer would
have a better bargaining position to reduce the price further."
There is no problem to obtain the required wave-shape in the HV-range from 765 kV
down to 161 kV, even for extreme ratings (P = 1500 MVA, z = 10%). Problems occur for
low voltages, especially of course for low voltage windings of GSUs."
"For those windings generally the necessary frequency cannot be obtained and tail-
times down to 20 µs can be expected. Generally an additional grounding resistor R G is used.
It is then no problem to obtain a sufficient wave-length, but the voltage across the inductance
is very short. This is only a good test of the insulation strength to ground. On the other
hand it must be considered that already low order harmonics of low impedance windings
show a high frequency and are not essentially influenced by the tail (see example file
impgen04.doc). No influence can also be observed on gradients, they are mainly influenced
only by the front (see the same file). Therefore a test with the winding grounded at one
terminal is in the most cases meaningful, even when the tail-time is short."
"General guide-lines for the necessary minimum energy of impulse generators are
certainly a valuable tool, although they cannot cover every case. Tests should be
performed in a way that they simulate stresses in service as close as possible. How meaningful
a test is depends on the type of winding and/or transformer and has to be found out in the
course of design reviews. Low impedance windings may require a combination of tests. I
believe that a guide should point out these facts and encourage user and manufacturer
to find the optimum by close cooperation."
0.8
40
0.6
0.4
20
0.2
0
0 10 20 30 40 50
µs
kette01
2.0
0.8
0.6
0.4
0.2
0 0
0 2 4 6 8 10
µs
kette02
2- Transformers classified as Class I (highest system voltage rating 69 kV) and having
small power ratings (categories I and II) are now treated separately since a impulse fault in
service of such transformers have generally minor impacts compared to power
transformers having higher rated power (transmission substations). The requirement
regarding a minimum impulse generator energy is not any more mandatory. For these
transformers ratings, a minimum impulse generator capacitance is now given.
3- The minimum impulse generator energy for category IVc (highest power range) has been
reduced to 62,5 kJ since several transformer manufacturers have no impulse generators
rated more than 250 kJ. This will reduce the number of cases covered but could be a
valuable compromised (to be discussed)
4- The minimum impulse generator energy suggested for transformers belonging to Class II
et to medium and large power ratings (categories III and IV) of transformers designated
Class I is not anymore mandatory but only recommended.
5- The use of resistors on the non impulsed terminals is now considered fully acceptable as
the mitigation method to achieve the tail time.
New calculations:
New sets of calculations have been performed by using the following assumptions:
Studied cases
- The proposed energy levels were chosen in order to cover 80% of the cases studied
(80% has been agreed upon during the Oklahoma City meeting);
- A maximum of 62,5 kJ has been used because this is the practical and available upper
limit that can be obtained from most impulse generators;
- Transformer power ratings have been categorized according to the classification used
in C57.12.00 for short-circuit withstand capability (minimum nameplate rating; ONAN; as
agreed during the Oklahoma City meeting);
(kVA) (kJ)
Covering 80% of the Raleigh proposal
studied cases based on a tail time of
40 µs
I 5 to 500 3,0 3,0
II 501 to 1667 15,0 15,0
III 1668 to 10000 13,5 15,0
IVa 10001 to 40000 12,5 25,0
IVb 40001 to 160000 50,0 25,0 and 100,0
IVc 160001 to 600000 See note 100,0
Note:
For a minimum limit of 62,5 kJ, 26% of the studied cases will be covered
- In order to optimize and to reduce the size of impulse generators, the limits applicable to each
sub-categories of Category IV, have been changed.
- For transformers belonging to Category IVc, the number of cases that will be covered by the
new impulse generator limit (62,5 kJ instead of 100 kJ) has decreased from 47% (Raleigh's
proposal) to 26% (new proposal with reduce energy).
Modified proposal:
- We propose to change the first paragraph of indent b) of clause 10.3.1.1 of C57.12.90 as
follows:
"The impedance of some windings may be so low that the desired time to the 50% voltage point
on the tail of the wave can not be obtained with available test equipment. For such cases,
shorter waves are considered acceptable provided that:
2- Any generator configurations (available energy) can be used during tests if the impulse waveshape "t 2" parameter is within
the prescribed tolerance (40 s to 60 s).
3- These transformer categories generally belong to transformers classified "Class I" in IEEE C57.12.00. For such
transformers, a minimum impulse generator capacitance of 1,0 F should be used in combination with alternative methods.
2 f t 2 U BIL
2 2
Emin . VA
z U 2
where:
If the calculated impulse generator energy for a particular connection and transformer design is
such that the minimum time to 50% (e.g.: 40 µs) can not be achieved, the manufacturer shall
notify it during the bidding stage. The manufacturer shall also state the strategy that will be
taken to obtain an acceptable waveshape. In case that the minimum recommended impulse
generator energy or capacitance value can not be achieved for a particular transformer
design and test laboratory limitations, shorter waveshapes may be agreed upon the
manufacturer and the user at the time of an order."
Next step(s):