Beruflich Dokumente
Kultur Dokumente
P. L. SPEDDING
Department of Chemical Engineering, Queen’s University of Belfast, Belfast BT9 5AH (U.K.)
M. T. JONES
Health Department, Auckland (New Zealand)
(2)
1. INTRODUCTION
or
Wetted-wall columns have been used exten- d
-= ‘hoRTdpBM
sively in the investigation of mass transfer (3)
X
between gas and liquid. The liquid flows as a DG&
l---T
THERMCOUPLE
2. APPARATUS WELL : . _. ,.
.‘.‘._I
.. . .
glassware such that the wetted length could Fig. 2. Water distributor on the wetted-wall column.
be altered by joining various lengths of pipe
so that no discontinuities occur on the inside Water was supplied from a reservoir via a
wall of the wetted section. Tower heights of pump and a calibrated rotameter capable of
0.723, 1.700, 2.337, 2.980 and 3.538 m were delivering 0 - 0.045 X 10d3 m3 s-‘. The water
used. Calming lengths were provided for air entered at the base of the distributor and rose
inlet and outlet. The lower end of the upper through calming baffles which also acted as
calming length was ground flat. A 15 cm centralizers for the pipe.
length of Perspex tube bored to the inside Water was allowed to build up beyond the
diameter of the pipe formed the upper por- weir level by removing the air bleed plug. The
tion of the wetted section, set below the 50 cm long upper calming section, made of
upper calming length and connected to it by Perspex with a 4.04 cm bore, could be
an enclosing collar. The upper end of this raised or lowered to adjust the gap over the
Perspex tube was bevelled at a 45” angle to weir. The gap was usually set at a distance
TABLE 1
Mass transfer in wetted wall columns
Haslam et al. [8,9] 1923 S02/water 20.3 76.1 2.7 - 2.8 50 - 230 }
of historical interest only
Haslametal. [10] 1924 S02/water 7.62 91.44 1.8 2.5-130
NH 3/water
Greenwalt [11] 1926 H 2S0 4/air; 2.54 78.7 not reported 7.5'- 150 entrance effects studied
dehumidification 5.08 68.7
Hanks and McAdams [12] 1929 NH 3/water 4.95 84.5 1.8 0.6 - 50 solution effect studied
Harte and Baker [13] 1933 CO 2/sodium 2.54 152 0.96 12 liq uor concentration
carbonate- effect studied
bicarbonate
Gilliland and Sherwood [1] 1934 Various liquids/air; 2.67 117 0.79 35 - 490 classic work: end effects
vaporisation studied
Chilton and Colburn [7] 1934 water/air 2.64 170 0.52 33 - 144 classic work
Hollings and Silver [14] 1934 NH 3 , S02. H 2S/ 1 15 0.07 0.1 - 9 general work only
water
Chambers and Sherwood [15] 1937 N0 2/water, S02/ 1.46 95 not reported 20 - 50 classic work: wetting
NaOH; humidi- agents tested
fication
Barnet and Kobe [3] 1941 water/air; 2.54 122 0.07 - 0.68 17 - 350 end effects minimised:
humidification considerable data
Van Krevelen et al. [16] 1949 CO 2/water; 3 30 - 100 not reported 2 - 240. entrance effects studied
humidification
Jackson and Ceaglske [17 ] 1950 various liquids/air; 3.81 183 not reported 60 - 670 intermediate sampling:
vaporisation used considerable data
Emmert and Pigford [18] ]954 O 2, CO 2/water; 2.4 3.87,113.7 0.28 - 1.1 not reported
absorption,
desorption
Cairns and Roper [4] 1954 water/air; 2.29 94.6 0.20 - 1.1 10-155
humidification high humidities and
2.64 94.6 0.53 - 0.57 8 - 40 solute effect studied
Cairns and Roper [5] 1955 water/air;
humidification \. ~,
Lynn et al. [19] 1955 S02/water, HCI, 1.5 12 - 22 0.097 - 0.776 not reported
NaCI solutions ......
Ol
Lynn et al. [20] 1955 S02/water 1.5 1 -5 0.008 - 0.776 not reported (continued) -J
TABLE 1 (continued) ....Cl>
00
Vivian and Peaceman [21] 1956 CO 2/air desorption 2.54 1.9·4.3 0.056·0.798 0·40.7
McCarter and Stutzman [22] 1959 various liquids/air; 7.5 35.6 - 101.6 not reported 19 - 2000 end effects minimised
vaporisation
Haselden and Malaty [23] 1959 NH 3/water 1.27 119 0.015·0.18 not reported rippling studies
Kafesjian et al. [24] 1961 humidification 2.54 101.6 0.036 - 1.31 37·200
Vivian and Behrmann [25] 1965 NH 3/water, NH3 2.77 5.56 not reported not reported
solutions
Vivian and Schoenberg [26] 1968 humidification 2.54 10 0.439 55.5 - 110
Cunningham [27] 1971 humidification 4.04 220 - 410 0.5·1.9 50·400
Cain [28] 1972 humidification 4.04 170·350 0.664,0.419 60·370
Lamourelle and Sandall [29] 1972 He, H 30 2 , CO 2 / 1.588 91.4 - 182.9 not reported 15·96
water
Jones [30] 1975 humidification 4.04 72.3·353.8 0.19·0.92 72 - 354
Hikita and Ishimi [31] 1976 NH 3/H 2S0 4 , 2· 4.1 40,80 0.19 - 0.56 3 - 30
methanol/water
Goodfellow and co-workers 1976, humidification 3.99
152.4 0.3· 2.3 60 - 480
[32,33] 1977 7.79
Hikita and Ishimi [34] 1978 NH 3/H 2S0 4 , 2 40,80 0.19·0.56 3·30 Sh, Gr and interfacial
methanol/water velocity gives data
correlation
169
tube.
Air was taken from the compressed air line,
through a filter, a pressure regulator and a
control valve before being measured by cali-
brated rotameters capable of delivering 0 -
Fig. 3. Wet bulb thermometer holder.
7.5 X 10e3 m3 sl. For flow rates of less than
1.5 X 10d3 m3 s-l the air was passed from the
control valve through a 30 1 stainless steel air temperature was measured with a thermo-
drum which dampened out any fluctuations couple inserted up the air inlet tube to 3 cm
in the flow before it reached the rotameter. from the top. Outlet air temperature was mea-
The air passed to an air heater consisting of a sured using a thermocouple in the centre of
35 cm length of ceramic core wound with the upper calming section, 2 cm above the
Nichrome wire to give about 1 kW of heating. weir. The most difficult temperature to
A combination of an on-off controller and measure was that of the outlet water. As the
d.c. voltage supply to the heater provided water left the transfer section it continued as
control over the air temperature to the a film on the tube wall for 40 cm down to the
column. To minimise heat losses the whole water level. The temperature had to be read
column was insulated with 2.5 cm fibreglass just as the water left the transfer section;
insulation. Even so it took about an hour for therefore a thin thermocouple was inserted
the apparatus to settle to a given set of condi- from the base of the tower so that the junc-
tions. tion was in the film. Radiation effects were
The preheated air passed to a calming accounted for by using shields [ 351, by insu-
section set in the base of the apparatus. It lating the column and also by allowing the
consisted of a centrally placed 150 cm length column to reach steady state before readings
of tube of 2.5 cm bore, designed so as to were taken. The last technique should have
eliminate entrance effects. allowed the column wall and the gas temper-
Monometers were connected to the air atures to equalise and gave rise to no heat
rotameter, to the air inlet tube and just above transfer by radiation. Sufficient thermocouple
the wetted section of the column. wire (usually more than 10 cm), was inserted
The mass transfer rate was found by mea- into the column to minimise problems that
suring the humidities of the inlet and outlet might have arisen due to heat conduction
air. The inlet air was sampled at a point along the wire.
between the reducing valve and the control The thermocouples were read using a
valve. The outlet air was sampled in a by-pass potentiometer with an ice bath as compensa-
system after the air left the tower. The tion and were calibrated using ice, boiling
humidities were measured using wet and dry water and warmed air. For the last of these,
bulb thermometers. These were placed in the thermocouple for calibration was placed
holders (see Fig. 3) such that the velocity in the wet bulb position of one of the ther-
past the wet bulb was about 5 m s-l which mometer holders. A standardised thermom-
occurred when the flow in the by-pass system eter calibrated to 0.01 “C was then placed in
was adjusted to approximately 1 X 10e3 m3 the dry bulb position and air at various tem-
min-‘. peratures blown past at velocities of about
To measure the inlet water temperature a 20 m s-l.
thermometer was inserted through the side of The thermocouples required frequent recal-
the water distributor body at the level of the ibration and although initially they were used
weir. for all temperature measurements they were
All other temperatures were read using subsequently replaced by thermometers
copper-constantan thermocouples. The inlet where possible. When the thermocouples were
170
=
7x1~ d(G,y)
4dA
(10)
N OG =
s
Y,
(1 -Y12(Ye
YBM
-Y)
dY (19)
171
Using the Wiegand [ 431 approximation various heights within the column. This is not
easily done with the wetted-wall column and
1 1 l-y * the humidity can only be measured at the top
N OG= In -
-
; + U-Ye) i Ye-Yi \t I and bottom of the column. Therefore, in
1 2(1 -Y)
order to examine the possibility of a height
and by letting effect experiments had to be carried out using
various heights of column but under the same
conditions of gas and liquid flow. Practical
(20) considerations dictated the possible range of
column heights to be used. Small amounts of
d4 humidification occurred when the column
-
dl
=KGYBM
was short and saturated or near saturated
conditions occurred when the column was
where long. For these reasons, column lengths
between 0.723 and 3.538 m were used. Even
‘G,d 1
- - so, a few of the experimental results at 3.538
4=
@T 2u -Y) m had to be discarded because saturation had
occurred or was close to occurring, and the
+
1
driving force could not be determined accu-
(l-Ye) rately.
No attempt was made to eliminate rippling
(22) in the column and indeed the shortest height
and the slope of the 4 us. 1 plot will be depen- of tower employed ensured that rippling
dent only on KoyBM. occurred. Very short columns have been used
in the past to eliminate rippling but the
lengths employed were well below the mini-
4. EXPERIMENTAL METHOD AND PRELIMINARY
mum height used in this work. Nevertheless,
EXPERIMENTS
in order to investigate whether or not the
Wetted-wall columns have been used exten- degree of rippling affected the mass transfer,
sively as a simple tool for studying aspects of the weir gap at the top of the column was
heat and mass transfer, where the liquid flow closed to less than the final film thickness.
characteristics in particular could be easily The pressure in the distributor forced the
described. Spedding et al. [ 421 have proposed water out of the gap so that it continued
that the height effect in a packed column is down the column for 2 - 3 cm as a high speed
due to the liquid flow characteristics over the thin film. A hydraulic jump effect then took
packing. In a wetted-wall column the liquid place which caused the onset of intense
flow pattern should not change with height rippling for a few centimetres further before
but it would be interesting to ascertain the normal appearance of the film occurred.
whether a height effect does exist and also to No variation could be found between experi-
measure the end effect. ments with normal and forced rippling.
The concept of a simple system does not Indeed, all attempts that were made to elimi-
apply when the basic mass transfer equation is nate rippling failed. Experiments were run
integrated. However eqn. (20) can be devel- with varying amounts of surfactant (1 - 80
oped on the basis of certain reasonable ppm) but again no difference was detected
assumptions. To use the equation the air between these results and those under normal
entering the column must be heated to a circumstances.
temperature such that the heat lost by the air When the water temperature is held con-
exactly balances the latent heat of vaporiza- stant throughout the column, the heat lost by
tion that occurs during the humidification the air is used to vaporise the water, thus
process. This means that the water tempera- enabling the heat transfer coefficient during
ture and the equilibrium partial pressure simultaneous heat and mass transfer to be
remain constant. found. Most investigators have used the tech-
In packed column experiments the gas nique of adjusting the water inlet temperature
phase mole fraction can be measured at to the wet bulb temperature of the exit air so
172
that the water was being vaporised at the constant, the line joining the points at any
wet bulb temperature and the water tempera- specific pair of gas and liquid rates should be
ture would not change. Trial experiments straight and intersect the $ = 0 line at a dis-
showed it to be more difficult to vary the tance from the inlet point equal to the end
water temperature to keep it at the wet bulb effect.
temperature, than to use a heated inlet air The lines on Fig. 4 approximate two
system to maintain constant water tempera- straight lines for each data set. Below a tower
ture. This was probably due to the long height of about 2.4 m, a straight line can be
columns and the particular equipment layout drawn which passes through @ = 0 at an aver-
used in this work. age position of -5 cm. The two plots at a
A series of experiments were run at room water flow of 7 X 1O-6 m s-l, intersect at
temperature and at a temperature above 40 “C! about -4 cm while the two at a flow of
to test the equipment and to check whether 1.1 X 10e5 m sP1 intersect at about -6 cm,
the mass transfer coefficient was in any way but it is not possible to conclude from just
dependent on the inlet gas temperature. Again four data sets that the liquid rate influences
there was no difference between the results the end effect.
at an elevated air inlet temperature of about Above 2.40 m a further series of straight
51 “C and those under normal atmospheric lines is found, of about 5% lower slope in each
operation. case. However it is not possible to conclude
from the four sets of results that the mass
5. MASS TRANSFER RESULTS
transfer coefficient decreased owing to a
height effect. It is far more likely that the
A set of experiments were run under con- apparent decrease in mass transfer coefficient
stant water temperature conditions at two gas is attributable to increased inaccuracy in mea-
and water rates and at each tower height. suring the driving force at the top of the col-
There was some imbalance in the heat, the umn. For example at 3.538 m of column the
worst case involving 3.5% greater heat loss by difference between wet and dry bulb temper-
the air to that used for humidification. A atures was often as low as 3 “C and thus any
graph of @Jus. column height is given in Fig. 4 error would be magnified as the gas came
for the four combinations of air and liquid closer to saturation and the temperature dif-
rates. ference decreased. Indeed, under these condi-
If the mass transfer coefficient Kay,, is tions it is important not to round off figures
during calculation if large errors in @ are to be
avoided.
GAS 3.2 x llJ3,3s-’ LIQUID ,x 1&,,3s-1 -a- - The apparent drop in mass transfer coeffi-
II I, I, l+stj5 ” -
7x,@ 0 --o- - cient could not have been caused by a concen-
n ,, x
tration effect of water in the air of the type
1-1x1f5 ” -
When the data are expressed in the d/x [45] and McCarter and Stutzman [22] when
form there is a gradual increase in the param- the end effect is incorporated into the calcula-
eter with water flow rate for any given tions and using the Reynolds number relative
Reynolds number. This is in direct conflict to the water film. The values of the Chilton-
with the conclusions of Gilliland and Sher- Colburn j-factors agree (within f 20%) with
wood [l] who found that the water rate had the results of the investigators mentioned
no effect on the mass transfer. When they above, and with those of Barnett and Kobe
plotted the mass transfer coefficient against r31.
the Reynolds number relative to the liquid The data obtained from this investigation
velocity, a wide divergence of results was do not agree with those of Grimley [48] or
found, especially between counter-current Emmert and Pigford [49] who found elevated
and co-current experiments. When the results rates of absorption when using very short
of the present work are plotted against the columns and rippling films. A study of the
Reynolds number relative to the liquid film apparatus they describe does not show that
(in the range 3000 - 20 000) there is no sig- any obvious end effect was occurring, but an
nificant difference between the data at vari- end effect could explain the increase in rate.
ous water rates. Hence, by least-squares fit Greenwalt [ll] found that the mass transfer
d coefficient was several times that predicted
- = 0.016 + 0.002Re2*83’ O.O1’ (23) by Gilliland and Sherwood [ 11. This could be
X
partly caused by rippling but is mainly due to
An average for all data gives a Schmidt num- an end effect. It is imperative, especially when
ber of 0.594. If the exponent on this number using short columns, that extreme care is
is 0.44 [l] then taken in designing the ends of the equipment
in order to minimise end effects, and if such a
d
- = 0.020Re,0.83Sc0.44 (24) precedure is not possible it is necessary to
X determine accurately the end effect.
It must be stressed that this equation uses
the air velocity relative to the water film,
calculated using the equation of Danckwerts 6. HEAT TRANSFER RESULTS
[ 401. It is probable that the actual velocity of
the water surface in our experiments was less A relationship in terms of heat transfer can
than this. For example the ripples in the col- also be obtained using similar reasoning to
umn were observed to travel at 50% - 60% of that for mass transfer. Since the water tem-
the predicted velocity. Morris and Jackson perature is constant and it is assumed that no
[45] found that the effective liquid surface heat losses occur
velocity was 70% of the calculated velocity, nd2
assuming streamline flow in the liquid film. Q dA = ‘G,C, dTa4M (26)
For purposes of comparison, the data of
Gilliland and Sherwood [l] for Reynolds and using the transfer equation described by
numbers relative to the water film were corre- Gilliland [ 501
lated by least-squares fit to give
Q = h,(T - T,) (27)
d
- = 0.0197Re,0*84Sc0.44 (25) Equations (26) and (27) can be combined and
X
the first two terms of the equation for C,
which was 9% higher than predictions based substituted to give, on integration
on eqn. (24) at the lower value of the
l/z,, = & = 0.0020’G,d{998.5500 ln(T - T,)
Reynolds number range and 11.8% higher at
the higher value of the range. Certainly the + 0.1431T + O.l431T, ln(T - T,)}Fni& r
agreement is close and is better than when the
correlation is attempted in the manner sug- (28)
gested by the original authors.
The results of the present work agree The results for constant water temperature
closely with those of Van Krevelen and Hof- were used to calculate & and these are
tyzer [46], Pratt [47], Morris and Jackson plotted in Fig. 5. By extrapolating to (bh = 0,
174
100S----l--- I 0 1
I which were used in this investigation (eqns.
GAS LIQUID
3.1 x 18 m351 7x\gdm%- --x-- (20) and (28)) do not rely on a logarithmic
,, II 1.1x165 I, -
4.7 x 183 ” 7x,(j6 14 -__d__ value. Both use point values at the top and
t, l.lXlcj5 ” - bottom of the column. The mass transfer
version does require the use of the Wiegand
approximation, but this has already been
shown to be very accurate for the YBM values
60-1 used [ 421. Hence, using eqns. (20) and (28),
transfer coefficients can be obtained and com-
pared with that found using eqn. (6). This has
been done and in all cases the coefficients
were within 5% of each other. There was no
consistent variation, so it may be concluded
that for the experiments in this investigation
the use of a logarithmic mean value is suffi-
ciently accurate.
-1 t
7. CONCLUSIONS
TOWER HEIGHT m
if it did, its magnitude was beyond the accu- Huntjen, Studies of gas absorption, V: mass trans-
racy of the experiments. fer in film reactors, Rec. Trau. Chim. Pays-Bas, 68
(1949) 221 - 233.
Heat transfer data were also obtained from
17 M. L. Jackson and N. H. Cleagske, Distillation,
adiabatic experiments. A zero end effect on a vaporization and gas absorption in a wetted
heat transfer basis was found using a method wall column, Ind. Eng. Chem., 42 (1950) 1188 -
similar to that for mass transfer. The reasons 1198.
for the difference between mass and heat 18 R. E. Emmert and R. L. Pigford, Interfacial resis-
tance-gas absorption in falling liquid film, Chem.
transfer as far as end effect is concerned
Eng, Prog., 50 (1954) 87 - 93.
remain obscure and must be left for further, 19 S. Lynn, J. R. Straatemeier and H. Kramers,
more detailed investigation. Absorption studies in the light of the penetration
theory, I and III, Chem. Eng. Sci., 4 (1955) 49
57, 63 67.
REFERENCES 20 S. Lynn, J. R. Straatemeier and H. Kramers,
Absorption studies in the light of the penetration
1 E. R. Gilliland and T. K. Sherwood, Diffusion of theory, II, Chem. Eng. Sci., 4 (1955) 58 - 62.
vapours into air streams, Ind. Eng. Chem., 26 21 J. E. Vivian and D. W. Peaceman, Liquid-side
(1934) 516 - 523. resistance in gas absorption, AIChE J., 2 (1956)
2 S. Uchida and S. Maeda, On the influence of fluid 437 - 443.
velocity on heterogeneous reactions, I, J. SOC. 22 R. J. McCarter and L. F. Stutzman, Transfer
Chem. Ind. Jpn., 38s (1935) 625 - 662. resistance and fluid mechanics, AIChE J., 5
3 W. I. Barnett and K. A. Kobe, Heat and vapour (1959) 502 - 505.
transfer in a wetted-wall tower, Znd. Eng. Chem., 23 G. G. Haselden and S. A. Malaty, Heat and mass
33 (1941) 436 - 442. transfer accompanying the absorption of ammo-
4 R. C. Cairns and G. H. Roper, Heat and mass nia in water, Trans. Inst. Chem. Eng., 37 (1959)
transfer at high humidities in a wetted-wall col- 137 - 146.
umn, Chem. Eng. Sci., 3 (1954) 97 - 107. 24 R. Kafesjian, C. A. Plank and E. R. Gerhanrd,
5 R. C. Cairns and G. H. Roper, Uni-directional Liquid flow and gas phase mass transfer in
heat and mass transfer at high humidities in a wetted-wall columns, AZChE J., 7 (1961) 463 -
wetted-wall column, Chem. Eng. Sci., 4 (1955) 466.
221 - 228. 25 J. E. Vivian and W. C. Behrmann, Effect of con-
6 J. M. Coulson and J. F. Richardson, Chemical centration level on gas phase absorption coeffi-
Engineering, Vol. IL, Pergamon, Oxford, 1967, cient, AZChE J., 11 (1965) 656 - 661.
p. 723. 26 J. E. Vivian and T. Schoenberg, Mass transfer
7 T. H. Chilton and A. P. Colburn, Mass transfer rates for vaporization and gas-phase controlled
(absorption) coefficients, Ind. Eng. Chem., 26 desorption in a short wetted wall column, AZChE
(1934) 1183 - 1187. J., 14 (1968) 986 - 988.
a R. T. Haslam, W. P. Ryan and H. C. Weber, Some 27 J. W. Cunningham, Humidification in a wetted
factors influencing the design of absorption appa- wall column, B.E. Thesis, University of Auckland,
ratus, Trans. Am. Inst. Chem. Eng., 15 (1923) 1971.
177 - 194. 28 M. M. Cain, Mass transfer in a wetted wall col-
9 R. T. Haslam, W. P. Ryan and H. C. Weber, Some umn, B.E. Thesis, University of Auckland, 1972.
factors influencing the design of absorption appa- 29 A. P. Lamourelle and 0. C. Sandall, Gas absorp-
ratus, Znd. Eng. Chem., 15 (1923) 1105 - 1108. tion into a turbulent liquid, Chem. Eng. Sci., 27
10 R. T. Haslam, R. L. Hershey and R. H. Keen, (1972) 1035 - 1043.
Effect of gas velocity and temperature on rate of 30 M. T. Jones, Height, end and solute concentration
absorption, Znd. Eng. Chem., 16 (1924) 1224. effects during gas/liquid mass transfer, Ph.D.
1230. Thesis, University of Auckland, 1975.
11 C. H. Greenwalt, Absorption of water vapour by 31 H. Hikita and K. Ishimi, Mass transfer in wetted-
sulfuric acid solutions, Ind. Eng. Chem., 18 wall columns, J. Chem. Eng. Jpn., 9 (1976) 362 -
(1926) 1291 - 1295. 369.
12 W. V. Hanks and W. H. McAdams, Studies in 32 W. B. Goodfellow, Heat and mass transfer in a
absorption, I, Ind. Eng. Chem., 21 (1929) 1034 - wetted wall tower, M.E. Thesis, University of
1039. Auckland, 1976.
13 C. R. Harte and E. M. Baker, Absorption of CO, 33 W. B. Goodfellow, P. L. Spedding and M. T.
in aqueous sodium carbonate-bicarbonate solu- Jones, Mass and heat transfer in a wetted wall
tions, II, Znd. Eng. Chem., 25 (1933) 1128 - column, Pac. Chem. Eng. Conf., 2 (1) (1977)
1132. 39 - 46.
14 H. Hollings and L. Silver, The washing of gas, 34 H. Hikita and K. Ishimi, Mass transfer into lami-
Trans. Inst. Chem. Eng., 12 (1934) 49 - 63. nar gas streams in wetted-wall columns with
15 F. S. Chambers and T. K. Sherwood, Absorption countercurrent gas-liquid flow, Chem. Eng. Com-
of nitrogen dioxide by aqueous solutions, Znd. mun., 2 (1978) 181 - 188.
Eng. Chem., 29 (1937) 1415 - 1422. 35 H. Spence-Gregory and E. Rourke, Hygrometry,
16 D. W. Van Krevelen, P. J. Hoftyzer and P. J. Crosby-Lockwood, London, 1957.
176
36 E. C. Bingham, Fluidity and Plasticity, McGraw- ‘G air molar gas rate (kg mol s-l me2)
37
Hill, New York, 1922, p. 340.
International Critical Tables, McGraw-Hill, New
hDm mass transfer coefficient (kg mol s-l
me2 (mol ratio)-‘)
York, 1928, pp. 5.2, 5.138.
D. M. Himmelblau, Basic Principles and CaZcuZa- hh heat transfer coefficient (W me2 K-‘)
38
tions in Chemical Engineering, 2nd edn., Prentice- AH‘4 logarithmic mean humidity difference
Hall, Englewood Cliffs, NJ, 1974, p. 444. (kg water (kg air-‘)
39 J. H. Perry, Chemical Engineers Handbook, mass transfer coefficient
jD
McGraw-Hill, New York, 1963, pp. 3-206, 3-43.
jh heat transfer coefficient
40 P. V. Danckwerts, Gas-Liquid Reactions,
McGraw-Hill, New York, 1970, p. 73. ‘hi film mass transfer coefficient (s m-l)
41 W. N. Carrier, Rational psychrometric formulae, kh thermal conductivity (W m-l K-‘)
Trans. Am. Sot. Mech. Eng., 33 (1911) 1005 - KG overall mass transfer coefficient (s m-l)
1039. 1 column height (m)
42 P. L. Spedding, M. T. Jones and G. R. Lightsey,
NV molar weight water (kg (kg mol))‘)
Ammonia absorption into water in a packed
tower, II: measurement of mass transfer coeffi- N‘4 molar mass transfer rate water (kg mol
cients, Chem. Eng. J., 32 (1986) 151 - 163. s-l mP2)
43 J. H. Wiegand, Written discussion on “The simpli- NOG number of overall gas transfer units
fied cumulations on diffusional processes”, Trans. partial pressure (kg m-l sC2)
P
Am. Inst. Chem. Eng., 36 (1940) 679 - 681.
APA logarithmic mean partial pressure dif-
44 C. R. Harte and E. M. Baker, Absorption of CO*
in aqueous sodium carbonate-bicarbonate solu-
ference (kg m-r se2)
tions, II, Znd. Eng. Chem., 25 (1933) 1128 - P pressure (kg m-’ s-*)
1132. Q heat transfer rate (W m-2)
G. A. Morris and J. Jackson, Absorption Towers,
45 AQ rate of heat transfer inbalance (W mw2)
Butterworth, London, 1953.
R universal gas constant (J kg mol-’ K-l)
46 D. W. Van Krevelen and P. J. Hoftyzer, Studies of
gas absorption, I: liquid film resistance to gas Re, Reynolds number relative to liquid film
absorption in scrubbers, Rec. Trav. Chim. Pays- SC Schmidt number
Bas, 66 (1947) 49 - 66. T temperature (K)
47 N. R. C. Pratt, The performance of packed X thickness of theoretical film (m)
absorption and distillation columns with partic-
Y mole fraction of water in gas phase
ular reference to wetting, Trans. Inst. Chem. Eng.,
29 (1951) 195 - 214.
48 S. S. Grimely, Liquid flow conditions in packed Greek symbols
towers, Trans. Inst. Chem. Eng., 23 (1945) 225 - density (kg mP3)
P
235.
variable defined in eqn. (20) (s)
49 R. E. Emmert and R. L. Pigford, Gas absorption
accompanied by chemical reactions, AIChE J., 8 :h variable defined in eqn. (28) (W m-r
(1962) 171 - 175. K-r)
50 E. R. Gilliland, Fundamentals of drying and air-
conditioning, Znd. Eng. Chem., 30 (1938) 506 - Subscripts
514.
1 conditions at base of column
2 conditions at top of column
a air
APPENDIX A: NOMENCLATURE
BM logarithmic mean value of inert
A interfacial area for mass transfer (m) equilibrium value
CP specific heat (J kg-’ K-‘) : gas phase
d column internal diameter (m) i interfacial value
D diffusivity (m2 s-l) L liquid phase
G, total molar gas rate (kg mol s-l me2) T total