Release Notes
Open Line Detection IED
Platform Hardware Version: J
Platform Software Version: 31
Publication Reference: P846-RN-EN-1
© ALSTOM 2013. All rights reserved. Information contained in this document is indicative only. No representation or warranty is
given or should be relied on that it is complete or correct or will apply to any particular project. This will depend on the technical
and commercial circumstances. It is provided without liability and is subject to change without notice. Reproduction, use or
disclosure to third parties, without express written authority, is strictly prohibited.
Contents
Chapter 1 Introduction 1
1 Chapter Overview 3
2 Ordering Options 4
Index 39
ii P846-RN-EN-1
Table of Figures
Figure 1: Direct Access menu navigation 9
Figure 2: Default function key PSL 10
Figure 3: Remote Control of Circuit Breaker 11
Figure 4: CB Control logic 12
Figure 5: CB State Monitoring logic 17
Figure 6: VTS logic 22
Figure 7: CTS logic diagram 25
Figure 8: Pole Dead logic 27
Figure 9: Circuit Breaker Fail logic - three phase start 33
Figure 10: Circuit Breaker Fail logic - single phase start 34
Figure 11: CB Fail part 2 35
Figure 12: CB Fail timing 38
Table of Figures P846
iv P846-RN-EN-1
INTRODUCTION
CHAPTER 1
Chapter 1 - Introduction P846
2 P846-RN-EN-1
P846 Chapter 1 - Introduction
1 CHAPTER OVERVIEW
P846-RN-EN-1 3
Chapter 1 - Introduction P846
2 ORDERING OPTIONS
Digit # 1 -4 5 6 7 8 9 10 11 12-13 14 15
Variants Order No.
Open Line Detector P846
Hardware options
Second Rear Comms Port + IRIG-B (modulated) 8
Product Options
Minimal Hardware: 8 Relay Contacts (4 standard & 4 high break) &
A
8 Opto-Inputs, in a 80TE case.
Full Hardware: 32 Relay Contacts (12 standard & 4 high break) &
B
24 Opto-Inputs, in a 80TE case.
Protocol options
Courier 1
DNP3.0 4
Mounting
Flush/Panel Mounting with Harsh Environment Coating M
19" Rack Mounting with Harsh Environmental Coating N
Language
Multilingual - English, French, German, Spanish 0
Software
Date and application Dependant **
Settings Files
Default 0
Customer specific A
Customer engineered version: Hydro Quebec H
Design Suffix
Dual characteristic optos J *
E00043
4 P846-RN-EN-1
MONITORING AND CONTROL
CHAPTER 2
Chapter 2 - Monitoring and Control P846
6 P846-RN-EN-1
P846 Chapter 2 - Monitoring and Control
1 CHAPTER OVERVIEW
As well as providing a range of protection functions, the product includes comprehensive monitoring and
control functionality.
This chapter contains the following sections:
Chapter Overview 7
Circuit Breaker Control 8
CB State Monitoring 16
Voltage Transformer Supervision 20
Current Transformer Supervision 25
Pole Dead Function 27
P846-RN-EN-1 7
Chapter 2 - Monitoring and Control P846
Circuit Breaker control is only possible if the circuit breaker in question provides auxiliary contacts. The CB
Status Input cell in the CB CONTROL column must be set to the type of circuit breaker. If no CB auxiliary
contacts are available then this cell should be set to None, and no CB control will be possible.
For local control, the CB control by cell should be set accordingly.
The output contact can be set to operate following a time delay defined by the setting Man Close Delay.
One reason for this delay is to give personnel time to safely move away from the circuit breaker following a
CB close command.
The length of the trip and close control pulses can be set via the Trip Pulse Time and Close Pulse Time
settings respectively. These should be set long enough to ensure the breaker has completed its open or
close cycle before the pulse has elapsed.
If an attempt to close the breaker is being made, and a protection trip signal is generated, the protection trip
command overrides the close command.
The Reset Lockout by setting is used to enable or disable the resetting of lockout automatically from a
manual close after the time set by Man Close RstDly.
If the CB fails to respond to the control command (indicated by no change in the state of CB Status inputs) a
CB Failed to Trip or CB Failed to Close alarm is generated after the relevant trip or close pulses have
expired. These alarms can be viewed on the LCD display, remotely, or can be assigned to output contacts
using the programmable scheme logic (PSL).
The Lockout Reset and Reset Lockout by settings are applicable to CB Lockouts associated with manual
circuit breaker closure, CB Condition monitoring (Number of circuit breaker operations, for example) and
autoreclose lockouts.
The device includes the following options for control of a single circuit breaker:
● Local control using the IED menu
● Local control using the Hotkeys
● Local control using the function keys
● Local control using opto-inputs
● Remote control using remote communication
8 P846-RN-EN-1
P846 Chapter 2 - Monitoring and Control
CB control using the hotkey is achieved by pressing the right-hand button directly below LCD screen. This
button is only enabled if:
● The CB Control by setting is set to one of the options where local control is possible (option 1,3,5, or
7)
● The CB Status Input is set to '52A', '52B', or 'Both 52A and 52B'
If the CB is currently closed, the command text on the bottom right of the LCD screen will read Trip.
Conversely, if the CB is currently open, the command text will read Close.
If you execute a Trip, a screen with the CB status will be displayed once the command has been
completed. If you execute a Close, a screen with a timing bar will appear while the command is being
executed. This screen also gives you the option to cancel or restart the close procedure. The time delay is
determined by the Man Close Delay setting in the CB CONTROL menu. When the command has been
executed, a screen confirming the present status of the circuit breaker is displayed. You are then prompted
to select the next appropriate command or exit.
If no keys are pressed for a period of 25 seconds while waiting for the command confirmation, the device will
revert to showing the CB Status. If no key presses are made for a period of 25 seconds while displaying the
CB status screen, the device will revert to the default screen.
To avoid accidental operation of the trip and close functionality, the hotkey CB control commands are
disabled for 10 seconds after exiting the hotkey menu.
The direct access functionality is summarised graphically below:
Default Display
HOTKEY CB CTRL
Hotkey Menu
CB closed CB open
TRIP EXIT CONFIRM CANCEL EXIT CLOSE CANCEL CONFIRM CANCEL RESTART
E01209
P846-RN-EN-1 9
Chapter 2 - Monitoring and Control P846
The default PSL logic for the function key mappings is shown below. As you can see, function keys 2 and 3
have already been assigned to CB control in the default PSL.
V02025
10 P846-RN-EN-1
P846 Chapter 2 - Monitoring and Control
below. Where this feature is not required the same output contact(s) can be used for both protection and
remote tripping.
Protection Trip
Trip
Remote
Control
Trip Close
Remote
Control
Close
Local
Remote
Trip Close
E01207
P846-RN-EN-1 11
Chapter 2 - Monitoring and Control P846
&
Close CB 1 Close in Prog
Control Trip
CB Open 3ph
CB healthy window 1
CB Closed 3ph
& Man CB Unhealthy
CB Healthy
C/S window
Any Trip A
External Trip A 1
Any Trip B
External Trip B
Any Trip C
Key:
External Trip C
HMI key
1
External DDB Signal
CB Open
1 Setting cell
CB Open A ph
& Setting value
CB Open B ph
CB Open C ph
Pulse / Timer
Latch
CB Closed
1
CB Closed A ph AND gate & OR gate 1
&
CB Closed B ph
CB Closed C ph S
SR Latch Q
R
V01237
12 P846-RN-EN-1
P846 Chapter 2 - Monitoring and Control
P846-RN-EN-1 13
Chapter 2 - Monitoring and Control P846
14 P846-RN-EN-1
P846 Chapter 2 - Monitoring and Control
P846-RN-EN-1 15
Chapter 2 - Monitoring and Control P846
3 CB STATE MONITORING
CB State monitoring is used to verify the open or closed state of a circuit breaker. Most circuit breakers have
auxiliary contacts through which they transmit their status (open or closed) to control equipment such as
IEDs. These auxiliary contacts are known as:
● 52A for contacts that follow the state of the CB
● 52B for contacts that are in opposition to the state of the CB
All our devices can be set to monitor both of these types of circuit breaker. If the state is unknown for some
reason, an alarm can be raised.
Some CBs provide both sets of contacts. If this is the case, these contacts will normally be in opposite
states. Should both sets of contacts be open, this would indicate one of the following conditions:
● Auxiliary contacts/wiring defective
● Circuit Breaker (CB) is defective
● CB is in isolated position
Should both sets of contacts be closed, only one of the following two conditions would apply:
● Auxiliary contacts/wiring defective
● Circuit Breaker (CB) is defective
If any of the above conditions exist, an alarm will be issued after a 5 s time delay. An output contact can be
assigned to this function via the programmable scheme logic (PSL). The time delay is set to avoid unwanted
operation during normal switching duties.
In the CB CONTROL column there is a setting called CB Status Input. This cell can be set at one of the
following four options:
● None
● 52A
● 52B
● Both 52A and 52B
Where None is selected no CB status is available. Where only 52A is used on its own then the device will
assume a 52B signal from the absence of the 52A signal. Circuit breaker status information will be available
in this case but no discrepancy alarm will be available. The above is also true where only a 52B is used. If
both 52A and 52B are used then status information will be available and in addition a discrepancy alarm will
be possible, according to the following table:
Auxiliary Contact Position CB State Detected Action
52A 52B
Open Closed Breaker open Circuit breaker healthy
Closed Open Breaker closed Circuit breaker healthy
Closed Closed CB failure Alarm raised if the condition persists for greater than 5 s
Open Open State unknown Alarm raised if the condition persists for greater than 5 s
16 P846-RN-EN-1
P846 Chapter 2 - Monitoring and Control
Key:
AND gate & OR gate 1 External DDB Signal
Setting cell
XOR gate X1 Timer
Setting value
n = 1 or 2 x = A, B or C
CB(n) Status Input
None
52A (1 or 3 pole)
52B (1 or 3 pole) &
Both 52A and 52B (1 or 3 pole)
&
X1
&
& 1 CB Open 3 ph
&
CB Aux 3ph(52-B)
&
1 CB Status Alarm
&
&
X1
&
&
CB Aux (x)ph(52-B)
&
V01238
P846-RN-EN-1 17
Chapter 2 - Monitoring and Control P846
18 P846-RN-EN-1
P846 Chapter 2 - Monitoring and Control
P846-RN-EN-1 19
Chapter 2 - Monitoring and Control P846
The first condition would require VTS to block the voltage-dependent functions.
In the the second conditon, voltage dependent functions should not be blocked, as tripping is required.
To differentiate between these two conditions overcurrent level detectors are used (VTS I> Inhibit and VTS
I2> Inhibit). This will prevent a VTS block from being issued in case of a genuine fault. These elements
should be set in excess of any non-fault based currents on line energization (load, line charging current,
20 P846-RN-EN-1
P846 Chapter 2 - Monitoring and Control
transformer inrush current if applicable), but below the level of current produced by a close-up three-phase
fault.
If the line is now closed where a three-phase VT failure is present, the overcurrent detector will not operate
and a VTS block will be applied. Closing onto a three-phase fault, however, will result in operation of the
overcurrent detector and prevent a VTS block being applied.
P846-RN-EN-1 21
Chapter 2 - Monitoring and Control P846
VA
Comparator for Overvalues
VTS PickupThresh
VB
1
1 & S
VTS PickupThresh
Q
VC R 1
& VTS Slow Block
VTS PickupThresh
Delta IA
1 & VTS Fast Block
Hardcoded threshold
Delta IB
1 & S
Q
Hardcoded threshold
R
Delta IC
Hardcoded threshold
V2
MCB/VTS
VTS Status
Indication
Blocking
1 S 1 VT Fail Alarm
Any Pole Dead & Q
R
&
VTS Acc Ind
V01239
22 P846-RN-EN-1
P846 Chapter 2 - Monitoring and Control
The NPS voltage and current detection criteria (used for the case when one or two voltage inputs are lost) is
inhibited if an Any Pole Dead signal is present.
P846-RN-EN-1 23
Chapter 2 - Monitoring and Control P846
24 P846-RN-EN-1
P846 Chapter 2 - Monitoring and Control
Note:
The product uses one CT for the line current and one CT for the surge arrester current.
VN
Setting cell
Setting value
Comparator Timer
for Overvalues
P846-RN-EN-1 25
Chapter 2 - Monitoring and Control P846
than the threshold set by CTS VN< Inhibit. A CTS alarm is generated after a short time delay defined by the
setting CTS Time Delay.
26 P846-RN-EN-1
P846 Chapter 2 - Monitoring and Control
VA
Hardcoded threshold
IB
VB
Hardcoded threshold
IC
VC
1 Any Pole Dead
Hardcoded threshold
VTS Slow Block
& All Poles Dead
CB Open 3ph
P846-RN-EN-1 27
Chapter 2 - Monitoring and Control P846
28 P846-RN-EN-1
CB FAIL PROTECTION
CHAPTER 3
Chapter 3 - CB Fail Protection P846
30 P846-RN-EN-1
P846 Chapter 3 - CB Fail Protection
1 CHAPTER OVERVIEW
The device provides a Circuit Breaker Fail Protection function. This chapter describes the operation of this
functions including the principles, logic diagrams and applications.
This chapter contains the following sections:
Chapter Overview 31
Circuit Breaker Fail Protection 32
P846-RN-EN-1 31
Chapter 3 - CB Fail Protection P846
You can configure the CBF elements CB Fail 1 Timer and CBF Fail 2 Timer to operate for trips triggered by
protection elements within the device or by using an external protection trip. You can do the latter by
allocating one of the opto-inputs to the External Trip DDB signal in the PSL.
Resetting of the CBF is possible from a breaker open indication (from the relay’s pole dead logic) or from a
protection reset. In these cases resetting is only allowed provided the undercurrent elements have also
reset. The resetting mechanism is determined by the settings Volt Prot Reset and Ext Prot Reset.
32 P846-RN-EN-1
P846 Chapter 3 - CB Fail Protection
ZCD IA<
ZCD B<
CB Fail Alarm
External Trip EF S
Q
IN< Start R Note on SR Latches
1 All latches are reset dominant and are
ZCD IN<
triggered on the positive edge. If the edge
CBF NonI Trip S occurs while the reset is active, the
Q detection of the edge is delayed until the
Volt Prot Reset & R reset becomes non-active.
Prot Reset & I< 1
I<Only Key:
CB Open & I<
External DDB Signal
&
All Poles Dead Hidden DDB Signal
Ext. Trip 3ph S
Q Setting cell
Ext. Prot Reset R
& Setting value
Prot Reset & I< 1
I<Only
AND gate & OR gate 1
CB Open & I<
&
All Poles Dead S
SR Latch Q Timer
R
V00725
P846-RN-EN-1 33
Chapter 3 - CB Fail Protection P846
External Trip A S
Q
IA< Start R 1 CBFExtPhAStart
1
ZCD IA<
&
CB Fail Alarm CBFExtPhBStart
External Trip A S
Q
CBFExtPhCStart
Ext. Prot Reset & R
Prot Reset & I< 1
I<Only
External Trip B S
Q
IB< Start R 1
1
ZCD B<
&
CB Fail Alarm
External Trip B S
Q
Ext. Prot Reset R
&
Prot Reset & I< 1 Note on SR Latches
I<Only All latches are reset dominant and are
CB Open & I< triggered on the positive edge. If the edge
& occurs while the reset is active, the
Pole Dead B detection of the edge is delayed until the
reset becomes non-active.
External Trip C S
Q Key:
IC< Start R 1
1 External DDB Signal
ZCD C<
& Hidden DDB Signal
CB Fail Alarm
Setting cell
External Trip C S
Q Setting value
Ext. Prot Reset R
&
Prot Reset & I< 1 AND gate & OR gate 1
I<Only
CB Open & I< S
& SR Latch Q Timer
Pole Dead C R
34 P846-RN-EN-1
P846 Chapter 3 - CB Fail Protection
CB Fail 1 Status
Enabled
&
CBF3 PhStart 1 Bfail1 Trip 3ph
1
CBFExtPhAStart
& 1 CB Fail Alarm
1
CBFExtPhBStart Bfail2 Trip 3ph
&
1 Note on SR Latches
CBFExtPhCStart All latches are reset dominant and are
triggered on the positive edge. If the edge
occurs while the reset is active, the
CB Fail 2 Status detection of the edge is delayed until the
Enabled reset becomes non-active.
&
CBF3 PhStart 1 Key:
1
CBFExtPhAStart
External DDB Signal
&
Hidden DDB Signal
1
CBFExtPhBStart
& Setting cell
1 Setting value
CBFExtPhCStart
AND gate & OR gate 1
S
SR Latch Q Timer
R
V00634
The Remove I> Start and Remove IN> Start settings are used to remove starts issued from the overcurrent
and earth elements respectively following a breaker fail time out. The start is removed when the cell is set to
Enabled.
P846-RN-EN-1 35
Chapter 3 - CB Fail Protection P846
36 P846-RN-EN-1
P846 Chapter 3 - CB Fail Protection
For any protection function requiring current to operate, the device uses operation of undercurrent elements
to detect that the necessary circuit breaker poles have tripped and reset the CB fail timers. However, the
undercurrent elements may not be reliable methods of resetting CBF in all applications. For example:
● Where non-current operated protection, such as under/overvoltage or under/overfrequency, derives
measurements from a line connected voltage transformer. Here, I< only gives a reliable reset method
if the protected circuit would always have load current flowing. In this case, detecting drop-off of the
initiating protection element might be a more reliable method.
● Where non-current operated protection, such as under/overvoltage or under/overfrequency, derives
measurements from a busbar connected voltage transformer. Again using I< would rely on the feeder
normally being loaded. Also, tripping the circuit breaker may not remove the initiating condition from
the busbar, and so drop-off of the protection element may not occur. In such cases, the position of the
circuit breaker auxiliary contacts may give the best reset method.
P846-RN-EN-1 37
Chapter 3 - CB Fail Protection P846
CBF resets:
1. Undercurrent element asserts
2. Undercurrent element asserts and the
breaker status indicates an open position
3. Protection resets and the undercurrent
Fault occurs element asserts
CBF Safety
Protection Maximum breaker reset margin
Normal operating time clearing time time time
operation
t
Note:
All CB Fail resetting involves the operation of the undercurrent elements. Where element resetting or CB open
resetting is used, the undercurrent time setting should still be used if this proves to be the worst case.
Where auxiliary tripping relays are used, an additional 10-15 ms must be added to allow for trip relay operation.
38 P846-RN-EN-1
P846 Index
B S
Back Cover 42 Setting Guidelines (CB fail Timer) 37
Setting Guidelines (Undercurrent) 38
C Subsidence Current 32
CB Control DDBs 13
CB Control Logic 12 V
CB Control Settings 13 Voltage Transformer Supervision 20
CB Fail DDB signals 36 VTS DDB Signals 23
CB Fail Protection 29 VTS Implementation 21
CB Fail Settings 36 VTS Logic 21
CB Healthy Check 11 VTS Settings 23
CB State Monitoring 16
CB State Monitoring DDBs 18
CB State Monitoring Logic 17
CB State Monitoring Settings 18
Chapter Overview 3, 7, 31
Circuit Breaker Control 8
Circuit Breaker Fail Implementation 32
Circuit Breaker Fail Logic 33
Circuit Breaker Fail Protection 32
Circuit Breaker Fail Timers 32
CTS DDB Signals 26
CTS Implementation 25
CTS Logic 25
CTS Settings 26
Current Transformer Supervision 25
I
Introduction 1
L
Local Control using the Direct Access Keys 8
Local Control using the Function Keys 9
Local Control using the IED Menu 8
Local Control using the Opto-inputs 10
Loss of all Three Phase Voltages 20
Loss of One or Two Phase Voltages 20
M
Monitoring and Control 5
O
Ordering Options 4
P
Pole Dead DDB Signals 28
P846-RN-EN-1 39
Index P846
40 P846-RN-EN-1
Alstom Grid
www.alstom.com/grid/contactcentre/
www.alstom.com