Sie sind auf Seite 1von 1

Electrical installation 109

External power supply for the control unit (XPOW)


External +24 V (2 A) power supply for the control unit can be connected to terminal
block XPOW. Using an external supply is recommended if
• the control board needs to be kept operational during input power breaks, for
example, due to continuous fieldbus communication
• immediate restart is needed after power breaks (that is, no control board power
up delay is allowed).

AI1 and AI2 as Pt100, Pt1000, PTC and KTY84 sensor inputs (XAI, XAO)
Three Pt100, Pt1000 and PTC sensors or one KTY84 sensor for motor temperature
measurement can be connected between an analog input and output as shown
below. Do not connect both ends of the cable shields directly to ground. If a capacitor
cannot be used at one end, leave that end of the shield unconnected.

1…3 × Pt100/Pt1000/PTC or 1 × KTY XAI


AIn+ 1)
AIn-

XAO
T T T 2)
AOn
AGND

3.3 nF
> 630 V AC

1) Set the input type to voltage with switch J1 for analog input AI1or with J2 for analog input
AI2. Set the appropriate analog input unit to V (volt) in parameter group 12 Standard AI.
2) Select the excitation mode in parameter group 13 Standard AO.

WARNING! As the inputs pictured above are not insulated according to


IEC 60664, the connection of the motor temperature sensor requires double or
reinforced insulation between motor live parts and the sensor. If the assembly does
not fulfill the requirement, the I/O board terminals must be protected against contact
and must not be connected to other equipment or the temperature sensor must be
isolated from the I/O terminals.

Das könnte Ihnen auch gefallen