PT TAIYO SINAR RAYA TEKNIK

Senayan Tower 2 Project


DOOR LOUVER CALCULATION FOR TOILETS (TYPICAL FLOOR)

FORMULA : A = (Vol / v) / effective free area (EFA)

where: A = Projected Door louver area


Vol = volume of air
v = velocity of air (1.5 m/s)
EFA = 60%

FOR MALE TOILET:


Vol of Exhaust at Male toilet = 935 CMH
Thus,

A = (0.259 / 1.5) / 0.6 = 0.289 m2


= 650 mm x 450 mm Door louver size

FOR FEMALE TOILET:


Vol of Exhaust at Female toilet 765 CMH
Thus,

A = (0.213 / 1.5) / 0.6 = 0.236 m2


= 600 mm x 400 mm Door louver size

FOR EXE TOILET:


Vol of Exhaust at Exe toilet 510 CMH
Thus,

A = (0.142 / 1.5) / 0.6 = 0.157 m2


= 600 mm x 300 mm Door louver size
0.260

0.213

0.142