SF6-circuit
breaker
ABB Switchgear
The HPA circuit breaker
Arc
Main contact
contact
Nozzle
Moving
cylinder Fixed
plunger
The HPA breaker works according to the cylinder moves downwards, whereupon the
puffer principle, implying that when upper main contact opens and the current
breaking, the gas is compressed between a commutes over to the arc contact. At the
fixed plunger and a moving cylinder and same time, the gas in the cylinder is com-
then blown on to the arc between the fixed pressed. When the nozzle has left the arc
and moving arc contacts (see figure). contact, the compressed gas is blown along
When the breaker is closed, the current the arc and cools it. The breaking process is
flows via the main contacts and the cylinder. completed as the current passes through
When a tripping impulse is given, the zero.
Breaking poles
The casing for the breaking poles is made casing can under no circumstances “dis-
of cast epoxy resin. The poles are integrate“ due to negligence, for instance
Exploded HPA breaking thoroughly if it should be dropped during transport.
pole.
vacuum-dried The worst that can happen is that the
after assembly casing cracks and the gas pressure drops.
and then sub- To further increase their reliability, the
jected to breaking poles can be provided with
pressure and temperature-compensating transducers
sealing tests. The that provide an alarm at the lowest gas
low gas pressure pressure permissible upon breaking of full
(2.5 bar over- short-circuit current.
pressure) and the However, the safety margins are so
small volume (12 large that the poles can cope with
dm3) mean that the breaking of rated current even without
breaking pole’s overpressure.
Breaking gas
SF6 (sulphurhexafluoride) gas possesses a
unique combination of properties that
makes it extremely suitable for use in
circuit breakers. This has been confirmed
by service experience from more than
25,000 HPA breakers installed throughout
the world.
SF6 gas has an insulation strength some
three times higher than that of air at an
overpressure of 2 bar, which is even
higher than that of transformer oil.
Phase distance
640 mm
367 mm
90 mm
185 or 210 mm
139 mm
3.6 - 12 kV: 617 mm, 15 - 30 kV: 717 mm 3.6 - 12 kV: 622 mm, 15 - 30 kV: 747 mm
Principal data for HPA
Type testing has been carried out in accord- Holland, at IREQ in Canada and at Powertest
ance with IEC 56 and ANSI c37.09. in the U.S.A.
The short-circuit tests were performed at A certificate and test report can be
ABB’s laboratory in Sweden, at KEMA in obtained upon request.
Rated holding voltage with surge testing .....................................kV ...........................................95 .......................................125 ....................................150