HAEFELYN

HIGH VOLTAGE TEST

Power line filters type NLFA

Description

For the reduction of line carried noise from the mains. The power line filter filters both phases and
is connected to ground. Tl¡e filter is built into the cubicle of air insulated regulating transformers
or attached to their tank. Special arrangements are possible for big systems depending of local
installation conditions.

Their power rating is adapted to regulating transformer rated power.

Typical insertion loss per phase measurecl


at 50 o 150 e¿, MIL-STD 22A A 80 dB
in the following frequency range of 14 kH2...10 MHz

Gompensaling reactor type KDL

Descriptionl
I

For the compensation of the reactive power of capacitive test


objects

connected ppwer filter can be kept small.


The compedsating reactor comprises usually 3 inductors which can
be combineQ to achieve Ltp to 7 different power combinations. The
re-connectioft is basically done manually. Upon request (option), a
Compensating reactor type
remote re-cÓnnect¡on witfr sw¡tches actuated from the controls can KDL 180
be offered.

Technical d ta of the KDL compensating reactor ser¡es

Rated püwer Rated voltage

KDL 180
kVA cont. duty tv 1.1 x 1.2x 1.0
KDL 360 1,2x 1.2x 1.0
KDL 9OO 1.6x1.3x1.4
1'000 2.5 x 1.3 x 1.5
1',000 2,7x1.4x1.5

As the com nsating ieactors ale designed specifically to the system specification, only a few
examples ar given in the above table.
HAEFELYnK{n
HIGH VOLTAGE TEST

Low voltag protection device type NSP


t

Description

Used to prevent inadmissíble high recovery over-voltages on the test transformer in case of
disruptive discharges. on the test object. The low voltage protection device NSp acts by opening
the power supply and by short-circuiting the test transformer within a few hundred micróse'condsl
This avoids repetitive flash-overs in the test object.

Regulating Test transformer PZ(T)


transformer
"TL
/STO

Opening switch'for
disconnecting the
power supply

Closing switch for


short-circuiting the
pr¡mary w¡nding

Ac test,rl"former type Pz(r)(L)

'1
Descriptio^f
r

Test transfolrmers are used for the generation


of high AC rloltages, and are part of a complete
test systeml The Pz(T) type test transformers
are of the so-called insulating shell design. The
merits of tfrii design are:

ú small d¡mensions and reduced floor space


requirements in the test laboratory
. Cascade connections by superimpos¡ng two,
three or four transfonTrer units, w¡thout an
additional requirement in floor space (pzr
transformers only).

Generat dJú¡gn
i
The iest tfinrtormer are ür the insulating sheil
design wih metallic cover and base. The
insulating lcylinder is 'rlrade of reinforced
Fibreglass,l covered wiÜr a moisture-rejecting
pa¡nt. The IPZT transforrners have a tertiary
winüing. Tnr test trar¡sformers are
coqpletely lfilled with oil. The remaining air
not

volúme allofvs an oil expansion according to its


temperaturi. Iesf t¡ansfotmer cascade rated 200 kV; 0.7 A
\t I
HLEFELY^**
HIGH VOLTAGE TEST
I

I
The windings are of layer-wo-und design with a high capacitive coupling between layers and
turns. This provides a high transient voltage withstand capability in case of external
td.rign
breaKdovlns.

PrimarL,rding

The primary winding is divided into two groups. When the two winding groups are connected in
parallel and the regulating transformer is set to 100 7o voltage, the transformer reaches its
nominal ,voltage. When the two winding groups are connected in series, only 50 o/" of rated
voltage irre attained with the same regulating transformer setting. This allows to test at low
voltages livith higher precision.

Dielectrid
lr t

I
The dielectric materials consist of paper, transformer board and transformer oil. The insulating oil
is Shelloil Diala D.

Air dehumidifier

The cover of the transformer


houses an Orange-gel breather to
prevent the ingress of moisture.

Cotrpling (tertiaü winding.

The transformers for cascade


operation type PZT & PZTL have
a coupling winding rated in
w¡th the cascade
l:i;'o1nce
ov e r-vott agep rotelion
Surge prrestors are installed on
the prim ary winding connections
and tol ground, to protect the
transforfner against over-voltages
in the cáse of flashovers.
I

Layout of a fesf trcnsformer cascade 800 kV, 2,5 A

10
-I{AEFELYNT
HIGH VOLTAGE TTST

fl
Gro^pensaiion. Only PZT'transformers

To compensate the capacitive load, an..iron-cored compensating reactor with air gaps is
connected in parallel with the coupling winding of the test transformei. The compensating-reactor
allows a reduction il
lle input power and, in the case of cascade circuits, á uniform- voltage
distribution in the individualwindings. This reactor is placed on the transformer upper cover.

Cooling

The transformers w¡th high output currents or high duty cycles house an upper cooling-cover. The
cooling equipment consists of a tank with cooling ribs. The insulating oir is conductedlrough this
tank by natural convectiorr.

Top electrode

Depending of the transformer rated voltage, a top electrode is placed on its upper cover. The top
electrode is either an aluminium toroid or a Polycon electrode.

Base frarne

Normally the test transforrrrer is placed directly on the floor. Upon request, the base frame can be
equipped with air-cushions.

lnterconnection of ' frsf


transformers
fseveral
lndividual test transformers can be
connectecl both in series (cascade)
for an increase of the output voltage,
and in parallel for an increase of the
output clrrrent. Moreover, three-
phase configuration can be set up. E
b
ET
E
EI
I Eg

,,lro

Layout of fesf transformer 3OO kV, 1 A

:t
:l

11
E HtYN
OLTAGE TEST

Dimension and Weights (some examples only)

Transformei type Voltage U¡ Diameter Helght Weight of oll Total welght


Pz(rxL) approx. net, approx.

[*" m m kg kg

PZT 100-0.1t) ¡ 100 0.66 0.73 B5 290


PZTL l ooFo ,25 I too 0.85 0.70 110 385
PZT 100-b .70 100 1 .30 1.20 440 1440
PZ gO0-1r.0 300 2.40 3.00 2'1 00 5'000
PZ 300-1 .5 300 2.40 3.00 2',70A 7',600
PZ 300-2.5 30c) 2.50 3.50 3'200 8',200
PZ 300-4.0 300 2.50 3.50 3'200 8'200
PZ 400-1.0 400 2.40 3.30 2'900 5',500
PZ 400-1.5 400 2.40 3.40 3'600 9'500
PZ 400-2.5 400 2.50 3.50 5'500 13'000
PZ 400-4.0 400 2.50 3.50 5',500 13'000
PZ 500-1.0 2.40 3.60 6'000 12'000

I
Otli*, uon! n¡'' ürrrrent or chrty cycles are possible upon request !

300 kV cascade with 4 PZTL 100-A.25 transformers

12