Sie sind auf Seite 1von 2

4 X 360 MW Thermal Power Station at Ucchipinda

Design Calculations for RR Masonry Raw Water Reservoir

STABILITY CHECK FOR COMPOUND WALL

Stability Check

INPUT:

Width of wall at Top B1 = 0.15 m

Width of wall at Bottom B2 = 0.23 m

Height of Wall Above FGL h1 = 2.00 m

Height of Wall Below FGL h2 = 1.00 m

Total Height of wall h = 3.00 m

Angel of repose of soil Φ = 30.00 Degree

Weight of Brick Masonry ωM = 19 KN/M3

Weight of Soil (saturated) ωS = 19.4 KN/M3

Weight of Water ωw = 10.00 KN/M3

Surcharge load q = 0.00 KN/M2

Co-efficient of friction µ = 0.55 (assumed)

Ka = (1- Sin 300)/(1+ Sin 300) Ka = 0.33

0.15M

2M

FGL

1M

NGL A

0.23M
M

CALCULATION:

Critical Condition 1: Oneside soil, otherside empty condition

Distance Moment
Weight
S.No Description of C.G about B
KN
from B KN.M

Horizontal load

1 Earthpressure = (0.5 x Ka x ωS x h1 x h1) 3.23 0.33 1.08

2 Surcharge = (Ka x q) 0.00 0.50 0.00

Total 3.23 ΣMO 1.08

Vertical load

1 W1 = (h1 x B1 x ωM) 5.70 0.155 0.88

2 W2 = (h2 x B2 x ωM) 4.37 0.115 0.50

Total Weight - ΣW 10.07 ΣMR 1.39

FICHTNER INDIA 5
4 X 360 MW Thermal Power Station at Ucchipinda
Design Calculations for RR Masonry Raw Water Reservoir

Taking Moment about B


Total Overturning Moment ΣMO = 1.08 KN.M

Total Resisting Moment ΣMR = 1.39 KN.M


Net Moment = (ΣMR-ΣMO) ΣM = 0.31 KN.M
Factor of safety against Sliding = (µXΣW)/PH FS = 1.71 >1.2 Hence Safe
Factor of safety against Overturning = ΣMR/ΣMO FO = 1.29 >1.2 Hence Safe

Distance of CG from B = ΣM/ΣW X' = 0.03 m

Eccentricity = (B2/2)-X' e = 0.084 m


Allowable Eccentricity = B2/6 ea = 0.038 m Safe

Base pressure ΣW/Area = 43.78 KN/m 2


< SBC 115 KN/m2

FICHTNER INDIA 6