VACUTAP® V R
On-Load Tap-Changer
for Regulating Transformers
Types and variants of VACUTAP® VRC, VRE / OILTAP® M, RM Types and variants of VACUTAP® VRD, VRF, VRG / OILTAP® R
Um 72,5...245 kV
Um 72,5...245 kV
3-phase 3-phase 3-phase 3-phase
Um 72,5...245 kV
Um 72,5...245 kV
VRC III 400Y M III 350Y
VRC III 550Y M III 500Y
VRC III 700Y M III 600Y VRE III 700Y RM III 600Y
VRD III 1000Y R III 1200Y
2-phase VRD III 1300Y R III 1200Y VRF III 1300Y R III 1200Y
VRC II 402 M II 352 2-phase
VRC II 552 M II 502 VRF II 1302 R II 1202
VRC II 702 M II 602
1-phase 1-phase
VRC I 401 M I 351 1-phase 1-phase
Um 72,5...300 kV
Um 72,5...300 kV
Um 72,5...300 kV
Um 72,5...362 kV
VRC I 551 M I 501 VRD I 1301 M I 1203 VRF I 1301 R I 1201
VRC I 701 M I 601 VRE I 701 RM I 601 R I 1201
VRG I 25022)
VRC III 400Y
VRF I 25022)
VRE III 700Y
On-load tap-changer
VRG I 2503
VRG I 3003
VRG I 1602
VRG I 1301
VRD I 1301
VRC I 1301
VRG I 2102
VRC I 1001
VRE I 1602
VRE I 1301
VRF I 2503
VRF I 3003
VRF I 1602
VRE I 1001
VRF I 1301
VRF I 2102
VRC I 401
VRC I 551
VRC I 701
VRE I 701
Number of phases and application 31) 31) 1 31) 1 11 1 31) 1 1 1 1 31) 31) 31) 1 1 1 1 1 1 1
Max. rated through-current Ium (in A) 400 550 550 700 700 400
1000 1300 700 700 1000 1300 1600 1000 1300 1300 1300 1300 1600 2100 2500 2500 3000
Rated short-time withstand current (in kA) 6 8 8 10 10 612 15 10 10 12 15 24 12 15 15 15 15 20 24 25 25 30
Rated short-circuit duration (in s) 3 3 3 3 3 33 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3 3
Rated peak withstand current (in kA) 15 20 20 25 25 15
30 37,5 25 25 30 37,5 60 30 37,5 37,5 37,5 37,5 50 60 62,5 62,5 75
Max. rated step voltage Uim (in V)3) 3300 3300 3300 3300 3300 3300
3300 3300 4000 4000 4000 4000 4000 3300 3300 4000 3300 4000 4000 4000 4000 4000 4000
Step capacity PStN (in kVA) 1320 1500 1500 1500 1500 1320
1500 1500 2800 2800 3000 3000 6000 1500 1500 3000 1500 3000 6000 6000 6000 6000 6000
Rated frequency (in Hz) 50...60 50...60
Operating positions Without change-over selector: max. 18, with change-over selector: max. 35 Without change-over selector: max. 18, with change-over selector: max. 35
1) Neutral point 2) Forced current splitting by two parallel winding branches required 3) The maximum rated step voltage may be exceeded by 10% due to overexcitation of the transformer if the step capacity is limited to its rated value.
ACHTUNG !! Seite wird um 2cm auf 19cm verkürzt !!
VACUTAP® VR … – Developed for the future
Advantages VACUTAP®:
Important to know:
Step capacities 4)
4500
4000
VRE III 700Y
VRE I 701 3000 kVA 6000 kVA
3500
1500 kVA
3000
VRE I 1001
rated step voltages Ui [ V ]
2500
VRF I 1301 VRF I 1602 VRF I 2102 VRF I 25022 VRF I 3003
1500
1000
VRD III VRD III 1300Y
1000Y VRD I 1301
500 VRC I 1001 VRC I 1301
0
0 200 400 600 800 1000 1200 1400 1600 1800 2000 2200 2400 2600 2800 3000 3200
rated through-currents Iu [A]
4) Only applies to network service. When used for industrial transformers, please contact us.
©Maschinenfabrik Reinhausen GmbH Phone (+49) 9 41/40 90-0
www.reinhausen.com Falkensteinstrasse 8 Fax (+49) 9 41/40 90-1 11
93059 Regensburg E-mail: sales@reinhausen.com
Please note: The data in our publications may differ from the data of devices delivered.
We reserve the right to make changes without notice.
IN206/05en – 07/03/2000 – 206/05/01/0 – F0081704 · Printed in Germany