137-SS-01-FA-014
1. Project Specification:- P6000CFP.00010.30.014
(Design Guidilines for FGS Detector Systems.
2. Overall F&G Detection System Block Diagram -
A
P6011MAA-000-88-5-B031. A
137-ASD-001
VESDA PANEL
225
B B
Naming Philosophy
To Switch Gear AAA-BBB-CCC
Room Void AAA: Unit/Facility Code
BBB: Equipment Code (ASD)
POWER SUPPLY UNIT CCC: Serial Number
225
WITH BACKUP BATTERY
(VPS-300US-220)
40
PIPE-2
PIPE-3
C C
137-ASD-001
10
3
40
40
1630
225
BACKUP BATTERY
TYPE - C
40
40
120
TEXT HEIGHT : 3mm
LABEL LOCATION : INSIDE
THICKNESS : 2mm
1520
D 65 D
400
400
400
HARD WIRED CONNECTION to FACP
MODULE BOX TRANSFORMER BOX
FIRE 1
~
300 170
FIRE 2
~ ~ ~
435
POWER FAULT
440
E E
INSTRUMENT ROOM KNPC CLEAN FUELS PROJECT
Ref. Sheet:XX
(SCALE-N.T.S)
FAULT SIGNAL
POWER CONSUMPTION @ 24 VDC 10 W JOB. NO. 0-6798-2 Doc Type Code G71
F F
VESDA VLP DETECTOR DIAMENSIONS 350mm (W) x225mm (H) x 125mm (D) COMPANY REV.
DOC. No. VP-PG2181-019-A-137-SS-01-G71-080
POWER SUPPLY UNIT VESDA VLP DETECTOR WEIGHT 4.0 KG
PO NO. 0-6798-PJ2181-019-A1
SAMPLING NETWORK
CLEAN FUELS PROJECT KUWAIT
AGGREGATE PIPE LENGTH 200 MTR.
MINA AL-AHMADI REFINERY
MAX. SINGLE LENGTH 100 MTR.
G GENERAL ARRANGEMENT DIAGRAM OF FIRE ALARM PANEL (137-SFP-001) G
MIN. FLOW PER PIPE 15 LITER / MIN.
FOR PACKAGED SUBSTATION 137-SS-01
BACKUP BATTERY PIPE MOLDING DESIGN TOOL ASPIRE2 (BLAST RESISTANCE)
2
AREA COVERAGE 2000 M
PIPE SIZE
EXTERNAL DIA. 25 MM Gulf Safety & Fire
INTERNAL DIA. 15 - 21 MM
GULF SAFETY Protection Services Co. W.L.L.
PROGRAMMABLE RELAYS 7 RELAYS
REV.
VENDOR DWG NO. 137-SS-01-FA-014
07
SHEET (A3) 15 OF 16
1 2 3 4 5 6 7 8 9 10
CONFIDENTIAL AND COPYRIGHT PROPERTY OF AL-AHLEIA SWITCHGEAR CO.
A3