Sie sind auf Seite 1von 7

Dept.

of Electrical Engineering Rewa Engineering College, Rewa

REWA ENGINEERING COLLEGE, REWA

Department of Electrical Engineering

EE-5003 Switchgear and Protection Lab


Electrical Engineering, V-Semester

Prepared by
Durgesh Choudhary
Assistant professor
Electrical Engineering Dept.
Dept. of Electrical Engineering Rewa Engineering College, Rewa

List of Experiments

1. Determination of drop out factor of an instantaneous over current relay.


2. Determination of operating characteristic of IDMT relay.
3. Determination of operating characteristic of differential relay.
4. Study and operation of gas actuated protective relay.
5. Study and operation of static over current relay.
6. Determination of transmission line parameters using MATLAB.
7. Analysis of power system faults (Symmetrical & Asymmetrical) using
MATLAB.
8. Study of SF6 circuit breaker
9. Protectional simulation study of generator, Transformer, Feeder & Motor
protection.
Dept. of Electrical Engineering Rewa Engineering College, Rewa

Experiment-1
Objective- Determination of drop out factor of an instantaneous over current relay.
Dept. of Electrical Engineering Rewa Engineering College, Rewa

Experiment-2
Objective- Determination of operating characteristic of IDMT relay.
Apparatus Required: 1) Timer
2) IDMT relay (MODEL NO.ICM-21NP))
3) Auxiliary D.C. supplies = 110V
4) 1 phase Dimmer stat = 230V, 10A
5) Ammeter AC (0-15A)
6) Rheostat (38 ohm, 8.5 Amp)
7) Experiment Kit
8) Connecting wires

Procedure:
1. Make the connection as shown in the circuit diagram.
2. Select current setting (set phase trip) less than 100%, keeping phase TMS at
maximum position.
3. Select any time setting.
4. Switch on variac and check power ON indication provided on relay front panel.
5. Vary dimmer stat and observe current value till Pick-Up will show ‘Red’
indication when current value exceeds set phase trip position.
6. Switch OFF dimmer stat without disturbing its position with the help of DPT
switch. Also reset time.
7. Measure the relay time from timer by switching on DPT switch.
8. Now increase the fault current and note down timer time after switching ‘OFF’
and ‘DPT’ switch every time with same time setting.
9. Repeat same procedure for different time setting keeping current setting same.
Dept. of Electrical Engineering Rewa Engineering College, Rewa

Circuit Diagram:

Observation Table:
Sl No. Fault Current (A) PSM Operating Time

Characteristic of IDMT relay:


Dept. of Electrical Engineering Rewa Engineering College, Rewa

1.2
1
0.8
Time (S)

0.6
0.4
0.2
0
Category 1 Category 2 Category 3 Category 4
Fault Current (A)

Result: For lower values of current the “time current ” characteristics are inverse and for higher
value for current observed times are constant.