The Fluke DTX-1800 CableAnalyser can be used to measure the multimode optical loss
of an installed cabling plant. For this, CommScope requires the DTX-1800 to be
equipped with the DTX-MFM2 LED source and the NFA-LC adapters.
The following procedures are required to setup the custom fiber loss limit provided by the
Fiber LinkLoss Calculator:
Note that 1310 nm and 1550 nm wavelengths are for singlemode measurements.
DO NOT use the VCSEL light sources: CommScope does not recommend the use of
VCSEL-based light sources as the primary light source for testing fiber links. This is due
to the fact that there is a large variability in VCSEL launch conditions that may lead to
significant measurement variability.