PC - 2017-Analysis

VERSION 17.1
RECTANGULAR CONCRETE BEAM/SECTION ANALYSIS
Ultimate Moment Capacity of Singly or Doubly Reinforced Sections
Per ACI 318-99 Code
Job Name: PRECAST DRIVEN PILE-350mmX350 mm Subject: ANALYSIS ON MOMENT CAP.
Job Number: 2X660 MW MAITREE STPP. Originator: PC Checker:

Input Data:

Beam or Slab Section? Beam b=13.76''


Reinforcing Yield Strength, fy = 72.52 ksi
Concrete Comp. Strength, f 'c = 5.8 ksi
Beam Width, b = 13.760 in.
Depth to Tension Reinforcing, d = 11.290 in. h=13.76'' d=11.29''
Total Beam Depth, h = 13.760 in.
Tension Reinforcing, As = 1.320 in.^2
Depth to Compression Reinf., d' = 0.000 in.
* As=1.32
Compression Reinforcing, A's = 0.000 in.^2 Singly Reinforced Section

* CONSIDERING TOTAL 8 NOS #6 - MS BAR & 3 NOS #6 - MS BAR AS TENSION REINFORCEMENT.


d' b
Results:
A's
Stress Block Data:
h d
b1 = 0.76
c= 1.857 in.
a= 1.411 in. As
Doubly Reinforced Section
Reinforcing Criteria:

r= 0.00850
rb = 0.02818
r(min) = 0.00315
As(min) = 0.489 in.^2 <= As = 1.32 in.^2, O.K.
r(temp) = N.A. (total for section)
As(temp) = N.A. in.^2/face
r(max) = 0.02113
As(max) = 3.283 in.^2 >= As = 1.32 in.^2, O.K.

Ultimate Moment Capacity:

fMn = 75.99 ft-kips


f 's = N.A. ksi

Note: fMn should be >= Mu


Comments:
SO, SECTION CAPACITY=75.99 ft-kips=102.028 kN-m > 85.95 kN-m.
HENCE ADEQUATE REINFORCEMENT HAS BEEN CONFIRMED.
HENCE PROVIDE TOTAL 8NOS #06 MS BAR AT THE SECTION.

1 of 1 9/4/2017 9:35 AM