Beruflich Dokumente
Kultur Dokumente
1
1.1 Propiedades a la temperatura de evaporación
𝐸𝑛𝑡𝑎𝑙𝑝𝑖𝑎 𝑑𝑒 𝑙í𝑞𝑢𝑖𝑑𝑜 ℎ𝐿
ℎ𝐿𝑟𝑒𝑔 = 5,18557947𝐸 + 04
+ 1,34352655𝐸 + 03 ∗ 𝑇𝑒𝑣
2
+ 1,36074832𝐸 + 00 ∗ 𝑇𝑒𝑣
3
+ 4,72437926𝐸 − 03 ∗ 𝑇𝑒𝑣
𝐸𝑛𝑡𝑎𝑙𝑝𝑖𝑎 𝑑𝑒 𝑣𝑎𝑝𝑜𝑟 ℎ𝑣
ℎ𝑣𝑟𝑒𝑔 = 2,50450164𝐸 + 05
+ 5,83136502𝐸 + 02 ∗ 𝑇𝑒𝑣
2
− 1,08638269𝐸 + 00 ∗ 𝑇𝑒𝑣
3
− 7,00777637𝐸 − 03 ∗ 𝑇𝑒𝑣
2
𝐸𝑛𝑒𝑟𝑔í𝑎 𝑖𝑛𝑡𝑒𝑟𝑛𝑎 𝑑𝑒𝑙 𝑙í𝑞𝑢𝑖𝑑𝑜 𝑢𝐿
𝑢𝐿𝑟𝑒𝑔 = 5,16294488𝐸 + 04
+ 1,33473519𝐸 + 03 ∗ 𝑇𝑒𝑣
2
+ 1,22382084𝐸 + 00 ∗ 𝑇𝑒𝑣
3
+ 3,79249377𝐸 − 03 ∗ 𝑇𝑒𝑣
𝑢𝑣𝑟𝑒𝑔 = 2,30158718𝐸 + 05
+ 5,57085961𝐸 + 02 ∗ 𝑇𝑒𝑣
2
− 5,57448741𝐸 − 01 ∗ 𝑇𝑒𝑣
3
− 5,99710201𝐸 − 03 ∗ 𝑇𝑒𝑣
3
𝐸𝑛𝑡𝑟𝑜𝑝í𝑎 𝑑𝑒𝑙 𝑣𝑎𝑝𝑜𝑟 𝑆𝑣
𝑣𝐿𝑟𝑒𝑔 = 7,72336912𝐸 − 04
+ 1,97172433𝐸 − 06 ∗ 𝑇𝑒𝑣
2
+ 9,32462130𝐸 − 09 ∗ 𝑇𝑒𝑣
3
+ 4,94259796𝐸 − 11 ∗ 𝑇𝑒𝑣
4
𝑉𝑜𝑙𝑢𝑚𝑒𝑛 𝑒𝑠𝑝𝑒𝑐𝑖𝑓𝑖𝑐𝑜 𝑑𝑒𝑙 𝑣𝑎𝑝𝑜𝑟 𝑉𝑣
𝑣𝑣𝑟𝑒𝑔 = 6,92632842𝐸 − 02
− 2,43628404𝐸 − 03 ∗ 𝑇𝑒𝑣
2
+ 5,00096607𝐸 − 05 ∗ 𝑇𝑒𝑣
3
− 6,52350243𝐸 − 07 ∗ 𝑇𝑒𝑣
4
+ 2,55145127𝐸 − 08 ∗ 𝑇𝑒𝑣
𝑐𝑝𝑟𝑒𝑔 = 8,93857425𝐸 + 02
+ 4,43607892𝐸 + 00 ∗ 𝑇𝑒𝑣
2
+ 2,47743254𝐸 − 02 ∗ 𝑇𝑒𝑣
3
+ 1,31010659𝐸 − 04 ∗ 𝑇𝑒𝑣
5
𝐶𝑎𝑙𝑜𝑟 𝑒𝑠𝑝𝑒𝑐𝑖𝑓𝑖𝑐𝑜 𝑎 𝑣𝑜𝑙𝑢𝑚𝑒𝑛 𝑐𝑜𝑛𝑠𝑡𝑎𝑛𝑡𝑒 𝑑𝑒𝑙 𝑣𝑎𝑝𝑜𝑟 𝐶𝑣
𝑐𝑣𝑟𝑒𝑔 = 7,60884975𝐸 + 02
+ 2,91089795𝐸 + 00
∗ 𝑇𝑒𝑣 + 4,92324215𝐸
2
− 03 ∗ 𝑇𝑒𝑣
− 6,93632124𝐸 − 06
3
∗ 𝑇𝑒𝑣
𝑃𝑟𝑒𝑠𝑖ó𝑛 𝑑𝑒 𝑠𝑎𝑡𝑢𝑟𝑎𝑐𝑖ó𝑛 𝑃𝑣
6
1.2 Propiedades a la temperatura de condensación
𝐸𝑛𝑡𝑎𝑙𝑝𝑖𝑎 𝑑𝑒 𝑙í𝑞𝑢𝑖𝑑𝑜 ℎ𝐿 𝑐
ℎ𝐿𝑐𝑟𝑒𝑔 = 5,32342090𝐸 + 04
+ 1,25642586𝐸 + 03 ∗ 𝑇𝑐
+ 2,97438420𝐸 + 00 ∗ 𝑇𝑐2
7
𝐸𝑛𝑒𝑟𝑔í𝑎 𝑖𝑛𝑡𝑒𝑟𝑛𝑎 𝑑𝑒𝑙 𝑙í𝑞𝑢𝑖𝑑𝑜 𝑢𝐿𝑐
𝑢𝐿𝑐𝑟𝑒𝑔 = 5,27861980𝐸 + 04
+ 1,26184692𝐸 + 03 ∗ 𝑇𝑐
+ 2,56583685𝐸 + 00 ∗ 𝑇𝑐2
𝑢𝑣𝑐𝑟𝑒𝑔 = 2,28475505𝐸 + 05
+ 6,62723826𝐸 + 02 ∗ 𝑇𝑐
− 2,49553561𝐸 + 00 ∗ 𝑇𝑐2
8
𝑉𝑜𝑙𝑢𝑚𝑒𝑛 𝑒𝑠𝑝𝑒𝑐𝑖𝑓𝑖𝑐𝑜 𝑑𝑒𝑙 𝑙í𝑞𝑢𝑖𝑑𝑜 𝑣𝐿 𝑐
𝑣𝐿𝑐𝑟𝑒𝑔 = 7,92524739𝐸 − 04
+ 7,21631807𝐸 − 07 ∗ 𝑇𝑐
+ 3,15164295𝐸 − 08 ∗ 𝑇𝑐2
𝑣𝑣𝑐𝑟𝑒𝑔 = 6,29998202𝐸 − 02
− 1,73655921𝐸 − 03 ∗ 𝑇𝑐
+ 2,02924106𝐸 − 05 ∗ 𝑇𝑐2
− 9,46023941𝐸 − 08 ∗ 𝑇𝑐3
9
𝑃𝑟𝑒𝑠𝑖ó𝑛 𝑑𝑒 𝑠𝑎𝑡𝑢𝑟𝑎𝑐𝑖ó𝑛 𝑃𝑣 𝑐
10
2. Análisis estado estable del sistema de refrigeración
2.1 Sistema sin control con RPS constantes a 60 [RPS]
𝐾𝑔 𝑇1 = 10 [°𝐶]
𝑚̇𝑤𝑡𝑜𝑟𝑟𝑒 = 1,2 [ ]
𝑠
𝐾𝑔 𝑇𝑤1 = 24 [°𝐶]
𝑚̇𝑤 = 2 [ ]
𝑠
𝐾𝐽
𝑐𝑝𝑤 = 4,18 [ °𝐶]
𝐾𝑔
11
Termodinámica del ciclo
12
Análisis del evaporador
13
Análisis de la válvula
14
Resolviendo las ecuaciones en EES obtenemos los siguientes valores para el
estado estable cuando 𝑚𝑤 = 2 [𝑘𝑔/𝑠]
Evaporador Condensador
𝐾𝑔 𝐾𝑔
𝑚̇𝑤 = 2 [ ] 𝑚̇𝑤𝑡𝑜𝑟𝑟𝑒 = 1,2 [ ]
𝑠 𝑠
𝑇1 = 10 [°𝐶] 𝑇𝑤1 = 24 [°𝐶]
𝑇2 = 7,581 [°𝐶] 𝑇𝑤2 = 28,8 [°𝐶]
𝑘𝑔 𝑇𝑐 = 41,56 [°𝐶]
𝑚̇𝑟 = 0,1444 [ ]
𝑠 𝑃𝑐 = 1060387 [𝑃𝑎]
𝑇𝑒𝑣 = 0,3046 [°𝐶] 𝑀𝑐 = 0,6548 [𝑘𝑔]
𝑃𝑒𝑣 = 296255 [𝑃𝑎] 𝑄𝐻 = 24,06 [𝑘𝑊]
𝑀𝑒𝑣 = 0,453 [𝑘𝑔]
𝑥𝑒𝑣 = 0,2941 Compresor
𝑄𝐿 = 20,23 [𝑘𝑊] 𝑊̇ = 3,83 [𝑘𝑊]
15
A continuación se muestran las funciones de Matlab incluidas en el programa del
Simulink junto la imagen de cada bloque del programa al que corresponde dicha
función.
16
sv=9.31392042E+02-5.55956195E-01*Tev+6.50197199E-03*Tev^2-6.85342354E-
05*Tev^3;
ul_c=5.27861980E+04+1.26184692E+03*Tc+2.56583685E+00*Tc^2;
uv_c=2.28475505E+05+6.62723826E+02*Tc-2.49553561E+00*Tc^2;
vl_c=7.92524739E-04+7.21631807E-07*Tc+3.15164295E-08*Tc^2;
vv_c=6.29998202E-02-1.73655921E-03*Tc+2.02924106E-05*Tc^2-9.46023941E-
08*Tc^3;
h_c=1.03481259E+05+2.58740594E+01*sv+1.37105853E-01*sv^2+4.51705888E-
03*Pc-8.15237857E-09*Pc^2+3.54311888E-05*sv*Pc;
Evaporador
dTmw=(mw*cpw*(T1-T2)-Q)/(Mw*cpw);
dTev=(mr1*hl-mr2*hv+Q-(mr1-mr2)*u)/(Mt*dU);
17
Energía interna evaporador
dul=1.33473519*10^3+2*1.22382084*Tev+3*3.79249377*10^(-3)*Tev^2;
duv=5.57085961*10^2-2*5.57448741*10^(-1)*Tev-3*5.99710201*10^(-3)*Tev^2;
u=ul+x*(uv-ul);
dU=dul+x*(duv-dul);
Calidad evaporador
x=(h_c-hl_ev)/(hv_ev-hl_ev);
v=vl+x*(vv-vl);
Mt=Vt/v;
18
Razón de transferencia de calor en el evaporador
Compresor
n=Cp/Cv;
V=((pi*D^2)/4)*L;
mr2=((V*RPS)/vv)*(1-C*((Pc/Pv)^(1/n)-1));
19
Condensador
n=Cp/Cv;
V=((pi*D^2)/4)*L;
mr2=((V*RPS)/vv)*(1-C*((Pc/Pv)^(1/n)-1));
Masa condensador
function Mt = fcn(Vt_c,vv_c)
Mt=Vt_c/vv_c;
20
Energía interna del condensador
dU_c=6.62723826E+02-2*2.49553561E+00*Tc;
u_c=uv_c;
T2torre=2*Tmtorre-T1torre;
LMTD_c=((Tc-T1torre)-(Tc-T2torre))/log((Tc-T1torre)/(Tc-T2torre));
Q_c=U_c*A_c*LMTD_c;
21
Válvula
A0=(pi*d0^2)/4;
mr1 = Cv*A0*sqrt((Pc-Pv)/vl);
Builder
22
3.1.1 Graficas
23
Variación de la temperatura de salida del agua a enfriar en el tiempo
Evaporador Condensador
𝐾𝑔 𝐾𝑔
𝑚̇𝑤 = 3 [ ] 𝑚̇𝑤𝑡𝑜𝑟𝑟𝑒 = 1,2 [ ]
𝑠 𝑠
𝑇1 = 10 [°𝐶] 𝑇𝑤1 = 24 [°𝐶]
𝑇2 = 8,367 [°𝐶] 𝑇𝑤2 = 28,85 [°𝐶]
𝑘𝑔 𝑇𝑐 = 41,76 [°𝐶]
𝑚̇𝑟 = 0,1463 [ ]
𝑠 𝑃𝑐 = 1066056 [𝑃𝑎]
𝑇𝑒𝑣 = 0,6276 [°𝐶] 𝑀𝑐 = 0,6585 [𝑘𝑔]
𝑃𝑒𝑣 = 299729 [𝑃𝑎] 𝑄𝐻 = 24,33 [𝑘𝑊]
𝑀𝑒𝑣 = 0,4584 [𝑘𝑔]
𝑥𝑒𝑣 = 0,2938 Compresor
𝑄𝐿 = 20,47 [𝑘𝑊] 𝑊̇ = 3,86 [𝑘𝑊]
24
3.1.3 Análisis de graficas
agua a enfriar sale a 7,62 [°𝐶], este estado diferente difiere muy poco con el
estable del EES, aproximadamente 0,1 °C de diferencia, lo cual es un error
muy bajo por lo cual la aproximación es válida, posteriormente en el instante
t=10 cuando se induce un transitorio a causa de un incremento en el flujo
másico de agua a enfriar el sistema se estabiliza cuando 𝑇𝑒𝑣 = 0,75 [°𝐶], 𝑇𝑐 =
42,7 [°C] y el agua sale a 8,39 [°C], este proceso transitorio tiene una duración
aproximada de 2[s].
Según los datos obtenidos en EES para los estados estables alcanzados por
el sistema al cambiar el flujo másico de agua de aprecia que la temperatura
de evaporación aumenta en 0,32[°C] lo cual no es cambio significativo, de
igual forma que los valores relacionados con el evaporador como lo son la
25
masa de refrigerante, el flujo másico de refrigerante, el calor del evaporador
y la calidad del refrigerante a la entrada del evaporador; El cambio más
apreciable es el aumento en la temperatura de salida del agua, lo cual
concuerda con el sentido físico, a mayor flujo másico menos cambio en la
temperatura y mayor temperatura de salida
26
3.2 Análisis con control PI
27
El estado estable inicial del sistema de refrigeración con el control PI es el mismo
que se tiene cuando no se integra un control para las RPS, el cual es:
Evaporador Condensador
𝐾𝑔 𝐾𝑔
𝑚̇𝑤 = 2 [ ] 𝑚̇𝑤𝑡𝑜𝑟𝑟𝑒 = 1,2 [ ]
𝑠 𝑠
𝑇1 = 10 [°𝐶] 𝑇𝑤1 = 24 [°𝐶]
𝑇2 = 7,581 [°𝐶] 𝑇𝑤2 = 28,8 [°𝐶]
𝑘𝑔 𝑇𝑐 = 41,56 [°𝐶]
𝑚̇𝑟 = 0,1444 [ ]
𝑠 𝑃𝑐 = 1060387 [𝑃𝑎]
𝑇𝑒𝑣 = 0,3046 [°𝐶] 𝑀𝑐 = 0,453 [𝑘𝑔]
𝑃𝑒𝑣 = 296255 [𝑃𝑎] 𝑄𝐻 = 24,06 [𝑘𝑊]
𝑀𝑒𝑣 = 0,6548 [𝑘𝑔]
𝑥𝑒𝑣 = 0,2941 Compresor
𝑄𝐿 = 20,23 [𝑘𝑊] 𝑊̇ = 3,83 [𝑘𝑊]
28
El programa en Simulink es el mismo que en el análisis de la transitoriedad del
sistema sin control con la única diferencia, por supuesto, de la inclusión del control
PI. Por esta razón solo se incluye el bloque correspondiente al control que se
muestra a continuación:
Control PI
error=Tev-Tref;
Cp=kp*error;
Ci=Cia+ki*error;
RPS=Cp+Ci;
29
3.2.2 Graficas
30
Variación de la temperatura de salida del agua a enfriar en el tiempo
31
Resolviendo en EES se obtienen los siguientes valores
Evaporador
𝐾𝑔 Condensador
𝑚̇𝑤 = 2 [ ] 𝐾𝑔
𝑠 𝑚̇𝑤𝑡𝑜𝑟𝑟𝑒 = 1,2 [ ]
𝑇1 = 10 [°𝐶] 𝑠
𝑇2 = 8,311 [°𝐶] 𝑇𝑤1 = 24 [°𝐶]
𝑘𝑔 𝑇𝑤2 = 29,04 [°𝐶]
𝑚̇𝑟 = 0,1527 [ ]
𝑠 𝑇𝑐 = 42,47 [°𝐶]
𝑇𝑒𝑣 = 0,3046 [°𝐶] 𝑃𝑐 = 10686247 [𝑃𝑎]
𝑃𝑒𝑣 = 296255 [𝑃𝑎] 𝑀𝑐 = 0,6718 [𝑘𝑔]
𝑀𝑒𝑣 = 0,443 [𝑘𝑔] 𝑄𝐻 = 25,3 [𝑘𝑊]
𝑥𝑒𝑣 = 0,301
𝑄𝐿 = 21,18 [𝑘𝑊] Compresor
𝑅𝑃𝑆 = 63,81
𝑊̇ = 4,127 [𝑘𝑊]
32
CONCLUSIONES
33