Beruflich Dokumente
Kultur Dokumente
Question no (2).-Conduit can have no more than________in a single run between pull
points.
Ans: - (a) 180 degree bends (b) 270 degree bends (c) 360 degree bends (d) 90 degree
bends.
Ans:- (a) Grounded (b) Ground fault (c) Ground (d) Ground conductor.
Question no (4).-Why seal conduit system are applicable for installation in Class I
.Division 1 and 2 location.
Question no (1). If the resistance of 1 cmil-ft of copper at 23⁰C is 10.5, what is the
resistance of 500 feet of copper wire with a diameter of .292?
Ans:- (a)1 ohms (b).0635 ohms (c) below 1 ohms (d) .0615 ohms (e) none of them.
Question no (3). What is the minimum acceptable size of power cable below
600V?
Ans;-(a) 2.5mm²(b) 4mm² (c) 6mm² (d) 2.5mm²
Question no (5). What is the basic formula used to determine the voltage drop?
Explain in brief.
2xLxRxI
Ans;- 𝑉𝐷 =
1000
Ans: - Classified areas are locations that have a high risk of fire or explosion due to
volatile gases in the surrounding atmosphere or vicinity. These areas are divided
into different classes, divisions, and groups.
Ans: - (a) Class I division II (b) Class I division I (c) Class II division II (d) Class II division I
Question no (3). (a) Seals minimize the flow of gas/vapors and prevent flame
from passing through conduit. They must be installed.
Ans: - (a) Within 12 inch of boundaries and enclosures that contain arcing devices.
(a) Seal fitting (b) one or more plugs (c) conduit fitting (d) Vent plug
(e) One or two fiber dams (f) Sealing compound.
Ans:- (1) a,b,c,d (2) b,c,d.e (3) a,b,e,f (4) a,c,d,f (5) None of them.
Question no (5). Do not replace the pouring plug on the Seal fitting for at least
_______ hours after pouring to allow for proper drying and curing. The compound
will set up quickly if it is hot, slower if it is cold.
Ans:- (a) twenty four hours (b) twelve hours (c) Eight hours (d) Minimum two days.
ELECI 115
Or
A device that provides battery backup when the electrical power fails or drops to an
unacceptable voltage level. Small UPS systems provide power for a few minutes;
enough to power down the computer in an orderly manner, while larger systems have
enough battery for several hours.
Ans: - (a) Oxygen (b) Hydrogen (c) Nitrogen (d) Sulfur dioxides.
ELECI 108
Ans: - The distance between the end of the cable and the point where the
conductor shields is removed.
Ans: - High potential test is a procedure for testing new and used cable. The test
voltage test set .The test provides a means of increasing the test voltage in small
increments allowing voltage and current indications to be read precisely .The behavioral
characteristics of the leakage current are evaluated to determine the condition of the
cable, specifically the insulation.
Ans :-( a) Supports and termination. (b) Splice and supports (c) Splice and
termination (d) none of them.
Ans: - 5to 25kV (b) Above 30kV(c) 2kV to 45kV (d) 5kV to 35kV
Question no (5). The spacing of duct banks is done in accordance with the
______
Ans: - (a) NEC, Article 300(b) NEC, Article 250(c) NEC, Article 314(d) NEC, Article
310
ELECI 113
Ans:- (a) NEMA Type 1 (b) NEMA Type 3(c) NEMA Type 3R(d) NEMA
Type 5
Ans: - (a) 30A through 1200A (b) 600A through 1200A(c) 800A through
1000A
Question no (5). How much DC voltage applied for safety switches are
rated at 600volts or less before placing the equipment in service?