VC Series

Evaporative Condenser

Operation Manual

Please read this manual carefully before operating


Fujian Snowman Co.,Ltd

Contents

1. Preface....................................................................................................................................................... 1

2. safety precautions..................................................................................................................................... 1

2.1 classification of warning signs...................................................................................................... 1

2.2 Precautions for installation and using.......................................................................................... 2

2.3 Precautions for moving and maintenance................................................................................... 4

3. Principle, structure and instruction......................................................................................................... 4

3.1 Principle............................................................................................................................................ 4

3.2 Structure of main parts................................................................................................................... 5

4. Moving........................................................................................................................................................ 6

5. Precautions for installation...................................................................................................................... 6

5.1 Installation site................................................................................................................................. 6

5.2 Body installation.............................................................................................................................. 7

5.3 Water distribution pipe................................................................................................................... 7

5.4 Electrical wiring............................................................................................................................... 7

6. Precautions before running..................................................................................................................... 8

6.1 Air fan................................................................................................................................................ 8

6.2 Water supply.................................................................................................................................... 8

6.3 Water tank cleaning........................................................................................................................ 8

6.4 Pipe cleaning................................................................................................................................... 8

6.5 Water pump..................................................................................................................................... 9

6.6 Water quality check........................................................................................................................ 9

7. Running method........................................................................................................................................ 9

8. Precautions during running..................................................................................................................... 9

9. Maintenance............................................................................................................................................ 10

9.1 air fan.............................................................................................................................................. 10

9.2 Evaporating coil pipes.................................................................................................................. 10

9.3 Water quality management.......................................................................................................... 11

9.4 Dash board.................................................................................................................................... 11

i
Fujian Snowman Co.,Ltd

9.5 Water tank...................................................................................................................................... 11

9.6 Tank body, framework and spray water tank body................................................................... 11

9.7 Ball float valve............................................................................................................................... 12

9.8 Filter................................................................................................................................................ 12

9.9 Water pump................................................................................................................................... 13

9.10 Surface and louvre boards cleaning........................................................................................ 13

9.11 Coating......................................................................................................................................... 13

11. Precautions in winter season.............................................................................................................. 15

12. About energy-saving running.............................................................................................................. 16

ON-OFF control........................................................................................................................... 16

Phase inverter control................................................................................................................. 16

13. Precautions of stopping using for a long time.................................................................................. 16

14. Special attention................................................................................................................................... 16

15. About water replenishing flow............................................................................................................. 17

16. Disturbance and trouble shooting...................................................................................................... 18

ii
Fujian Snowman Co.,Ltd.

1. Preface

The manual is an instruction to safe use of the product in fields which applys STC series

evaporative condenser such as food processing, refrigeration, beer, drink, oil, chemical industry and

medicine, etc.

Look at the manual and fully understand the operation, inspection, maintenance and fittings before

using.

There may be difference between this manual and the actual indications on the machine, due to

improvement to the machine. Please understand it.

Any operation inconformity with the manual may cause serious injury, death, etc.

The following precautions are mentioned in many places in this manual, especially those

concerning safety, pls make sure fully understand them before operation.

Carelessness during operation may cause serious injury, death, etc.

Operators and maintenance personnel must read the manual carefully in advance before

operation.

Keep the manual near the machine for referring anytime.

No operations and maintenance before fully understand the manual.

If the manual is missing or tore, pls ask for it from our company or agency immediately.

! W arning
Turn over the manual to new user if staff replacement.

2. safety precautions

2.1 classification of warning signs

To better understand the manual and warning signs, they are divided into the following 3 types, pls

act in accordance with them.

1
Fujian Snowman Co.,Ltd.

! D anger
Dangers may cause serious injury or death, to ensure safety, use precaution or waring

signs in emergency and dangerous places.

! W arning
Dangers may cause serious injury or death, to ensure safety, use precaution or waring

signs in potentially hazardous places.

! A ttention
Dangers may cause slight or medium injury, to ensure safety, use precaution or waring

signs in potentially hazardous places.

2.2 Precautions for installation and using

! W arning
 please commission professional company for installation. If fault installation, it may

lead to water leakage, electric shock and fire disaster, etc

 Other things that is not included in the supply scope such as electrical heater, must

use products designated by our company. To avoid water leakage, electric shock and

fire, etc. Pls commission professional manufacturer to install.

! A ttention
 Please do grounding. Ground wire should not be joined with the burning line, water

line, lightning guard and telephone ground wire.Fault grounding will lead to electric

shock, etc.

 according to electrical equipment technology standard regulation, please do install

electricity leakage breaker. If not, it will lead to electric shock,etc.

 please do not locate at where may have flammable gas leakage. If leakage, it is liable

to fire disaster.

2
Fujian Snowman Co.,Ltd.

 standard evaporative condenser should not be located at special conditions, such as

hot spring zone, costal area, overstuffed places. Otherwise, corrosion will lead to

electricity leakage and fire disaster, etc.

 please make sure the overflow pipe and water drain pipe are unbarred. If not, it may

lead to water leakage and do damage to the equipment and property.

! W arning
 Shut down the machine and cut off the power before maintainance and inspection.

The fan runs suddenly when the machine is fast-running inside or in controlled state

may cause injury or electric shock, etc.

 Don’t put hand or stick into air inlet and outlet, the fast running fan may cause injury.

 Stop running and cut off power immediately when abnormity (char, etc.) occurs and

get contact with seller or manufacturer. If continue running under this situation may

cause disturbance, electric shock and fire, etc.

 No touch switch with wet hand, which may cause electric shock.

 Check if installation platform and anchor bolts damaged during long-term use. If the

condenser is erected with defected anchor bolt, it will turn over and cause injury, etc.

 Don’t erect the condenser where may blow to the animals and plants directly, which

is bad to them.

 Wear protective gloves before maintainance and inspection, or it may cause injury.

 Don’t touch heat exchanger fan, or it may cause injury.

 Don’t stand on the top of the condenser or put things on it, otherwise it may turn

over and cause injury.

 Use correct fuse, copper wire, or it may cause fire.

 Don’t put flammable sprayer close to the condenser or where can be blowed directly

to the evaporative condenser, which may cause fire.

 Use supply water and cooling water complying with water quality requirements, or

water deterioration may cause running disturbance.

 Clean the inner at least once a month, or it may lead to bacterial growth and heat

3
Fujian Snowman Co.,Ltd.

exchanger efficiency declined and pipes damaged.

 Inject unfrozen liquid into the pipe or drain the water inside the machine if it stops

using for a long time or during winter season. Otherwise it may cause water

leakage,etc.

 Lukewarm water and cooling water is harmful to health, do not use it for water.

 Do not touch the high temperature parts of motor and electrical heater, or it may

cause burn

2.3 Precautions for moving and maintenance

! W arning
 Switch off and cut off power when maintaining. Blower runs high speed inside

machine or stops suddenly in control state, may cause injury or electric shock, etc.

 Reconstruction of machine is absolutely forbiddened, or it may cause electric shock,

fire and running faults, etc.

! A ttention
 Stop running when short curcuit occurs in protective device, or it may cause fire,

etc.

 Pls do not change the settings of protective device, or it may cause fire, etc.

3. Principle, structure and instruction

3.1 Principle

Evaporative condenser adopts heat exchanger. The circulation water cooled (cooling water) is

sucked through the louvre boards to the air. The water is evenly sprayed onto the outer surface of the

coil pipes through the water spray nozzles on the water spray tank. The water on the pipe surface

would contact the air and evaporate. The evaporated water would cool down the refrigerant.

After evaporation, the nozzle water becomes moisturized air and discharged out of cooling tower

by air fan on the top of the tower. A part of it is for heat exchange and the rest falls down, gathering in

4
Fujian Snowman Co.,Ltd.

the water tank for circulation to the water spray tank water pump.

3.2 Structure of main parts

①Condensing coil pipe

Circulating refrigerant enters main inlet pipe from inlet pipe, and then distributes to condensing coil

pipes, and being cooled down during this period, and then gathers at the main outlet pipe, being

transported to liquid receiver again through outlet pipe.

Outlet and inlet pipe and main pipe adopts high purity aluminum pipe. Refrigerant flows smoothly

in the coil pipes with slope.

②framework

SUS304 steel, anti-corrosive.

③water tank, shell plate, fan unit

The material is imported stainless steel sheet.

④air fan

Unique low noise axial fan.

The blade material is aluminum alloy, with low noise, and excellent anticorrosion effect.

Adjustable impeller space. If adjustment necessary, please contact SNOWMAN for help.

Moreover, the motor is closed type designed for outdoor use and adopt direct driven method.

⑤water spray tank

Adopt water spray nozzle method, which can spray water evenly. Moreover, large orifice

prevents blockage.

⑥Louvre blade

Made from stainless steel sheet. It can prevent relatively large rubbish to enter. The boards can be

dismantled one by one as well.

⑦Dash board

Made from fiber glass reinforced plastics. It is designed for reducing the water brought out with the

air by the air fan.

⑧water pump

Use low noise stainless steel pump. The motor the motor is closed type for outdoor use .

5
Fujian Snowman Co.,Ltd.

4. Moving

The following points must be paid special attention to during moving:

(1) Use cradle for lifting during unloading instead lifting by thread steel wire through eyebolt, pay

attention that no crash, and handle carefully, don’t scratch the outside surface of the tower body.

(2) when lifting by cradle, pay attention not to cause loosen in the steel wire, etc.

5. Precautions for installation

To realize the max efficiency of the condenser, pls select a good site for installation.

5.1 Installation site

1) clean place with good ventilation

2) the hot air from evaporative condenser will not be recycled.

! A ttention
 If it is applied in a place with much dust, sulfinic acid, etc, it may cause damage in heat

exchanger, pipes.

Outside liquid (circulating water) Outside fog

Sulphur content Thermal water Thermal water area with much

Water that can absorb much oxide, sulphur content

sulphurous acid gas Area with much industrial smoke

and sulphurous acid gas

salinity Thermal water, brine Area near coast which can blow

Well water near coast sea wind

acid Water of low PH value (take measures for Area with much chemical and

strong acid PH value under 6.3) concrete

Water of high PH value (above 11, except Near ventilated places that

for NH3) discharge gas

6
Fujian Snowman Co.,Ltd.

4) keep away from places near kitchen, toilet and Ammonia copier vent;

5) keep away from places near chimney or can be heated by other heat sources;

6) place in an open place without reflection sound;

7) leave a distance of above 4m between air inlet of evaporative condenser (air suction port) and

wall. The height of wall (overall height) shall be lower than that of evaporative condenser, otherwise it

could cause backflow due to wind direction and lead to capacity decline.

8) The distance between ventilation vent of evaporative condenser and barriers should be more

than 5m.

5.2 Body installation

1) Construct foundation according to sample or reference dwg. in the drawings provided after the

installation site is confirmed.

! W arning
 Make sure that the anchor bolts are fixed on the horizontal foundation securely,

otherwise it will fall down due to earthquake, strong wind etc and cause serious

accidents.

5.3 Water distribution pipe

1) For convenience in cleaning distribution pipe during operation, pls set a bypass loop.

2) To prevent water pipe from freezing in winter season, pls install a drain tap at the bottom of the

intermediate part between water supply joint and valve.

5.4 Electrical wiring

The wiring project of the motor should in accordance with Equipment Technical Standard and

correct installation method as specified by Electric Power Bureau.

1) Make sure to use correct breaker, fuse, switch and wire.

! A ttention
 Pls proceed with the 3rd kind of grounding engineering for the

earth wire. Poor earthing will cause running accidents like

electric shock, etc.

7
Fujian Snowman Co.,Ltd.

2) Make sure that the motor terminals are connected firmly, otherwise the motor could burn out

due to phase lack because virtual connection. Pls take it into full consideration.

6. Precautions before running

! W arning
 Make sure to cut off power and disconnect switch before preparation. Sudden running of

air fan could cause unnecessary injury.

! A ttention
 Wear protective gloves during preparation.

The air fan may run even if the power is cut off and may cause injury.

6.1 Air fan

1) Make sure the front end of the blade will not touch the case when use manual air fan.

2) For discontinuously running equipments, check that if the rotation direction is correct and if there

is abnormal sound and vibration, etc.

6.2 Water supply

1) Assemble well the connecting rod with the ball float valve well;

2) Open the discharge outlet at the bottom of water tank, drain off the sewage.

3) Feed water from water supply pipe, until reach the mouth of the overflow pipe.

4) Make the circulating water pump run discontinuously, get rid of air inside the tube, and fill it

with water.

5) Adjust ball float valve to make the water level of the overflow pipe under 30mm.

6.3 Water tank cleaning

Clean the lower water tank and the inner of the evaporative condenser.

6.4 Pipe cleaning

Welding splash and trimming remain inside the tank during tube installation will cause the water

8
Fujian Snowman Co.,Ltd.

quality to worsen and the rust water produced consequently will lead to corrosion. Therefore the

tubes must be cleared thoroughly.

6.5 Water pump

Make sure the rotating direction of the motor is correct.

To prevent partially burnout inside the pump, it shall not idle and must be with correct rotating

direction and start up with water.

6.6 Water quality check

The water circulates inside the tubes of evaporative condenser, if it is clean then everything is OK,

but if water supplied with high hardness and density of free carbonic acid, then it is easy to cause

rust and corrosion due to external air. Therefore, it is necessary to test the water quality in advance,

and then change water or treat the water according to the test results.

7. Running method

1) Repeat to start up circulating pump and open and close discharge air valve to drain off the air

inside the tubes.

2) water circulation adjustment in full flow

3) confirm if water tank level is proper

4) make sure that air fan and circulating pump is running under rated current, and check on

abnormal sound and vibration.

! W arning
 Don’t put hand or stick into fan, or it may cause injury.

8. Precautions during running.

1) make sure that the circulation water amount reaches the value as specified which will affect the

capacity of evaporative condenser. Moreover, check that if each nozzle distributes evenly.

2) check on blockage of nozzle and that if sprayed water amount is correct.

3) check that if the water tank level is too low, or it may cause water pump to cavitation corrosion.
9
Fujian Snowman Co.,Ltd.

4) check on leakage, ect of water pump.

5) Pay attention to noise, vibration and current value, deal with abnormities in time according to

Disturbance Cause and Solution.

6) check if algae grows inside evaporative condenser, especially on the surface of cooling coil pipe

and corrosion and water rust.

7) check the water quality and treat water properly. Discharge water in the tank through adjustment

valve for water quality management. Feed water amount according to concentration degree of the

water quality, normally 1.5%-2.0% of the water amount of water pump.

8) For others, pls refer to Item 9 Maintainance for detail.

9. Maintenance

Check evaporative condenser regularly.

9.1 air fan

! W arning
 Cut off power and pull the plug before checking air fan.

Sudden running of air fan will cause injury.

1) check the air fan bearing and supply lubricating oil 10g, once every 3 months(8 to 10hrs per

day).

2)Check that if dust adhere to the surface of air fan and therefore cause failure of balance control.

9.2 Evaporating coil pipes

1) check on leakage;

2) check the coil pipe on corrosion, rust and growth of algae. It can be checked from the internal of

the tank after dismantling louvre boards and dash board when checking. Take measures if there is

abnormity after confirming the causes.

3) Pay special attention to water quality management, and running within specified water quality

standard value.

4) Pay special attention to water quality management, and running with specified water quality

standar.

5) Pay full attention to the balance of circulating water, excessive water will cause corrosion on
10
Fujian Snowman Co.,Ltd.

metal surface.

6) Pay attention to leakage, blockage by barriers , bend and damage, etc.

9.3 Water quality management

Check circulating water quality once or twice monthly according to water qualtiy standard. Check

items incl. PH value and electric conductivity, it is hoped to keep the check recordings.

Even if the testing value within standard range, pls replace the water as the following frequency:

around once a month for the water.

Handle in the following sequences if there is any testing value not within the standard:

1) Test all checking items

2) Adjust discharge water amount, feeding water amount according to water quality and

concentration degree, normally 1.5%-2.0% of sprayed water.

3) For better maintainance, pls consult water treatment specilist for proper inhibitor which must be

safe to hot galvanized steel and iron and do as what specilist instructs.

4) When water is contaminated by organisms such as bacteria and algae, etc, handle as the

aforementioned item 3).

9.4 Dash board

Check if rust and algae on the dash board. Large amount of eyewinker would lead to bend and

deform, increased pressure damage inside the cabinet, decreased wind flow, and increased motor

current, etc, which will therefore result in motor overload and cooling capacity decline. So it ’ s

important for adequate water quality management to avoid rust and algae.

9.5 Water tank

The blockage of hole in water tank will cause level rise abnormally, if it is not deal with in time, the

water will overflow to internal cooling tower. Thus check the hole on blockage and get rid of it

immediately if there is.

9.6 Tank body, framework and spray water tank body

Tank body, framework and spray water tank have corrosion resistance to normal water quality and

atmospheric condition. Check in due time and get rid of the rust if there is. The garbage and sundries

accumulate in the water tank shall be drained off through drainage plug, because most of these

11
Fujian Snowman Co.,Ltd.

sediments are strongly corrosive and will damage the surface of the tank.

9.7 Ball float valve

1) If sand or trimming of side cutting for tube enter rubber valve of float ball valve, it will cause

damage and can not cut off water, pls check it regularly.

2) Clean the strainer regularly on the float ball valve.

3) If water leaks from the upper seal, screw the bolt (setting screw returns) right until water stops,

(but if too tight, the water will leak from bottom)

4) If water leaks from the lower seal, loosen nut by turning it left until the upper and lower leakage

stops simultaneously. If leakage can not stop yet, then there is foreign objects in seal ring, clean or

replace it. The replacement method is removing cylinder and oscillating rod first, then pull out the

seal ring under the situation of 25A.

When dismantling and assembling, pay attention not to damage the O-ring and supporting part of

valve base.

9.8 Filter

The blockage in filter will cause reduce in water amount from nozzle and decline in capacity. Clear

the filter once a week in heavily contaminated and dusty place while check once a month in places

where there is little dust and rubbish.

Clear the filter in time if the filter is found dirty.

12
Fujian Snowman Co.,Ltd.

9.9 Water pump

1) Pay attention to vibration, sound, voltage, current and heat, etc at usual time, check the causes

of abnormity occurs and take corresponding measure.

2) Mechanical seal is consumable, long term use will cause leakage due to wear, its durability will

be affected by water quality and service time, etc. Pls prepare spare parts.

3) Idling will cause fetal damage to pump, it must be prevented.

4) For details pls refer to attached instruction of pump.

9.10 Surface and louvre boards cleaning

Water tank surface and louvre boards, etc are easily contaminated by rubbish and dust in the air,

pls clean it frequently with water.

Dismantle the louvre boards as the following instructions if necessary when checking internal

machine.

The louvre blades can be removed one by one. Firstly, put up the louvre boards. Pull out the

boards from the lower direction. While, assemble the boards, it is in the contrary direction, from the

upper direction.

If put the dismantled louvre boards vertically, it is easily to deform. Please put the boards

horizontally in shade place.

9.11 Coating

Please recoat once each year.

Table 3 Check points of maintenance and part replacement


Name Check items Date of check Date of Replaced part
replacement and quantity
day week month 3 6 month year
month
Air Check for ○
fan injuries,
case deformation,
corrosion
and dirt
Motor Check the ○
shell wear and
tear, with or
without

13
Fujian Snowman Co.,Ltd.
rotation
barriers
motor Check the ○ 0.5 Bearing load
wear and side,back
tear, with or load side
without with 1pump
rotation each
barriers
Pum Check ○ 2
p rotation
motor barriers,
insulation
resistance,
corrosion,
etc.
Shell Check ○
plate cracks,
deformation,
rust and dirt
Dash Check the ○
boar water, rust,
d attachments,
deformation,
and clear the
blockage
Louvr Check the ○
e damage,
boar deformation,
ds aging and
dirt
Wate Check the ○
r tank damage,
deformation,
pollution,
drainage
holes to plug
Ball Confirm the ○ ◎
float action
valve
frame Whether ○
work corrosion
filter Check the ○
plug,
deformation,
breakage,
14
Fujian Snowman Co.,Ltd.
and clean-up
Cond Whether ○
ensin corrosion
g coil
pipe
Wate Check ○ Bearing load
r rotation side,back
pump barrier, load side
insulation, with 1pump
abnormal each
sound,
vibration,
Yang water,
leakage,
corrosion,
etc.
Remark:

①○mark:eye check;◎ mark:disassemble check.

2) annual running 8000 hours

3) replace period by different water quality, ambient setting, service condition, maintenance care to

different design plan.

4) please refer to the pump regulation in the pump operation manual for the rotation part

regulation.

11. Precautions in winter season

1) To prevent circulating water from freezing, pls add non-corrosive antifreeze.

The antifreeze will become dilute due to water leakage , pls check its density regularly and add.

2) To prevent water freezing in the tank, pls apply anti-freezing heater.

To prevent working without water, pls power on after confirming that the heat zone is put into water.

3) Pay attention that the louvre boards shall not be blocked by snow or ice, or the motor will

burnout due to current rise.

4) Make sure that there is no snow accumulates on the boars when proceed with ON-OFF

opeartion.

5) Pls note that circulating with low temperature water will cause water tank and louvre boards to

freeze.

15
Fujian Snowman Co.,Ltd.

12. About energy-saving running

Pay attention to the following matters when proceed with energy-saving running through control of

air fan in spring or winter season.

ON-OFF control

Extend the setting range of water temperature to make the ON-OFF interval reach above 10

minutes.

Phase inverter control

It may produce electronic noise which will affect other machines, and magnetic noise. Use it on

the basis of full investigation in advance.

13. Precautions of stopping using for a long time.

1) Drain the circulating water as early as possible before winter coming, because water will freeze

in winter season.

2) Drain the water inside the tank and clear it. Water will be drained when the valve stays open.

Futuremore, the water between valves of supply line and float ball valve shall also be drained.

3) Open the discharge plug of pump to prevent water existing in the empty pump.

4) open the discharge plug of exhaust valve of circulating water, discharge plug, water pump and

tank.

5) please inject lubricating oil to the air fan bearing.

6)loosen all tighten bolts and check on rust, repair places that are difficult to screw.

7) Apply protective hood for air outlet and tank body.

14. Special attention

When the evaporative condenser is placed in the area near coast and can be blowed by sea wind,

or with the same poor environmental conditions aforementioned, pay special attention to the

maintainance and water quality management.

16
Fujian Snowman Co.,Ltd.

! A ttention
 When doing welding, etc near evaporative condenser, pay attention not to splash the

sparks to tank body, and take protective measure.

15. About water replenishing flow

There are three reasons that causing water reduce in the tank of evaporative condenser, thus the

reduced portion must be added.

1) A part of the circulating water evaporates from the surface of coil pipe, which cause the tank

water reduced.

2) Water droplet is taken out with air through air fan and cause water reduced which is called drop

loss.

3) normally, some part of water evaporated from the nozzle, solid matter of water from nozzle

dissolve to residue and concentrated, which leads to nozzle water highly corrosion or easy to be

water rust. In order to prevent these, it is necessary to discharge a part of tank water.

(1) evaporative loss

A part of water evaporate from the evaporator.

(2)drop loss

The loss amount is the water drop discharged with the air plus the water splashed out through the

ventilation opening.

Drop loss C(%)= approximately, 0.1% of circulation water

(3)discharge

Since the condenser will evaporate some water, the solution ingredient will remain in the

circulation water and concentrate. The concentration ratio between the concentrated solution

ingredient in the circulation water and the solution ingredient in the make-up water is called

circulation water concentration multiple. So as to make circulation water running in certain

concentration multiple condition, some circulation water is discharged outside, to keep certain water

quality. This is called discharging.

Discharging amount should be lower than the value of concentration multiple, which is set
17
Fujian Snowman Co.,Ltd.

according to make up water quality, setting environment and the using state. Generally, in order to

make circulation water run in a certain concentration multiple, the discharge capacity can be

calculated by following formula.

E
 C
B(%) = N  1 N:concentration multiple(usually, N=3)

make up water

Make up water M(kg/h)= E + C + B

16. Disturbance and trouble shooting

Disturbance Reasons Trouble shooting

Abnormal 1)the front end of air fan 1)adjust the axis installation

sound and interferes with the case 2) tighten the bolts

vibration 2) loosen of bolts 3) check, adjust and replacement

3) shaft disturbance parts

4) motor disturbance, especially 4) replace motor or bearing

bad state of bearing 5) get rid of foreign objects after

5) foreign objects adhered to air checking

fan 6)replace air fan

6)damage on air fan 7)bring back to balance

7)air fan is unbalanced 8)wiring again until it runs normally

8)water pump reverses

Over current 1) low voltage 1) measure the voltage and contact

2) angles of air fan blades are with power supply bureau

not unified 2) adjust the angle

3) motor disturbance 3) repair or replace

4) shaft disturbance 4) repair or replace

5) foreign objects adhered to 5) get rid of foreign objects, clear

nozzle, and replace

18
Fujian Snowman Co.,Ltd.

feeding , louvre boards and 6) adjust the angle of air fan

dash board and lead to

blockage.

6) over current caused

by excessive wind flow

Rise of cooling water 1) circulating water amount too 1) adjust to standard water flow

temperature less 2) check, adjust angle and belt of

2) insufficient wind flow in air air fan blade

fan 3) improve ventilation

3) recycle of discharged air 4) improve ventilation

4)deviation of incoming wind 5) adjust water pump

5) water from nozzle reduces Check water pump

and deviates Clean contamination on filter and

6) water rust adheres to water tank tray,as the air,outside

evaporating coil pipe material comes in. Check on

adhesion of foreign objects on

feeding and evaporate coil pipe

Water bias loss 1) Sprayed water from the 1) adjust pump

nozzle is too much. 2) clear and get rid of foreign

2) blockage on dash board objects

3) input air too large 3) adjust the angle of air fan

19
Thanks again for selecting SNOWKEY evaporative condenser unit. Correct
installation and maintenance is helpful for you.

FUJIAN SNOWMAN CO.,LTD


Dongshan Road, Mingjiang Idustrical District, Fujian, China zip code:350200
Fuzhou Binhai Industrial District, Fujian Province zip code:3350217
Tel:(0591)28765626 Fax:(0591)28709222
Http://www.snowkey.com E-mail:service@snowkey.com