0 FIRST ISSUE Name PARTHA NEERAJ
Date 27.07.18 27.07.18
Sign
Rev No. Description No. Date Prepared Review Elec. Civil Mech Approved Status
Checked
OWNER: POWER GRID COMPANY OF BANGLADESH LIMITED

PROJECT: Western Grid Network Development Project (Improvement of Power Transmission in Western Zone)
Lot4: Design, Supply, Installation, Testing & Commissioning of 230/132kV and 132/33kV Substations, Western Zone, on Turnkey
Basis

CONTRACT NO.: PGCB/KfW/2012.66.436/WZSS

TITLE: 132 KV BUS SIDE VT SIZING REPORT.

A4 Document No: Total Sheets Rev No.

(0)-G71770-AD 996-X131-001 P- 090996_E_D2_8046_KFW 4 0


Powergrid Company of Bangladesh Limited
RC-IN EM TS SAM EN KFW

VOLTAGE TRANSFORMER DIMENSIONING

GENERAL PROJECT DATA:


Customer: Powergrid Company of Bangladesh Limited
Project: KFW
Station: Jhenaidah
Feeder: 132KV JHENAIDAH
Issued by: Partha Acharya
Our reference: PSLD_REV01
Date: 7/26/2018
Remark: First Submission

GENERAL SYSTEM AND SUBSTATION DATA:


Nominal voltage: 132 kV
Nominal frequency: 50 Hz
Rated short-circuit current of station: 50 kA
SAME DOCUMENT IS APPLICABLE FOR
Remark:
RAJBARI AND GOPALGANJ SUBSTATION

DATA OF WINDING 1 (METERING CORE) ACCORDING TO IEC:


VT type: IEC Class 0.2
Transformation ratio: 132/ 1.732 / 0.11/ 1.732 kV
VT rated burden Sn: 25 VA
Remark: CORE 1

DATA OF WINDING 2 (PROTECTION) ACCORDING TO IEC:


VT type: IEC Class 3P
Transformation ratio: 132/ 1.732 / 0.11/ 1.732 kV
VT rated burden Sn: 75 VA
Remark: CORE 2

VT REQUIREMENTS:

Requirement 1:
The burden shall be between 0% and 100% of the rated burden.

Requirement 2:
The voltage drop along the secondary wiring shall not be higher that 0.5% for metering windings and
2.5% for protection windings according to good engineering practice.

Requirement 3 (not mandatory):


According to the IEC 61869-3 the accuracy class of the VT is guaranteed only when the actual burden
of the VT has:
any value from 0VA to 100% of the rated burden (for the burden range I VTs), or
any value between 25% and 100% of the rated burden (for the burden range II VTs).
Remark 1: This requirement can be especially important (mandatory) when using VT winding for tariff
metering or when high accuracy metering is necessary.
Remark 2: Even for the burden range II VTs an extended range of burden can be specified in
agreement with the manufacturer, e.g. 0VA to 20VA or 0VA to 50VA. Then, the accuracy class is
maintained within this range.
RC-IN EM TS SAM EN/PSLD_REV01/Partha Acharya 7/26/2018
Revision 0 132KV JHENAIDAH
© CTDim 3.6 VT
Powergrid Company of Bangladesh Limited
RC-IN EM TS SAM EN KFW

CALCULATION OF TOTAL VT CONNECTED BURDENS:


The performance of the voltage transformer depends on the connected burdens at the secondary
terminals.

WINDING 1 (METERING CORE) (IEC Class 0.2):


The cable burden is calculated by the single length, the cross section, the specific resistivity for copper
and an effective factor for the wire length. This factor k wire is 2 if the return wire is to be considered.
Cable burden:
Length: lwire = 200 m
Cross section: Awire = 2.5 mm2
ρCu 2 O
Spec. resistivity (Cu): = 0.02171 Ω mm /m at 75 C
Eff. wire length in p.u.: kwire =2
k wire √ θ Cu √ l wire
Rwire < = 3.4737 Ohm
a wire
The total effective burden is given by the sum of all connected burdens:
Burden [VA] Burden Rb [Ω]
= 0.1 VA x 3 per phase = 13.44 kOhm
PROMETER 100_MAIN x 3
= 0.3 VA per phase (at 0.11/1.732 kV)
= 0.1 VA x 3 per phase = 13.44 kOhm
PROMETER 100_BACKUP x 3
= 0.3 VA per phase (at 0.11/1.732 kV)
= 0.15 VA x 4 per phase = 6.72 kOhm
MFM_ELITE 445 x 4
= 0.6 VA per phase (at 0.11/1.732 kV)
Total connected burden S'
(connected in parallel = 3.36 kOhm
= 1.2 VA per phase
incl. Rwire in series) (at 0.11/1.732 kV)

WINDING 2 (PROTECTION) (IEC Class 3P):


The cable burden is calculated by the single length, the cross section, the specific resistivity for copper
and an effective factor for the wire length. This factor k wire is 2 if the return wire is to be considered.
Cable burden:
Length: lwire = 200 m
Awire 2
Cross section: = 2.5 mm
Spec. resistivity (Cu): ρCu = 0.02171 Ω mm2/m at 75 OC
Eff. wire length in p.u.: kwire =2
k wire √ θ Cu √ l wire
Rwire < = 3.4737 Ohm
a wire
The total effective burden is given by the sum of all connected burdens:
Burden [VA] Burden Rb [Ω]
= 0.1 VA x 13 per phase = 3.1 kOhm
BCPU_7SJ85 x 13
= 1.3 VA per phase (at 0.11/1.732 kV)
MAIN 1 PROTECTION_7UT6 x = 0.1 VA x 3 per phase = 13.44 kOhm
3 = 0.3 VA per phase (at 0.11/1.732 kV)
MAIN 2 PROTECTION_7UT6 x = 0.1 VA x 3 per phase = 13.44 kOhm
3 = 0.3 VA per phase (at 0.11/1.732 kV)
= 0.05 VA x 2 per phase = 40.33 kOhm
DFDR x 2
= 0.1 VA per phase (at 0.11/1.732 kV)
Total connected burden S' = 2 VA per phase = 2.02 kOhm
RC-IN EM TS SAM EN/PSLD_REV01/Partha Acharya 7/26/2018
Revision 0 132KV JHENAIDAH
© CTDim 3.6 VT
Powergrid Company of Bangladesh Limited
RC-IN EM TS SAM EN KFW

(connected in parallel (at 0.11/1.732 kV)


incl. Rwire in series)

CHECK OF VT REQUIREMENTS:

WINDING 1 (METERING CORE) (IEC Class 0.2):


Requirement 1
The total connected burden is lower than 100% of VT rated burden:
S'′ Sn
S' = 1.2 VA
Sn = 25 VA Meets requirement
Requirement 2
Voltage drop along the wiring can be calculated:
U wire R √I R
Χu ' < √ 100 % < wire √ 100% < wire √ 100%
Un Un Rb '
Χu ' ′ Χu max
Χu ' = 0.103 %
Χu max = 0.5 % Meets requirement
Requirement 3 (not mandatory)
The total connected burden shall be between 25% and 100% of VT rated burden:
0.25S n ′ S ' ′ S n :
25% Sn = 6.25 VA
S' = 1.2 VA
Sn = 25 VA Doesn't meet requirement
According to the IEC 61869-3 the accuracy class of the VT is guaranteed only when the actual burden
of the VT has:
any value from 0VA to 100% of the rated burden (for the burden range I VTs), or
any value between 25% and 100% of the rated burden (for the burden range II VTs).
Remark 1: This requirement can be especially important (mandatory) when using VT winding for tariff
metering or when high accuracy metering is necessary.
Remark 2: Even for the burden range II VTs an extended range of burden can be specified in
agreement with the manufacturer, e.g. 0VA to 20VA or 0VA to 50VA. Then, the accuracy class is
maintained within this range.

The voltage transformer winding is correctly dimensioned, however when required an


extended range of burden has to be specified in agreement with the manufacturer.

WINDING 2 (PROTECTION) (IEC Class 3P):


Requirement 1
The total connected burden is lower than 100% of VT rated burden:
S'′ Sn
S' = 2 VA
RC-IN EM TS SAM EN/PSLD_REV01/Partha Acharya 7/26/2018
Revision 0 132KV JHENAIDAH
© CTDim 3.6 VT
Powergrid Company of Bangladesh Limited
RC-IN EM TS SAM EN KFW

Sn = 75 VA Meets requirement
Requirement 2
Voltage drop along the wiring can be calculated:
U wire R √I R
Χu ' < √ 100 % < wire √ 100% < wire √ 100%
Un Un Rb '
Χu ' ′ Χu max
Χu ' = 0.172 %
Χu max = 2.5 % Meets requirement
Requirement 3 (not mandatory)
The total connected burden shall be between 25% and 100% of VT rated burden:
0.25S n ′ S ' ′ S n
:
25% Sn = 18.75 VA
S' = 2 VA
Sn = 75 VA Doesn't meet requirement
According to the IEC 61869-3 the accuracy class of the VT is guaranteed only when the actual burden
of the VT has:
any value from 0VA to 100% of the rated burden (for the burden range I VTs), or
any value between 25% and 100% of the rated burden (for the burden range II VTs).
Remark 1: This requirement can be especially important (mandatory) when using VT winding for tariff
metering or when high accuracy metering is necessary.
Remark 2: Even for the burden range II VTs an extended range of burden can be specified in
agreement with the manufacturer, e.g. 0VA to 20VA or 0VA to 50VA. Then, the accuracy class is
maintained within this range.

The voltage transformer winding is correctly dimensioned, however when required an


extended range of burden has to be specified in agreement with the manufacturer.

The voltage transformer is correctly dimensioned!

RC-IN EM TS SAM EN/PSLD_REV01/Partha Acharya 7/26/2018


Revision 0 132KV JHENAIDAH
© CTDim 3.6 VT