Sie sind auf Seite 1von 4

Design calculation sheet

Project no: Date: Sheet no.: 1 of 1 Computed by:


Subject: Checked by:
Water Softner Sizing Approved by:

(1) Required grain removal per Gallon


gr/gal=Δ ppm/17 . 1
(grain/gal)

Inlet Water Hardness = 350 ppm (Very Hard)


Outlet Water Hardness = 50 ppm
⌂ Hardness = 300 ppm
1 grain per gallon = 17.1 ppm

Total grains per gallon = 17.55 grain / gal

(2) Water Usage per Day


gals/day=gpm×60×hrs/day
(gal/day)

Average Flow Rate = 21 gpm


Conversion = 60 min/hr
Operating Hours per day = 24 hrs / day

Water Usage per Day = 30240 gals/day

(3) Required Exchange Capacity


gr gal
(grains/day) gr /day= ×
gal day

Total grains per gallon = 17.55 grain / gal from (1)


Water Usage per Day = 30240 gals/day from (2)

Required Exchange Capacity = 530712 gr / day

(4) Required Resin


(ft3)
Resin=(REC×N/Cap)

Required Exchange Capacity (REC) = 530712 gr / day from (3)


Days of operation / regeneration (N) = 1 day
Resin Exchange Capacity (Cap) = 32000 gr /ft3 of resin

Required Resin = 16.6 ft3 of resin = 0.5 m3

(5) Salt Consumption per Generation


(lb)
Salt=(ResinCap×Salt Dosage)

Required Resin = 16.6 ft3 from (4)


Salt Dosage = 15 lb/ft3 salt dosage
Salt Consumption per Generation = 249 lbs = 113.2 kg
Design calculation sheet
Project no.: Date: Sheet no.: 25 of 25 Computed by:

Subject Checked by:

Extract from ASPE, Chap 11 - Water Treatment, Conditioning, and Purification Approved by:

The following are extracts from ASPE Data Book, Volume 2, Chapter 11 - " Water Treatment,
Conditioning, and Purification".

Hardness: is a measure of the total calcium, magnesium, iron and other metallic elements that
contribute to the "hard" feel of water. Carbonate, sulfate, and chloride salts of these
elements are responsible for most of the scaling deposited on pipe and boiler walls.
Generally accepted practice limits the term "hardness" to include only calcium and
magnesium. Hardness is usually expressed in terms of mg/L (ppm) as CaCO 3.

Often, Water is characterized in general terms by the amount of hardness as follows:

Soft 0 - 75 mg/L (ppm) as CaCO3


Moderate 76 - 150 mg/L (ppm) as CaCO3
Hard 151 - 300 mg/L (ppm) as CaCO3
Very hard > 300 mg/L (ppm) as CaCO3