Sie sind auf Seite 1von 2

JPY

Model
Jockey Pump Controller
Reduced Voltage Wye-delta Open Starter
Solid State Controls with Digital
Operator Interface
Standard Features:
• Solid state controls with digital iPD+
operator interface
• All adjustments on door front
• Visual indicators
• Manual motor run
• Automatic motor run
• System pressure
• Automatic mode
• Off mode
• Motor overload
• Pump start counter
• Elapsed time meter
(hours / non-resettable)
• Timers
• Minimum run period timer
• Sequential start timer
• Operators
• OFF-AUTO pushbutton
• Start and stop pushbuttons
• NEMA 2 enclosure
• Pressure transducer
• Wye-delta open transition fuseless
magnetic motor starter

The model JPY jockey pump controllers are specifically motor run, system pressure above stop pressure
designed to control jockey pumps in order to maintain setting, system pressure in-between start and stop
the desired water pressure in fire pump serviced systems. pressure setting and system pressure below start
A jockey pump installation prevents unnecessary starting pressure setting.
of the fire pump due to small leaks in the sprinkler system
piping. The standard power circuit consists of a horsepower
rated disconnect switch, a wye-delta open transition
The model JPY jockey pump controllers are supplied with magnetic motor starter and a thermo-magnetic motor
the front door mounted, solid state controls with digital protector for short circuit and overload protection.
iPD+ operator interface. The iPD+ allows the user to set
and adjust all parameters required such as start and stop Individual models are specific to the horsepower and
pressures, ON or OFF timers and units of measure (psi, bar, voltage available on site:
kPA, feet of head, meter of head) without having to open • JPY: 208 to 600 V / HP (kW) / 3 ph / 50Hz or 60Hz
the controller door. The iPD+ also continuously displays the
system pressure and the start and stop pressure settings.
LED visual indications include manual motor run, automatic N.Y.C.
APPROVED

2014-2015
JPY
Model
Operator Interface
7

2
1

5
4

9
8
4 - Start and stop pushbuttons
5 - Navigation keypad
1 - High luminosity four digit digital display
6 - OFF-AUTO position pushbutton and visual
2 - System status diagnostic LED’s for:
indication (LED)
i. Green: system pressure at or above cut-out
7 - Horsepower rated door interlocked rotary
value
type disconnect switch
ii. Yellow: system pressure between cut-in
8 - Wye-delta open transition fuseless magnetic
and cut-out
motor starter with thermo-magnetic motor
iii. Red: system pressure at or below cut-in value
protector
3 - Motor run LEDs (manual start or automatic start)
9 - Pressure transducer with 0-600psi
HOW TO ORDER: JPx - V / HP / Ph / Hz range and 316 stainless steel construction
Ex.: JPY - / / 3 / 50

JPY-BRO-002/E Rev.2
tornatech.com info@tornatech.com

Das könnte Ihnen auch gefallen