Figure 1 -Typical Cable Tray Layout – Metric Dimensions

SUBJECT: CABLE TRAY LAYOUT AND DESIGNATION

DESIGN STANDARD
3D-15.01 1
ISSUED FOR P-2569 CMPC
PROJECT NO. SHEET 1 OF 5 Rev.
LAJA MILL MODERNIZATION
DEPT. DATE OF
APPR. H. Jimenez ISSUE Marzo 10

PROJ. GENERIC
APPR. P.Healy APPR. DATE .
Figure 3 – Illustration of Fittings (sizes omitted for clarity)

SUBJECT: CABLE TRAY LAYOUT AND DESIGNATION

DESIGN STANDARD
3D-15.01 1
ISSUED FOR P-2569 CMPC
PROJECT NO. SHEET 2 OF 5 Rev.
LAJA MILL MODERNIZATION
DEPT. DATE OF
APPR. H. Jimenez ISSUE Marzo 10

PROJ. GENERIC
APPR. P.Healy APPR. DATE .
Symbols Description

L-w Straight Lengths

IL-w Straight Lengths Instrument Tray

H-a-w-r Horizontal Elbow

VI-a-w-r Inside Vertical Elbow

VO-a-w-r Outside Vertical Elbow

AV Adjustable Vertical

SR-w-w Concentric Reducer

LR-w-w Left Hand Reducer

RR-w-w Right Hand Reducer

T-w Horizontal Tee

X-w Horizontal Cross

Ex Expansion Joint Splice Plate

B Barrier

C Cover

E-w End Cap

DO Drop Out

Modifier Description

w Width in mm [in]; 150 [6], 300 [12], 450 [18], 600 [24], 900 [36]

a Angles in degrees; 15, 30, 45, 60, 90

r Radius in mm [in]; 600 [24] is standard and is not shown, 300 [12], 900 [36]

SUBJECT: CABLE TRAY LAYOUT AND DESIGNATION

DESIGN STANDARD
3D-15.01 1
ISSUED FOR P-2569 CMPC
PROJECT NO. SHEET 3 OF 5 Rev.
LAJA MILL MODERNIZATION
DEPT. DATE OF
APPR. H. Jimenez ISSUE Marzo 10

PROJ. GENERIC
APPR. P.Healy APPR. DATE .
Notes on Design

1. For trough spacing see Design Standard 3D-15.05.


2. Show elevation at both ends of vertical offset
3. Show trough sections only if layout is not explicit or to indicate special non-standard support
requirements.
4. Class 8C troughs (150 kg/m). See NEMA standard.
5. For items not shown or identified, indicate with maker and Cat. N°
6. Expansion joints to be installed at max. spacing of 18 m on trough.

Note on Installation
1. Troughs to be grounded at intervals - See Design Standard 3D-35.06.
2. Dedicated bonding jumpers, as furnished with expansion joints, shall be installed at each
'EX' location. At all other locations where electrical continuity -of the trough system as
been weakened or broken (e.g. at 'AV' locations), use N° 2/0 AWG, 19 strand copper
conductor with compression type lugs approved for project. Bolt lugs to trough with cadmium
plated round head bolts.
3. Covers must be `used where falling debris could injure cables or where combustibles such
as sawdust could accumulate on cable.
4. Where trough covers are used to protect cables from sun, use 2.5cm (min.) spacers
between trough and covers to provide air circulation.
5. Troughs which pass through electrical room walls shall slope down on the outside in order to
prevent ingress of water into the electrical room.
6. Deleted

7. Panatrox "A" seal and oxide inhibiting compound shall be used on all connections.
8. Bolt barrier with cadmium plated bolts. Barrier ends shall be 280 mm apart, to allow slack for
expansion or contraction.

SUBJECT: CABLE TRAY LAYOUT AND DESIGNATION

DESIGN STANDARD
3D-15.01 1
ISSUED FOR P-2569 CMPC
PROJECT NO. SHEET 4 OF 5 Rev.
LAJA MILL MODERNIZATION
DEPT. DATE OF
APPR. H. Jimenez ISSUE Marzo 10

PROJ. GENERIC
APPR. P.Healy APPR. DATE .
9. For vertical bends of less than 60° use the adjustable vertical risers ´AV´
10. Trays will be designated in the drawings and marked in the will as follow:

TRAY LEGEND

SUBJECT: CABLE TRAY LAYOUT AND DESIGNATION

DESIGN STANDARD
3D-15.01 1
ISSUED FOR P-2569 CMPC
PROJECT NO. SHEET 5 OF 5 Rev.
LAJA MILL MODERNIZATION
DEPT. DATE OF
APPR. H. Jimenez ISSUE Marzo 10

PROJ. GENERIC
APPR. P.Healy APPR. DATE .