BS 7671 lists five types of earthing system: TN-S, TN-C, TT, TN-C and IT.
T= Earth
N = Neutral
S = Separate
C = Combined
I = Isolated
The Earthing conductor and main protective bonding conductor sizes (copper equivalent)
for TN-S and TN-C-S supplies are determined as follows:
Notes:
1. Protective conductors (including earth and bonding conductors) of 10mm² cross-
sectional area or less shall be of copper.
2. The distributor may require a minimum size of earth conductor at the origin of the
supply of 16mm² copper or greater for TN-S and TN-C-S supplies.
Notes:
1. Assuming protection against corrosion by a sheath
2. The main protective bonding conductors shall have a cross-sectional area of not less
than half that required for the earthing conductor and not less than 6mm².
c) Where practicable, the connection to the gas, water, oil, etc service should be within
600mm of the service meter, or a point of entry to the building if the service meter is
external and must be on the consumer’s side before and branch pipework and after any
insulating section in the service. The connection must be made to hard pipework, not to
soft or flexible meter connections.
d) The connection must be made using clamps (to BS 951) and be suitably protested
against corrosion at the point of contact.
(Taken from source: Onsite Guide: BS 7671:2008 +A3: 2015. 6th Edition)