Unlike SVC, STATCOM controls the output current independently of the AC system
voltage, while the DC side voltage is automatically maintained to serve as a voltage source.
Mostly, STATCOM is designed based on the voltage source inverter. Also, the combination
of STATCOM with a different storage device or power source endows the STATCOM the
ability to control the real power output.
In distribution system, medium and low voltage STATCOM is employed mainly for
In the case of two AC sources, which have the same frequency and are connected
through a series reactance, the power flows will be:
Active or Real Power flows from the leading source to the lagging source.
Reactive Power flows from the higher to the lower voltage magnitude source.
Consequently, the phase angle difference between the sources decides the active
power flow, while the voltage magnitude difference between the sources determines the
reactive power flow. Based on this principle, a STATCOM can be used to regulate the
reactive power flow by changing the output voltage of the voltage-source converter with
respect to the system voltage.
Modes of Operation
A. Voltage Regulation
In steady-state operation, the voltage V2 generated by the VSC through the DC capacitor
is in phase with the system voltage V1 (δ=0), so that only reactive power (Q) is flowing (P=0)
• From a DC input voltage source, provided by the charged capacitor CS, the
converter produces a set of controllable three-phase output voltages with the
frequency of the ac power system. Each output voltage is in phase with, and
coupled to the corresponding ac system voltage via a relatively small (0.1-0.15
p.u.) tie reactance (which in practice is provided by the per phase leakage
inductance of the coupling transformer).
• By varying the amplitude of the output voltages produced, the reactive power
exchange between the converter and the ac system can be controlled in a
manner similar to that of the rotating synchronous machine.
• If the amplitude of the output voltage is decreased below that of the ac system,
then the reactive current flows from the ac system to the converter, and the
converter absorbs reactive (inductive) power. If the amplitude of the output
voltage is equal to that of the ac system voltage, the reactive power exchange is
zero.
Q = [V1 (V1-V2)] / X
B. VAR Control
In this mode, the STATCOM reactive power output is kept constant independent of
other system parameter
Procedure
STATCOM
1. Turn on the power supply to source, battery charger and STATCOM.
2. Check whether any protection circuit is activated, and reset it.
3. Check the DC rail voltage for the battery charger.
4. Turn on the DSP kit and select STATCOM operation using the switch SW2 on it.
5. Switch on MCB 1.
6. Adjust the sending end voltage to 110 V (line to neutral) using switches SW1 and
SW2 on the interface board and note down the voltage, current, power factor, active
power and reactive power at the receiving end for the applied load.
7. Increase the STATCOM modulation index to 80% using switches SW3 and SW4 on
the interface board.
8. Switch on MCB 2 and note down the sending end and receiving end parameters.
9. Adjust the angle of STATCOM using the switches SW2 and SW3 on the DSP kit to
improve the sending end and receiving end power factor.
Results:
B) Voltage Regulation