CONTROL PANELS
PLC based
3.02.00 Local control panels for Coal handling plant (under BTG scope):
Local control panels for traveling trippers, sump pumps, hydraulic scoop coupling
and dust suppression system. shall be free standing, floor/wall mounting type.
Bottom ash local control panel for each unit and Silo control panel along with mimic
for control of various drives in bottom ash area & silo area respectively. Necessary
miniature push buttons, control/selector switches, lamps, meters, annunciation
windows etc suitable for 24V DC operation shall be provided.
3.06.00 All drives related to Coal Handling shall be controlled through microprocessor based
Distributed Control System (DCS) as specified in C&I module.
3.07.00 All drives related to Ash Handling System except for the controls of HCSD system
shall be controlled through microprocessor based Distributed Control System (DCS)
as specified in C&I module.
1). The control system for HCSD system shall be PLC based.
Each PLC system shall be provided with 2 x100% processors in hot standby
mode. Standby processor shall be energised and continuously monitored for
healthiness. In case a failure of working processor, the standby processor
shall take over the operation automatically by bumpless transfer and
necessary failure alarm shall be provided. Both the work stations of a PLC
system shall be suitable for operation and also for programming hence
2). The processor along with OWS, printer etc. and control panels shall be
interlinked through independent dual data highway and dual I/O
communication links.
3). The push button and selector switches mounted on control desk shall send
necessary signals through PLC.
4). The PLC shall provide supervisory information for alarm, various types of
displays, status information, trending, historical storage of data etc. and also
perform self monitoring and diagnostic functions.
1). Normal / local mode of operation shall be selected from the key board.
(a) In normal mode of operation, which shall be the default mode, all
drives shall be operated from control desk through keyboard.
Whenever required for maintenance, maintenance mode for equipment
will be selected through keyboard. Operation interlocks, except trip
interlocks shall be locked using a unique password. After
maintenance, the drives shall be started through keyboard, with all
process interlocks, by re-entering the password. Normal mode of
operation can be selected then. Irrespective of any PLC mode of
operation, the running equipment can be stopped from keyboard or
from desk/panel or from emergency stop push button.
6.00.00 TRAINING
(d.) Any other specialized training as required for system operation and
maintenance.
7.01.00 Each PLC system shall consist of redundant processors, PCs with TFT (latest
version with latest application software) & keyboard, I/O modules, UPS / power
supply with battery backup, printer etc. Each PC based operating and programming
workstation shall be fully equipped for operation and control of the various systems.
The configuration of PLC shall be as per enclosed drawing. Details of various
components shall be as given below :
d) Monitor & Keyboard Twenty inches (20 inches) TFT flat monitor with
resolution of 1280 x 1024 pixels non interfaced,
refresh rate min. 75Hz, with flat membrane type
keyboard/ mouse. The numbers of OWS shall be as
per PLC configuration diagram.
i) Fusing philosophy Individual fuses with blown fuse indicator for each
output. Individual fuses for each input/ group of inputs,
keeping in view of system availability.
m) Power supply i) Two (2) nos 415V AC feeders shall be provided for
each control panel / desk and remotely located I/O
panels.
system.
r) System reaction Less than 100 msec. from input signal to output signal
time including logic processing.
v) Long time 168 hours latest data on hard disc. Data to be stored:
storage &
retrieval
i) Alarm list.
d) Name Plates & Each panel shall be identified by a name plate. Panel
Labels internal equipment shall be identified by paint marking.
Nameplates shall be non rusting metal or 3-ply
lamicoid, with engraved lettering and shall be subjected
to Employer’s approval.
h) Type Elmex - CATD type for CTs. Elmex - CSLT for other
application.
i) Spare 20 percent.
k) Panel Lighting Each free standing panel shall be provided with a door
switch operated fluorescent lamp and a 240V AC plug
point.
(a) All equipment to be supplied shall be of type tested quality. The Contractor shall
submit for Employer’s approval the reports of all the type tests as listed in this
specification and carried out within last ten years from the date of bid opening.
These reports should be for the tests conducted on the equipment similar to those
proposed to be supplied under this contract and the test(s) should have been either
conducted at an independent laboratory or should have been witnessed by a client.
(b) However if the Contractor is not able to submit report of the type test(s)
conducted within last ten years from the date of bid opening, or in case the type test
report(s) are not found to be meeting the specification requirements, the Contractor
shall conduct all such tests under this contract, at no additional cost to the Employer
either at third party lab or in presence of clients/Employers representative and
submit the reports for approval
(c) All acceptance and routine tests as per the specification and relevant standards
shall be carried out. Charges for these shall be deemed to be included in the
equipment price.
(d) The type test reports once approved for any projects shall be treated as
reference. For subsequent projects if NTPC, an endorsement sheet will be furnished
by the manufacturer confirming similarity and "No Design Change." Minor changes if
any shall be highlighted on the endorsement sheet.
9.01.02 Following tests shall be conducted under this contract as routine tests:
d). Task transition test (for each task, the Contractor will list out the user
accessible conditions which shall be used in the simulation of the task).
e). Functional testing of software and hardware in accordance with the approved
block logic diagram with simulation of the system with switches, relays and
solenoid valves etc. or equivalent loads.