Criterios de cálculo y dimensionamiento

Método-Estándar de Cálculo IEC 60909-1

Standard for cable dimensioning IEC 60364

Overload Overload verifications are made according the following relations: IB <= In <= Iz and I2 <= 1.45*Iz

Legenda:

IB = the current for which the circuit is designed

In = nominal current of the protective device (For adjustable protective devices, the nominal current In is the current setting selected)

I2 = current ensuring effective operation in the conventional time of the protective device

Iz = capacidad de conducción del cable acorde al estándar elegido

Cortocircuito Interruptores automáticos y fusibles son dimensions con la capacidad de ruptura mayor a la máxima corriente de cortocircuito en el punto de instalación.

Circuit breakers dimensioned according to IEC 60497-2 are also chosen with the making capacity Icm higher than the maxiimum peak current

La protección por cortocircuito debe satisfacer la siguiente regla I2t <= K2S2

Legenda:

I2t = energía pasante a la corriente máxima de cortocircuito (definida por el fabricante)

S = sección de los conductores

K = factor definido en IEC60364-4-43 tabla 43A y IEC60364-5-54 tablas A.54.2, A.54.4 y A-54.5

Contacto indirecto Sistemas TT: la verificación es Idn * Rt <= Vo, o Im <= Ib mín

Sistemas TN: la verificación es Im <= Ib mín

Leyenda:

Idn = sensibilidad del interruptor diferencial

Ra = resistencia a tierra

Vo = max admitted contact voltage

Im = valor de tripeo del dispositivo de protección al tiempo límite

Ib mín = mínima corriente de cortocircuito al final de la línea

Selectividad y Back-up Los valores de selectividad y back-up son determinados por tests de laboratorio del fabricante

Discriminación no requerida en la instalación

Backup not required in the installation

Rev. n1 Fecha: Descripcion Cliente: Numero de Dibujo:


Rev. n2 Dibujante: Proyecto:
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 1 1
Hipótesis para el cálculo de corto circuito según IEC60909-0

Algoritmo de Cálculo

The calculation of maximum and minimum, balanced and unbalanced, short-circuit currents is made by application of symmetrical components.

Condiciones Generales

The calculation of maximum and minimum short-circuit currents is based on the following simplifications.

a) For the duration of the short circuit, there is no change in the type of short circuit involved (a three-phase short circuit remains three-phase)

b) For the duration of the short circuit, there is no change in the network involved.

c) La impedancia de los transformadores está referida al "tap-changer" en posición principal

d) Las resistencias de arco no son tomadas en consideración.

e) Todas las líneas de capacitancia, admitancias derivadas y cargas no rotativas, excepto aquellas que tengan sistemas de secuencia cero, no son consideradas.

Maximum short-circuit currents

En el cálculo de las corrientes de cortocircuito máximas, se considera lo siguiente:

- se aplica el factor de voltaje Cmáx acorde a la tabla 1, IEC 60909-0

- se elije la configuración de red que conduce al valor máximo de corriente de cortocircuito en el lugar del cortocircuito.

- la contribución de motores síncronos es considerada, si su contribución es mayor al 5% de la corriente inicial de cortocircuito calculada sin motores

- resistencia RL de las líneas (líneas aereas y cables) son ingresadas a una temperatura de 20°C

Minimum short-circuit currents

En el cálculo de las corrientes de cortocircuito mínimas, se considera lo siguiente:

- se aplica el factor de voltaje Cmín acorde a la tabla 1, IEC 60909-0

- se elije la configuración de red que conduce al valor mínimo de corriente de cortocircuito en el lugar del cortocircuito.

- No se considera la contribución de los motores asíncronos

- resistencia RL de las líneas (líneas aereas y cables) son ingresadas a una temperatura de 160°C

Rev. n1 Fecha: Descripcion Cliente: Numero de Dibujo:


Rev. n2 Dibujante: Proyecto:
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 1 1

-QF3
T6N 800 PR221DS-LS/I 800A
TD-G1
Un [V] 380
LLLN / TN-S
Ik LLL [kA] 20.9
Ik LN [kA] 12.5 
-WC1
Ik LPE [kA] 12.5 TD-G1
6x(1x240)+2x(1x120)+2G120
P [kW] 325.7 Ib = 550.5 A
Q [kvar] 158.8 Iz = 1193.1 A
dV = 0.18 %
L = 10 m


-QF1
T6N 800 PR221DS-LS/I 800A
TD-G1
-B1
TD-G1
FU = 0.95
U=379.3 V
IB = 550.5 A
Cosphi = 0.90
Ik max = 19.5 kA
     Ik LLL = 19.5 kA
-QF8 -QF2 -QF4 -QF5 -QF6
T5N 630 PR221DS-LS/I 630A A1N 125 TMF 40-400 T1N 160 TMD40-500 T2N 160 TMD50-500 XT4N 160 Ekip LSI R40
TDE-G1 TD-VES1 TD-BO3 TD-MA1 TD-BO4

    
-WC6 -WC2 -WC3 -WC4 -WC5
TDE-G1 TD-VES1 TD-BO3 TD-MA1 TD-BO4
6x(1x185)+2x(1x95)+2G95 3x(1x25)+1x(1x16)+1G16 4x(1x16)+1G16 3x(1x50)+1x(1x25)+1G25 3x(1x25)+1x(1x16)+1G16
Ib = 508.7 A Ib = 13.5 A Ib = 5.9 A Ib = 38.2 A Ib = 11.4 A
Iz = 1010.7 A Iz = 51.9 A Iz = 40.5 A Iz = 73.5 A Iz = 51.9 A
dV = 0.31 % dV = 0.64 % dV = 0.18 % dV = 0.53 % dV = 0.57 %
L = 16 m L = 141 m L = 58 m L = 76 m L = 147 m
    
-L73 -L72 -L71 -L70 -L69
TDE-G1 TD-VES1 TD-BO3 TD-MA1 TD-BO4
Sn = 334.84 [kVA] Sn = 8.87 [kVA] Sn = 3.87 [kVA] Sn = 25.15 [kVA] Sn = 7.52 [kVA]
Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90 Cosphi (nominal) = 0.90
In = 508.7 [A] In = 13.5 [A] In = 5.9 [A] In = 38.2 [A] In = 11.4 [A]
U = 378.1 [V] U = 376.9 [V] U = 378.7 [V] U = 377.3 [V] U = 377.2 [V]
dU = 0.49 % dU = 0.82 % dU = 0.35 % dU = 0.71 % dU = 0.75 %
P = 299.89 [kW] P = 7.91 [kW] P = 3.47 [kW] P = 22.48 [kW] P = 6.72 [kW]
Q = 145.24 [kvar] Q = 3.83 [kvar] Q = 1.68 [kvar] Q = 10.89 [kvar] Q = 3.25 [kvar]
Distribución

Voltaje de Referencia [V] 380 Corriente de cortocircuito simétrica LLL [kA] 20.89
Fases LLLN Corriente de cortocircuito LN [kA] 12.53
Sistema de distribución TN-S Corriente de cortocircuito LPE [kA] 12.53

Potencia Activa P [kW] 325.69 Cmax 1.10


Potencia Reactiva Q [kvar] 158.79 Resistencia a Voltaje de Referencia [mOhm] 1.155
Ib (A) [A] 550.52 Reactancia a Voltaje Referencial [mOhm] 11.494
Factor de potencia Cosphi 0.90 Impedancia a Voltaje Referencial [mOhm] 11.552

Rev. n1 Fecha: Descripcion Cliente: Numero de Dibujo:


Rev. n2 Dibujante: Proyecto:
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 1 1
Cálculos de cortocircuito

Cuadro Ib LLL (kA) Ip LLL (kA) Ib LL (kA) Ip LL (kA) Ib LN (kA) Ip LN (kA) Ib LPE (kA) Ip LPE (kA)
+Q1 19.50 46.68 16.89 40.42 11.52 27.57 11.52 27.57
+Q2 20.89 51.55 18.09 44.65 12.53 30.93 12.53 30.93

Rev. n1 Fecha: Descripcion Cliente: Numero de Dibujo:


Rev. n2 Dibujante: Proyecto:
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 1 1
Corrientes de Cortocircuito (IEC61363)

Cuadro Ib LLL (kA) Ip LLL (kA) Ip LLL (kA)


+Q1
+Q2

Rev. n1 Fecha: Descripcion Cliente: Numero de Dibujo:


Rev. n2 Dibujante: Proyecto:
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 1 1
Protección de cables

-WC1 TD-G1
Datos de carga

Fases - Sistema de Distribución LLLN / TN-S Overload: protected by -QF3 T6N 800 PR221DS-LS/I 800A
Pasado
Voltaje [V] 380 Overload: Ib (550.52[A]) <= Ith (608.00[A]) <= Iz (1193.10[A]) and If (790.40[A]) <= 1.45*Iz (1729.99[A]); Uref=380V
IB (A) [A] 550.5
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF3 T6N 800 PR221DS-LS/I 800A

Protection checks
Cosphi 0.90 Pasado
Short-circuit: Protection guaranteed up to Ik LLL (20.89[kA]), Ik LN (12.53[kA]), Ik L-PE (12.53[kA]); Uref=380V
Sección transversal de los cables 6x(1x240)+2x(1x120)+2G120
Aislador Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QF3 T6N 800 PR221DS-LS/I 800A
Pasado
Longitud (m) [m] 10 2 People protection: I@Max tripping time ( 3.10[kA])<=Ikmin L-PE ( 9.90[kA]); Trip time=5.00[s]; Uref=380V
Cable

Iz (A) [A] 1193.1


1 Short circuit at terminal 2 (current flowing upstream): protected by
dV ( ) 0.18
Temp de Trabajo (°C) [°C] 38.5
Power loss [W] 376.59 Indirect touch at terminal 1 (current flowing upstream): protected by
K2S2 [A2s] 759590568 2

-WC2 TD-VES1
Datos de carga

Fases - Sistema de Distribución LLLN / TN-S Overload: protected by -QF2 A1N 125 TMF 40-400
Pasado
Voltaje [V] 380 Overload: Ib (13.47[A]) <= Ith (40.00[A]) <= Iz (51.93[A]) and If (52.00[A]) <= 1.45*Iz (75.29[A]); Uref=380V
IB (A) [A] 13.5
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF2 A1N 125 TMF 40-400
Cosphi 0.90 Protection checks Pasado
Short-circuit: Protection guaranteed up to Ik LLL (19.50[kA]), Ik LN (11.52[kA]), Ik L-PE (11.52[kA]); Uref=380V
Sección transversal de los cables 3x(1x25)+1x(1x16)+1G16
Aislador Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QF2 A1N 125 TMF 40-400
Pasado
Longitud (m) [m] 141 2 People protection: I@Max tripping time ( 0.48[kA])<=Ikmin L-PE ( 0.49[kA]); Trip time=0.40[s]; Uref=380V
Cable

Iz (A) [A] 51.9


1 Short circuit at terminal 2 (current flowing upstream): protected by
dV ( ) 0.64
Temp de Trabajo (°C) [°C] 32.7
Power loss [W] 59.72 Indirect touch at terminal 1 (current flowing upstream): protected by
K2S2 [A2s] 8242085 2

-WC3 TD-BO3
Datos de carga

Fases - Sistema de Distribución LLLN / TN-S Overload: protected by -QF4 T1N 160 TMD40-500
Pasado
Voltaje [V] 380 Overload: Ib ( 5.87[A]) <= Ith (34.00[A]) <= Iz (40.53[A]) and If (44.20[A]) <= 1.45*Iz (58.77[A]); Uref=380V
IB (A) [A] 5.9
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF4 T1N 160 TMD40-500
Protection checks

Cosphi 0.90 Pasado


Short-circuit: Protection guaranteed up to Ik LLL (19.50[kA]), Ik LN (11.52[kA]), Ik L-PE (11.52[kA]); Uref=380V
Sección transversal de los cables 4x(1x16)+1G16
Aislador Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QF4 T1N 160 TMD40-500
Pasado
Longitud (m) [m] 58 2 People protection: I@Max tripping time ( 0.60[kA])<=Ikmin L-PE ( 0.97[kA]); Trip time=0.40[s]; Uref=380V
Cable

Iz (A) [A] 40.5


1 Short circuit at terminal 2 (current flowing upstream): protected by
dV ( ) 0.18
Temp de Trabajo (°C) [°C] 30.8
Power loss [W] 7.25 Indirect touch at terminal 1 (current flowing upstream): protected by
K2S2 [A2s] 3375958 2

Rev. n1 Fecha: Descripcion Cliente: Numero de Dibujo:


Rev. n2 Dibujante: Proyecto:
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 1 2 2
Protección de cables

-WC4 TD-MA1
Datos de carga

Fases - Sistema de Distribución LLLN / TN-S Overload: protected by -QF5 T2N 160 TMD50-500
Pasado
Voltaje [V] 380 Overload: Ib (38.21[A]) <= Ith (40.24[A]) <= Iz (73.46[A]) and If (52.31[A]) <= 1.45*Iz (106.51[A]); Uref=380V
IB (A) [A] 38.2
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF5 T2N 160 TMD50-500

Protection checks
Cosphi 0.90 Pasado
Short-circuit: Protection guaranteed up to Ik LLL (19.50[kA]), Ik LN (11.52[kA]), Ik L-PE (11.52[kA]); Uref=380V
Sección transversal de los cables 3x(1x50)+1x(1x25)+1G25
Aislador Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QF5 T2N 160 TMD50-500
Pasado
Longitud (m) [m] 76 2 People protection: I@Max tripping time ( 0.46[kA])<=Ikmin L-PE ( 1.49[kA]); Trip time=5.00[s]; Uref=380V
Cable

Iz (A) [A] 73.5


1 Short circuit at terminal 2 (current flowing upstream): protected by
dV ( ) 0.53
Temp de Trabajo (°C) [°C] 40.8
Power loss [W] 133.52 Indirect touch at terminal 1 (current flowing upstream): protected by
K2S2 [A2s] 32968341 2

-WC5 TD-BO4
Datos de carga

Fases - Sistema de Distribución LLLN / TN-S Overload: protected by -QF6 XT4N 160 Ekip LSI R40
Pasado
Voltaje [V] 380 Overload: Ib (11.43[A]) <= Ith (16.00[A]) <= Iz (51.93[A]) and If (20.80[A]) <= 1.45*Iz (75.29[A]); Uref=380V
IB (A) [A] 11.4
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF6 XT4N 160 Ekip LSI R40
Cosphi 0.90 Protection checks Pasado
Short-circuit: Protection guaranteed up to Ik LLL (19.50[kA]), Ik LN (11.52[kA]), Ik L-PE (11.52[kA]); Uref=380V
Sección transversal de los cables 3x(1x25)+1x(1x16)+1G16
Aislador Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QF6 XT4N 160 Ekip LSI R40
Pasado
Longitud (m) [m] 147 2 People protection: I@Max tripping time ( 0.22[kA])<=Ikmin L-PE ( 0.47[kA]); Trip time=0.40[s]; Uref=380V
Cable

Iz (A) [A] 51.9


1 Short circuit at terminal 2 (current flowing upstream): protected by
dV ( ) 0.57
Temp de Trabajo (°C) [°C] 31.9
Power loss [W] 44.69 Indirect touch at terminal 1 (current flowing upstream): protected by
K2S2 [A2s] 8242085 2

-WC6 TDE-G1
Datos de carga

Fases - Sistema de Distribución LLLN / TN-S Overload: protected by -QF8 T5N 630 PR221DS-LS/I 630A
Pasado
Voltaje [V] 380 Overload: Ib (508.74[A]) <= Ith (579.60[A]) <= Iz (1010.74[A]) and If (753.48[A]) <= 1.45*Iz (1465.57[A]); Uref=380V
IB (A) [A] 508.7
1 Short circuit at terminal 1 (current flowing downstream): protected by -QF8 T5N 630 PR221DS-LS/I 630A
Protection checks

Cosphi 0.90 Pasado


Short-circuit: Protection guaranteed up to Ik LLL (19.50[kA]), Ik LN (11.52[kA]), Ik L-PE (11.52[kA]); Uref=380V
Sección transversal de los cables 6x(1x185)+2x(1x95)+2G95
Aislador Cu / PVC Indirect touch at terminal 2 (current flowing downstream): protected by -QF8 T5N 630 PR221DS-LS/I 630A
Pasado
Longitud (m) [m] 16 2 People protection: I@Max tripping time ( 2.95[kA])<=Ikmin L-PE ( 8.54[kA]); Trip time=5.00[s]; Uref=380V
Cable

Iz (A) [A] 1010.7


1 Short circuit at terminal 2 (current flowing upstream): protected by
dV ( ) 0.31
Temp de Trabajo (°C) [°C] 40.1
Power loss [W] 671.56 Indirect touch at terminal 1 (current flowing upstream): protected by
K2S2 [A2s] 451336583 2

Rev. n1 Fecha: Descripcion Cliente: Numero de Dibujo:


Rev. n2 Dibujante: Proyecto:
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 2 2
Lista de aparatos de BT

Símbolo Código de Parte Tipo Código RCB Tipo de RCB Descripción de Usuario 1 Descripción de Usuario 2
-QF1 1SDA060268R1 T6N 800 PR221DS-LS/I 800A TD-G1
-QF2 1SDA066725R1 A1N 125 TMF 40-400 TD-VES1
-QF3 1SDA060268R1 T6N 800 PR221DS-LS/I 800A TD-G1
-QF4 1SDA050918R1 T1N 160 TMD40-500 TD-BO3
-QF5 1SDA050955R1 T2N 160 TMD50-500 TD-MA1
-QF6 1SDA068132R1 XT4N 160 Ekip LSI R40 TD-BO4
-QF8 1SDA054396R1 T5N 630 PR221DS-LS/I 630A TDE-G1

Rev. n1 Fecha: Descripcion Cliente: Numero de Dibujo:


Rev. n2 Dibujante: Proyecto:
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 1 1
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20

A
Reporte de interruptores en BT

Interruptor Automático Termomagnético Electrónico Dispositivo RCB

B Símbolo Cuadro Polos In (A) Icu-Icn (kA) Ics (kA) Thermal (A) L I1 S I2 S2 I2-2 I G I4 R I5 InN/In (%) Id (A) Td (s)

Tipo Descripción de Usuario 1 Magnetic (A) Curva L t1 Curva S t2 Curva S2 t2-2 I3 Curva G t4 t5 Tipo RCB

C -QF1 +Q1 3P 800 36.0 36.0 On 0.76 Off On (null)

T6N 800 PR221DS-LS/I 800A TD-G1 3s 4.50

D -QF2 +Q1 3P 40 36.0 0.0 40.0 On Off (null)

A1N 125 TMF 40-400 TD-VES1 400.0

E -QF3 +Q2 3P 800 36.0 0.0 On 0.76 Off On (null)

T6N 800 PR221DS-LS/I 800A TD-G1 3s 4.50

F -QF4 +Q1 3P 40 36.0 0.0 34.0

T1N 160 TMD40-500 TD-BO3 500.0

G -QF5 +Q1 3P 50 36.0 0.0 40.2

T2N 160 TMD50-500 TD-MA1 500.0

H -QF6 +Q1 3P 40 36.0 0.0 On 0.40 Off On (null)

XT4N 160 Ekip LSI R40 TD-BO4 3s I2t const. 4.50

I -QF8 +Q1 3P 630 36.0 0.0 On 0.92 Off On (null)

T5N 630 PR221DS-LS/I 630A TDE-G1 3s 4.50

Rev. n1 Fecha: Descripcion Cliente: Numero de Dibujo:


N Rev. n2 Dibujante: Proyecto:
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 1 1
List of Lv Cables

-WC1 TD-G1
Fases - Sistema de Distribución LLLN / TN-S Ib L1 [A] 550.5 R Ph 20°C [mOhm] 0.39
Voltaje [V] 380 Ib L2 [A] 550.5 R Ph 160°C [mOhm] 0.60
Sección transversal de los cables 6x(1x240)+2x(1x120)+2G120 Ib L3 [A] 550.5 XF [mOhm] 0.79
Aislador Cu / PVC Ib N [A] 0.0 R N 20°C [mOhm] 0.77
Método 34 Cosphi 0.90 R N 160°C [mOhm] 1.20
Factor K 0.97 Iz (A) [A] 1193.1 XN [mOhm] 0.79
Longitud (m) [m] 10 dV ( ) [%] 0.18 R PE 20°C [mOhm] 0.77
Ib máx (kA) [kA] 20.89 Potencia Disipatada (W) [W] 376.6 R PE 160°C [mOhm] 1.20
Ib mín (kA) [kA] 9.90 Temp de Trabajo (°C) [°C] 38.5 X PE [mOhm] 0.79

-WC2 TD-VES1
Fases - Sistema de Distribución LLLN / TN-S Ib L1 [A] 13.5 R Ph 20°C [mOhm] 104.40
Voltaje [V] 380 Ib L2 [A] 13.5 R Ph 160°C [mOhm] 162.86
Sección transversal de los cables 3x(1x25)+1x(1x16)+1G16 Ib L3 [A] 13.5 XF [mOhm] 13.54
Aislador Cu / PVC Ib N [A] 0.0 R N 20°C [mOhm] 163.12
Método 71 Cosphi 0.90 R N 160°C [mOhm] 254.47
Factor K 0.63 Iz (A) [A] 51.9 XN [mOhm] 13.68
Longitud (m) [m] 141 dV ( ) [%] 0.64 R PE 20°C [mOhm] 163.12
Ib máx (kA) [kA] 19.50 Potencia Disipatada (W) [W] 59.7 R PE 160°C [mOhm] 254.47
Ib mín (kA) [kA] 0.49 Temp de Trabajo (°C) [°C] 32.7 X PE [mOhm] 13.68

-WC3 TD-BO3
Fases - Sistema de Distribución LLLN / TN-S Ib L1 [A] 5.9 R Ph 20°C [mOhm] 67.10
Voltaje [V] 380 Ib L2 [A] 5.9 R Ph 160°C [mOhm] 104.67
Sección transversal de los cables 4x(1x16)+1G16 Ib L3 [A] 5.9 XF [mOhm] 5.63
Aislador Cu / PVC Ib N [A] 0.0 R N 20°C [mOhm] 67.10
Método 71 Cosphi 0.90 R N 160°C [mOhm] 104.67
Factor K 0.63 Iz (A) [A] 40.5 XN [mOhm] 5.63
Longitud (m) [m] 58 dV ( ) [%] 0.18 R PE 20°C [mOhm] 67.10
Ib máx (kA) [kA] 19.50 Potencia Disipatada (W) [W] 7.2 R PE 160°C [mOhm] 104.67
Ib mín (kA) [kA] 0.97 Temp de Trabajo (°C) [°C] 30.8 X PE [mOhm] 5.63

-WC4 TD-MA1
Fases - Sistema de Distribución LLLN / TN-S Ib L1 [A] 38.2 R Ph 20°C [mOhm] 28.14
Voltaje [V] 380 Ib L2 [A] 38.2 R Ph 160°C [mOhm] 43.89
Sección transversal de los cables 3x(1x50)+1x(1x25)+1G25 Ib L3 [A] 38.2 XF [mOhm] 7.07
Aislador Cu / PVC Ib N [A] 0.0 R N 20°C [mOhm] 56.27
Método 71 Cosphi 0.90 R N 160°C [mOhm] 87.78
Factor K 0.63 Iz (A) [A] 73.5 XN [mOhm] 7.30
Longitud (m) [m] 76 dV ( ) [%] 0.53 R PE 20°C [mOhm] 56.27
Ib máx (kA) [kA] 19.50 Potencia Disipatada (W) [W] 133.5 R PE 160°C [mOhm] 87.78
Ib mín (kA) [kA] 1.49 Temp de Trabajo (°C) [°C] 40.8 X PE [mOhm] 7.30

Rev. n1 Fecha: Descripcion Cliente: Numero de Dibujo:


Rev. n2 Dibujante: Proyecto:
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 1 2 2
List of Lv Cables

-WC5 TD-BO4
Fases - Sistema de Distribución LLLN / TN-S Ib L1 [A] 11.4 R Ph 20°C [mOhm] 108.84
Voltaje [V] 380 Ib L2 [A] 11.4 R Ph 160°C [mOhm] 169.79
Sección transversal de los cables 3x(1x25)+1x(1x16)+1G16 Ib L3 [A] 11.4 XF [mOhm] 14.11
Aislador Cu / PVC Ib N [A] 0.0 R N 20°C [mOhm] 170.06
Método 71 Cosphi 0.90 R N 160°C [mOhm] 265.29
Factor K 0.63 Iz (A) [A] 51.9 XN [mOhm] 14.26
Longitud (m) [m] 147 dV ( ) [%] 0.57 R PE 20°C [mOhm] 170.06
Ib máx (kA) [kA] 19.50 Potencia Disipatada (W) [W] 44.7 R PE 160°C [mOhm] 265.29
Ib mín (kA) [kA] 0.47 Temp de Trabajo (°C) [°C] 31.9 X PE [mOhm] 14.26

-WC6 TDE-G1
Fases - Sistema de Distribución LLLN / TN-S Ib L1 [A] 508.7 R Ph 20°C [mOhm] 0.80
Voltaje [V] 380 Ib L2 [A] 508.7 R Ph 160°C [mOhm] 1.25
Sección transversal de los cables 6x(1x185)+2x(1x95)+2G95 Ib L3 [A] 508.7 XF [mOhm] 1.26
Aislador Cu / PVC Ib N [A] 0.0 R N 20°C [mOhm] 1.56
Método 34 Cosphi 0.90 R N 160°C [mOhm] 2.43
Factor K 0.97 Iz (A) [A] 1010.7 XN [mOhm] 1.27
Longitud (m) [m] 16 dV ( ) [%] 0.31 R PE 20°C [mOhm] 1.56
Ib máx (kA) [kA] 19.50 Potencia Disipatada (W) [W] 671.6 R PE 160°C [mOhm] 2.43
Ib mín (kA) [kA] 8.54 Temp de Trabajo (°C) [°C] 40.1 X PE [mOhm] 1.27

Fases - Sistema de Distribución Ib L1 [A] R Ph 20°C [mOhm]


Voltaje [V] Ib L2 [A] R Ph 160°C [mOhm]
Sección transversal de los cables Ib L3 [A] XF [mOhm]
Aislador Ib N [A] R N 20°C [mOhm]
Método Cosphi R N 160°C [mOhm]
Factor K Iz (A) [A] XN [mOhm]
Longitud (m) [m] dV ( ) [%] R PE 20°C [mOhm]
Ib máx (kA) [kA] Potencia Disipatada (W) [W] R PE 160°C [mOhm]
Ib mín (kA) [kA] Temp de Trabajo (°C) [°C] X PE [mOhm]

Fases - Sistema de Distribución Ib L1 [A] R Ph 20°C [mOhm]


Voltaje [V] Ib L2 [A] R Ph 160°C [mOhm]
Sección transversal de los cables Ib L3 [A] XF [mOhm]
Aislador Ib N [A] R N 20°C [mOhm]
Método Cosphi R N 160°C [mOhm]
Factor K Iz (A) [A] XN [mOhm]
Longitud (m) [m] dV ( ) [%] R PE 20°C [mOhm]
Ib máx (kA) [kA] Potencia Disipatada (W) [W] R PE 160°C [mOhm]
Ib mín (kA) [kA] Temp de Trabajo (°C) [°C] X PE [mOhm]

Rev. n1 Fecha: Descripcion Cliente: Numero de Dibujo:


Rev. n2 Dibujante: Proyecto:
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 2 2
Lista de Cargas

-L69 TD-BO4
Fases - Sistema de Distribución LLLN / TN-S Factor de utlización [%] 100 Voltage computado [V] 377.2
Voltaje nominal [V] 380 Potencia Activa P [kW] 6.72 Máx caída de tensión admitida por el standard [%] 4.0
IB [A] 11.4 Potencia Reactiva Q [kvar] 3.25 Máx caída de tensión admitida por el usuario [%] 3.0
Cosphi 0.90 Caída de tensión calculada [%] 0.75

-L70 TD-MA1
Fases - Sistema de Distribución LLLN / TN-S Factor de utlización [%] 100 Voltage computado [V] 377.3
Voltaje nominal [V] 380 Potencia Activa P [kW] 22.48 Máx caída de tensión admitida por el standard [%] 4.0
IB [A] 38.2 Potencia Reactiva Q [kvar] 10.89 Máx caída de tensión admitida por el usuario [%] 4.0
Cosphi 0.90 Caída de tensión calculada [%] 0.71

-L71 TD-BO3
Fases - Sistema de Distribución LLLN / TN-S Factor de utlización [%] 100 Voltage computado [V] 378.7
Voltaje nominal [V] 380 Potencia Activa P [kW] 3.47 Máx caída de tensión admitida por el standard [%] 4.0
IB [A] 5.9 Potencia Reactiva Q [kvar] 1.68 Máx caída de tensión admitida por el usuario [%] 4.0
Cosphi 0.90 Caída de tensión calculada [%] 0.35

-L72 TD-VES1
Fases - Sistema de Distribución LLLN / TN-S Factor de utlización [%] 100 Voltage computado [V] 376.9
Voltaje nominal [V] 380 Potencia Activa P [kW] 7.91 Máx caída de tensión admitida por el standard [%] 4.0
IB [A] 13.5 Potencia Reactiva Q [kvar] 3.83 Máx caída de tensión admitida por el usuario [%] 3.0
Cosphi 0.90 Caída de tensión calculada [%] 0.82

-L73 TDE-G1
Fases - Sistema de Distribución LLLN / TN-S Factor de utlización [%] 100 Voltage computado [V] 378.1
Voltaje nominal [V] 380 Potencia Activa P [kW] 299.89 Máx caída de tensión admitida por el standard [%] 4.0
IB [A] 508.7 Potencia Reactiva Q [kvar] 145.24 Máx caída de tensión admitida por el usuario [%] 3.0
Cosphi 0.90 Caída de tensión calculada [%] 0.49

Fases - Sistema de Distribución Factor de utlización [%] Voltage computado [V]


Voltaje nominal [V] Potencia Activa P [kW] Máx caída de tensión admitida por el standard [%] 4.0
IB [A] Potencia Reactiva Q [kvar] Máx caída de tensión admitida por el usuario [%]
Cosphi Caída de tensión calculada [%]

Fases - Sistema de Distribución Factor de utlización [%] Voltage computado [V]


Voltaje nominal [V] Potencia Activa P [kW] Máx caída de tensión admitida por el standard [%] 4.0
IB [A] Potencia Reactiva Q [kvar] Máx caída de tensión admitida por el usuario [%]
Cosphi Caída de tensión calculada [%]

Rev. n1 Fecha: Descripcion Cliente: Numero de Dibujo:


Rev. n2 Dibujante: Proyecto:
Rev. n3 Diseñador: Archivo: Página: Siguiente página: Páginas:
REVISIONES Fecha: Firmas Aprobador: Serie: 1 1
List of Busbars

-B1 TD-G1
Fases - Sistema de Distribución LLLN / TN-S Ib LLL (kA) Ib LLL (kA) Ip LLL (kA) Ib LL (kA) Ip LL (kA)

S.C. currents
Demand factor 0.95 19.50 19.50 46.68 16.89 40.42
Load data

Voltaje nominal [V] 380


Voltage computado [V] 379.3
IB [A] 550.5 Ib LN (kA) Ib LN (kA) Ip LN (kA) Ib LPE (kA) Ip LPE (kA)
Cosphi 0.90 11.52 11.52 27.57 11.52 27.57

Fases - Sistema de Distribución Ib LLL (kA) Ib LLL (kA) Ip LLL (kA) Ib LL (kA) Ip LL (kA)

S.C. currents
Demand factor
Load data

Voltaje nominal [V]


Voltage computado [V]
IB [A] Ib LN (kA) Ib LN (kA) Ip LN (kA) Ib LPE (kA) Ip LPE (kA)
Cosphi

Fases - Sistema de Distribución Ib LLL (kA) Ib LLL (kA) Ip LLL (kA) Ib LL (kA) Ip LL (kA)

S.C. currents
Demand factor
Load data

Voltaje nominal [V]


Voltage computado [V]
IB [A] Ib LN (kA) Ib LN (kA) Ip LN (kA) Ib LPE (kA) Ip LPE (kA)
Cosphi

Fases - Sistema de Distribución Ib LLL (kA) Ib LLL (kA) Ip LLL (kA) Ib LL (kA) Ip LL (kA)

S.C. currents
Demand factor
Load data

Voltaje nominal [V]


Voltage computado [V]
IB [A] Ib LN (kA) Ib LN (kA) Ip LN (kA) Ib LPE (kA) Ip LPE (kA)
Cosphi

Fases - Sistema de Distribución Ib LLL (kA) Ib LLL (kA) Ip LLL (kA) Ib LL (kA) Ip LL (kA)
S.C. currents

Demand factor
Load data

Voltaje nominal [V]


Voltage computado [V]
IB [A] Ib LN (kA) Ib LN (kA) Ip LN (kA) Ib LPE (kA) Ip LPE (kA)
Cosphi