For the owner and the heating engineer

Operating and Installation Manual


VRC 400

Programmable weather compensator with separat HW time control

GB
Contents

Contents 4 Operation. . . . . . . . . . . . . . . . . . 9
4.1 Setting the operating modes ...... 9
Notes on the documentation . . . . . 4 4.2 Setting the current day and
Symbols used........................................... 4 time ................................................... 12
Storage of the documents.................... 4 4.3 Setting timer programmes .......... 13
4.4 Setting the room temperature ... 16
Safety . . . . . . . . . . . . . . . . . . . . . . . . 5 4.5 Setting the hot water
temperature .................................... 19
Operating manual. . . . . . . . . . . . . . . 6 4.6 Activating special functions ........ 20
4.7 Info level........................................... 22
1 Control overview. . . . . . . . . . . . 6
5 Vaillant warranty . . . . . . . . . . . 23
2 Display overview. . . . . . . . . . . . 7
6 Recycling and disposal. . . . . . . 24
3 Description of the control . . . . 8

2 Operating manual and installation manual for VRC 400 weather compensator
Contents

Installation manual . . . . . . . . . . . . . 25 10 Electrical installation. . . . . . . . 33


10.1 Connecting the weather
7 Information on installation compensator ................................... 34
and operation . . . . . . . . . . . . . . 25 10.2 Connecting the outside sensor... 34
7.1 CE label............................................. 25
7.2 Intended use.................................... 25 11 Start-up. . . . . . . . . . . . . . . . . . . 35
11.1 Installer level................................... 36
8 Safety instructions and 11.2 Service/diagnostic level................ 40
regulations . . . . . . . . . . . . . . . . 26 11.3 Handing over to the owner.......... 42
8.1 Safety instructions ........................ 27
8.2 Regulations...................................... 27 12 Technical data. . . . . . . . . . . . . . 43

9 Installation . . . . . . . . . . . . . . . . 28 13 Vaillant customer service . . . . 43


9.1 Control installation ........................ 28
9.2 Wall mounting ................................. 28
9.3 Installing the VRC 693 outdoor
sensor ............................................... 30

Operating manual and installation manual for VRC 400 weather compensator 3
Notes on the documentation

Notes on the documentation Symbols used


Please observe the safety instructions in
The following information is intended to this manual for the installation of the
help you throughout the entire docu- control.
mentation. Further documents apply in
combination with this installation and Danger
operation manual. Immediate risk of serious injury
We accept no liability for any damage or death
caused by failure to observe these
instructions. • Symbol for a necessary task

Storage of the documents


Please pass on this operating and installa-
tion manual to the owner of the system
so that he can keep it available whenev-
er it is required.

4 Operating manual and installation manual for VRC 400 weather compensator
Safety

Safety
The weather compensator must be
installed by a qualified engineer, who is
responsible for adhering to the existing
standards and regulations.

We accept no liability for any damage


caused by failure to observe these
instructions.

Operating manual and installation manual for VRC 400 weather compensator 5
1 Control overview

Operating manual

1 Control overview
Key
1 Display
1 2 Dial (turn and click)
I Info button
F Special functions button
2 P Programming button/installer level

Fig. 1.1 Control overview

6 Operating Manual for VRC 400 weather compensator


Display overview 2

2 Display overview

9 Key
8
1 1 Installer level and
10 service/diagnosis level (see 11.1)
7
2
2 Info level (see 4.7)
3
3 Circulation pump symbol
11 4 Time/temperature display
6
12
5 Days of the week
5 6 Actual temperature
7 Operating modes (see 4.1)
4 8 Special functions (see 4.6)
9 Setting timer programmes (see 4.3)
Fig. 2.1 Overview of display 10 Boiler operation indicator
11 Hot water symbol
12 Heating circuit symbol

Operating Manual for VRC 400 weather compensator 7


3 Description of the control

3 Description of the
control
The VRC 400 is a weather compensator
with a weekly programme for heating,
hot water and a circulation pump for
connecting to Vaillant boilers with an
eBus.
The VRC 400 enables you to set heating
programmes depending on the outside
temperature. In addition, you can select
special functions such as the party func-
tion, and control the timed operation of
hot water and a separate circulation
pump.

8 Operating Manual for VRC 400 weather compensator


Operation 4

4 Operation 4.1 Setting the operating modes


Table 4.1 contains an overview of the
The operating principle uses three but- operating modes you can select.
tons and a dial (Vaillant “Turn and Click” The selected operating mode affects the
operating concept). timer programmes both for heating and
The display normally shows the current for hot water and the circulation pump.
operating mode (e.g. ), or, if activat- • When the weather compensator is in
ed, the special function and the cur- normal display mode, press the dial
rent room temperature, the day of the once – the symbol for the selected
week, the time and the symbol for mode flashes in the display.
heating, hot water and/or the circula- • Turn the dial until the display shows
tion pump, depending on which is the operating mode you want.
requested.
The display switches back to normal
mode after five seconds.

Operating Manual for VRC 400 weather compensator 9


4 Operation

Symbol Meaning Meaning


Heating Hot water/circulation pump
Automatic:
According to the timer programmes set in the The hot water cylinder/circulation
weather compensator, the heating circuit switches pump mode switches between heat-
between heating mode and set-back mode . ing ON and OFF according to the
The heating circuit symbol is displayed if a heating timer programme set on the control-
requirement is detected. ler. The hot water symbol and the
Heating: circulation pump symbol are shown
The heating circuit is operated according to the when the time window is active. If
room temperature, regardless of the programme set there is a hot water request, the hot
on the controller. water symbol flashes.
The heating circuit symbol is displayed if a heating
requirement is detected.
Set-back:
The heating circuit is operated according to the
set-back temperature “ECO”, regardless of the pro-
gramme set on the controller.
The heating circuit symbol is displayed if a heating
requirement is detected.

10 Operating Manual for VRC 400 weather compensator


Operation 4

Symbol Meaning Meaning


Heating Hot water/circulation pump
ECO:
According to the setted timer programmes, the See the table on the left
heating circuit switches between heating mode
and OFF. The heating circuit is switched off in set-
back mode, provided the anti-frost function (activat-
ed when the outside temperature is below 3 °C) is
not active. The heating circuit symbol is displayed if
a heating requirement is detected or the anti-frost
function is active.
Off:
The heating circuit is off, provided that the frost The boiler is not heated up, regard-
protection function (if the outside temperature is less of the set timer programme. The
below 3 °C) is not activated. If the frost protection circulation pump is switched off.
function is activated, the heating circuit symbol is The hot water and circulation pump
displayed. symbols are not displayed.

Table 4.1 Operating modes

Operating Manual for VRC 400 weather compensator 11


4 Operation

4.2 Setting the current day and time • Press the dial. The hours start flashing.
• Turn the dial until you see the current
To set the current day and time with the hour.
display in normal mode, you must per- • Press the dial. The minutes start flash-
form the following steps: ing.
• Press the dial until a day of the week • Turn the dial until you see the current
starts flashing. minute.
• Turn the dial until you see the current
day of the week. The display switches back to normal
MO = Monday mode after five seconds.
TU = Tuesday If the calendar is activated on the install-
WE = Wednesday er level (see 11.1), you can set the day,
TH = Thursday month and year in the same way.
FR = Friday This allows automatic switching from win-
SA = Saturday ter to summer time.
SU = Sunday

12 Operating Manual for VRC 400 weather compensator


Operation 4

4.3 Setting timer programmes You can adapt the default programmes
The controller is equipped with a basic to suit your needs. There are six steps to
program (Table 4.2). setting the times you want:
1. Press the programming button P
Time Day/Block of Start End 2. Select the timer programme (heating,
window days time time
hot water or circulation pump)
H1 MO-FR 6:00 22:00
3. Select the time window
H2 - - -
4. Select the day or block of days
H3 - - -
5. Set the start time
H1 SA 7:30 23:30
6. Set the end time
H2 - - -
H3 - - - You can define three time windows for
H1 SU 7:30 22:00 each day.
H2 - - - When you press the P button the display
H3 - - - returns to basic mode.
Table 4.2 Default heating, hot water and cir-
culation programmes

Operating Manual for VRC 400 weather compensator 13


4 Operation

The table below illustrates the individual Display Required steps


Press the programming
steps again, using the example of the hot button P. The cursor (black
water timer programme. triangle) marks the value
If you want to change the timer pro- which can be changed
gramme for heating or the circulation ( ), which also flashes.
Turn the dial until you see
pump, after pressing the programming the hot water symbol.
button P, select the corresponding sym-
Press the dial. The cursor
bol (heating circuit or circulation pump) marks the adjustable value
and continue as shown in the example. (H1), which also flashes.
Select the time window by
turning the dial.
Settings: H1, H2, H3

14 Operating Manual for VRC 400 weather compensator


Operation 4

Display Required steps Display Required steps


Press the dial. The cursor Press the dial. The cursor
marks the days of week dis- marks the start time and the
play, which also flashes. hour display flashes.
Select a block of days or a Select the start time by
single day of the week by turning the dial. Press the
turning the dial. dial again to set the min-
Settings: utes.
MO - SU
MO - FR Press the dial. The cursor
SA - SU marks the end time and the
MO = Monday hour display flashes.
TU = Tuesday Select the end time by turn-
WE = Wednesday ing the dial.
TH = Thursday Click the dial again to set
FR = Friday the minutes.
SA = Saturday
SU = Sunday Table 4.3 Setting time windows

Operating Manual for VRC 400 weather compensator 15


4 Operation

If necessary, you can switch the weather You can set the room temperature
compensator from the week programme directly from the basic display. If the
to a daily programme. temperature level function is activated
• With the display in normal mode, press on the installer level (setting different
the F button for 10 seconds. temperatures for each time window, see
When you programme time windows, 11.1), the display shows the currently set -
days of the week will no longer be dis- room temperature (T-H1, T-H2, T-H3).
played.
If the controller is installed outside the
4.4 Setting the room temperature boiler in a wall mounting box, the basic
If the controller is installed in the boiler, display shows the room temperature cur-
the basic display shows the set room rently measured.
temperature, from which the required
flow temperature for the set heating
curve is calculated.

16 Operating Manual for VRC 400 weather compensator


Operation 4

move the set heating curve parallel on a


45° axis and the flow temperature calcu-
lated by the weather compensator.

Setting the required room temperature


directly
• Turn the dial (with the display in nor-
mal mode).
The current temperature display disap-
pears, the sun symbol is displayed on
the mode level and the required room
Fig. 4.1 Set room temperature diagram temperature is shown (e. g. TEMP
20.0 °C).
The diagram in fig. 4.1 shows you the • By turning the dial you can set the
relationship between the set room tem- required room temperature directly
perature and the heating curve. If you (after 1 second).
increase the set room temperature, you

Operating Manual for VRC 400 weather compensator 17


4 Operation

The display switches back to normal • Press the dial. T-H2 is displayed along
mode after five seconds. with a set value.
The set value flashes.
Setting the room temperature for time • Turn the dial until you see the room
windows temperature you want for the time win-
(Only possible if the temperature level dow H2.
function is set on the installer level, see The new room temperature is assigned
11.1). In this case you can set different to all time windows with H2.
room temperatures for each time window. • Press the dial. T-H3 is displayed along
• Press the dial several times until T-H1 with a set value.
appears in the display along with a set The set value flashes.
value. The set value flashes. • Turn the dial until you see the room
• Turn the dial until you see the room tem- temperature you want for the time win-
perature you want for the time window H1. dow H3.
The new room temperature is assigned The new room temperature is assigned
to all time windows with H1. to all time windows with H3.

18 Operating Manual for VRC 400 weather compensator


Operation 4

The display switches back to normal 4.5 Setting the hot water
mode after five seconds. temperature
You can set the hot water temperature
Setting the set-back temperature from the basic display.
“ECO” Please note the set maximum hot water
• Press the dial several times until ECO temperature on the boiler.
appears in the display. The set-back • Press the dial several times until DHW
temperature is displayed and starts appears in the display. The set value
flashing. flashes.
• Turn the dial until the required set-back • Turn the dial until the required hot
temperature is displayed (e.g. ECO water temperature is displayed (e.g.
15.0 °C). DHW 60 °C).
The display switches back to normal
The display switches back to normal mode after five seconds.
mode after five seconds.

Operating Manual for VRC 400 weather compensator 19


4 Operation

4.6 Activating special functions Display Required steps


Energy-Saving function
Press the F button to access the special The energy-saving function lets
functions. You can activate the following you lower the heating for an
adjustable period regardless of
functions: the set heating programme. Press
the special function button twice
Display Required steps and the energy-saving symbol
Quick veto appears on the display. You will
The quick veto function allows you also see the time flashing. Now
to adjust the room temperature turn the dial to set the end time
for a short time (until the next up to which the heating is oper-
time window). Press the special ated in set-back mode. The display
function button F once. The quick switches back to basic mode after
veto symbol appears in the display 10 seconds and the function is
along with the quick veto room activated.
temperature, which flashes. Turn To deactivate the function early,
the dial until the quick veto tem- just press the F button.
perature you want is displayed.
After 10 seconds, the display
returns to normal mode and the
function is activated. To deactivate
the function early, just press the
F button.

20 Operating Manual for VRC 400 weather compensator


Operation 4

Display Required steps Display Required steps


Party function One-time recharging/
When you activate the party Cylinder Boost
function the heating phase is con- This function allows you to fill
tinued beyond the next set-back the cylinder, regardless of the
phase. This also applies to the set timer programme. Press the
hot water and circulation pump special function button four times.
programmes. Press the special The once-only cylinder filling
function button F three times. The symbol appears in the display and
party symbol appears in the dis- the function is activated after ten
play and the function is activated seconds. If you want to deactivate
after ten seconds. the function early, just press the
The function is deactivated auto- F button.
matically on reaching the next
heating phase. If you want to
deactivate the function before, just
press the F button.
The function can be activated
only in “Auto” mode or “Eco”
mode.

Operating Manual for VRC 400 weather compensator 21


4 Operation

Display Required steps 4.7 Info level


Holiday function
The holiday function deactivates Press the info button to access the info
the weather compensator, but not level. The info symbol appears in the dis-
the frost protection function. The
hot water and circulation pump are play as soon as you open the info level.
also deactivated. Each time you press the info button, dif-
Press the special function button
F five times - the holiday function ferent information is displayed:
symbol flashes in the display. The - The name of the weather compensator
set value for the number of days‘
holiday also flashes. Turn the dial (VRC 400)
until the required number of day‘s - The quick veto room temperature (if
holiday appears. After 10 seconds
the function is activated and the
active)
mode is set to OFF for the selected - The set room temperature T-H1 (if acti-
period (see 4.1). vated - e.g. T-H1 20.0 °C)
If you want to deactivate the
function before, just press the F - The set room temperature T-H2 (if acti-
button. If the anti-legionnaire‘s vated - e.g. T-H2 23.0 °C)
disease function is activated, it is
performed on the last day of the - The set room temperature T-H3 (if acti-
holiday. vated - e.g. T-H3 20.0 °C)
Table 4.4 Special functions

22 Operating Manual for VRC 400 weather compensator


Operation 4, Vaillant warranty 5

- The set room temperature if the tem- 5 Vaillant warranty


perature level function is not activated
(e.g.. TEMP 21.5 °C) We only grant a Vaillant manufacturer‘s
- The current set-back temperature warranty if a suitably qualified engineer
(e.g. ECO 15.0 °C) has installed the system in accordance
- The set hot water temperature (e.g. with Vaillant instructions.
DHW 60 °C) The system owner will be granted a war-
- The day/month/year (if the calendar is ranty in accordance with the Vaillant
activated) terms and conditions. All requests for
- Timer programmes set for heating (eve- work during the guarantee period must
ry single time window per day) be made to Vaillant service
- Timer programmes set for hot water (0870 6060 777).
(every single time window per day)
- Timer programmes set for the circula-
tion pump (every single time window
per day)

Operating Manual for VRC 400 weather compensator 23


6 Recycling and disposal

6 Recycling and disposal


Neither the weather compensator or
any of its accessories belong in the
household waste. Make sure the old con-
trol and any accessories are disposed of
properly.

24 Operating Manual for VRC 400 weather compensator


Information on installation and operation 7

Installation manual ic compatibility and the low voltage


directive 73/23/EEC.
7 Information on installa-
tion and operation 7.2 Intended use
The VRC 400 weather compensator is a
The assembly, electrical connection, con- state-of-the-art control which has been
trol settings and commissioning may constructed in accordance with recog-
only be carried out by an approved com- nised safety regulations. Nevertheless,
pany specialising in heating engineering. there is a risk of death or serious injury
to the user or others, and the control or
7.1 CE label other property may be damaged in the
The CE label shows that the VRC 400 event of improper use or use for which it
weather compensator, when connected is not intended.
to Vaillant boilers, meets the basic
requirements of the Council of Europe‘s The VRC 400 weather compensator is
directive 89/336/EEC on electromagnet- designed to control a heating system
with a heating circuit with or without a

Installation Manual for VRC 400 weather compensator 25


7 Information on installation and operation, 8 Safety instructions and regulations

hot water system or circulation pump 8 Safety instructions and


according to weather conditions, time regulations
and location, in connection with a Vail-
lant boiler with an eBUS. The control must be installed by an
Any other use or extended use is consid- approved company specialised in heating
ered to be improper. The manufacturer or engineering, which is responsible for
supplier is not liable for any resulting compliance with applicable standards
damage. and regulations. We accept no liability
The user alone bears any risk. Intended for any damage caused by failure to
use includes the observance of the oper- observe these instructions.
ating and installation manual.

26 Installation Manual for VRC 400 weather compensator


Safety instructions and regulations 8

8.1 Safety instructions 8.2 Regulations


All wiring must be in accordance with
Danger! Building Regulations Part P, current IEE
Risk of fatal electric shock from regulations, and all other relevant regu-
touching live connections. lations and guidelines, and must be car-
Before working on the control, ried out by a suitably qualified person.
switch off the power supply and
prevent it from being switched Use standard commercial cables for the
on again. wiring.
Only remove the controller from - Minimum cross-section of wires:
its wall mounting or base when it 0.75 mm2
is not live. Do not exceed following maximum wire
lengths:
- Bus wires: 300 m
Connections with 230 V and bus wires
must be laid separately if longer than
10 m.

Installation Manual for VRC 400 weather compensator 27


8 Safety instructions and regulations, 9 Installation

The controller may only be installed in screen and to push the controller into
dry rooms. the supplied plug-in connection with a
pin bar.

9 Installation 9.2 Wall mounting


The VRC 400 weather compensator is
The weather compensator can be alter- designed so that it can be used as a
nately integrated in the boiler or e.g. can remote-control control with or without
be installed on the wall in the living area room modulation. The controller must be
with the wall socket provided with the installed to ensure that it can properly
control. It is connected to the boiler record the room temperature (away from
merely with a 2-core connection cable. heat traps, not mounted on cold walls
etc.).
9.1 Control installation The best place of installation is mostly in
To install the weather compensator the main living room on an inside wall at
directly in the front screen of the boiler, approx. 1.5 m height. There, the control-
you only need to remove the front ler will be able to record the circulating

28 Installation Manual for VRC 400 weather compensator


Installation 9

air, unhindered by furniture, curtains or 1


other objects. In the room where the
controller is installed, all radiator valves
must be fully open when using room
modulation. i F P

The connection to the boiler is a 2-core 5 3

bus cable (eBus), see fig. 10.1.


• Pull the weather compensator (1) out
of the mounting box (5).
2
• Drill two holes (3) of 6 mm diameter
(as shown in fig. 9.1) and put in the sup-
4
plied wall plugs.
• Thread the connection cable through
the duct (4). Fig 9.1 Mounting the controller
• Fix the mounting box to the wall with
the two screws provided.

Installation Manual for VRC 400 weather compensator 29


9 Installation

• Connect the lead as described in sec- ing equipment and for the heating con-
tion 10. troller.
• Place the weather compensator (1) on
the mounting box (5) so that the pins Installation location
on the back of the upper section fit The outdoor sensor should be installed
into the recesses (2). on the side of the house where the most
• Push the weather compensator onto frequented rooms are located. If this side
the mounting box until it catches. can‘t be clearly identified, then install it
on the north or north-west side of the
9.3 Installing the VRC 693 outdoor house.
sensor To ideally measure the outdoor tempera-
This equipment may only be opened by a ture, for houses up to three storeys, the
qualified specialist and installed as device should be fitted about two thirds
shown in the diagram. Current safety of the way up the wall. For taller build-
regulations must be followed as well as ings, installation is recommended
the installation instructions for the heat- between the 2nd and 3rd floors.

30 Installation Manual for VRC 400 weather compensator


Installation 9

The location should not be protected


from the wind, nor particularly exposed
and it should not be exposed to direct
sunlight. The device must be at least 1 m
away from any opening in the outer wall,
from which warm air can either continu- > 1 m 1/3

ously or occasionally issue.


It can be installed either in or on the
wall, depending on the accessibility of 2/3

the location.
O

S
ł

Ł
N

W
ð

N, NW (optional)

Fig. 9.2 Installation location of the VRC 693


outdoor sensor

Installation Manual for VRC 400 weather compensator 31


9 Installation

Caution!
There is a risk of the wall and
control becoming wet.
Lay the cables properly and
carefully to ensure that the out-
door sensor and the building are
not damaged by water.
The control must be fixed to the
wall in the correct position, as
shown in fig. 9.3.
The cable entry (3, fig. 9.3) must
point downwards.

Fig. 9.3 Fitting and positioning the outdoor


sensor

32 Installation Manual for VRC 400 weather compensator


Installation 9, Electrical installation 10

• Remove the cover (1) of the housing • Fix the top of the housing (1) to the
and fix the housing to the wall using bottom (2) using the screws supplied.
two screws through the fixing holes
(8).
• Lay a connection cable (4) of at least 10 Electrical installation
2 x 0.75 mm2 and pull it up through the
cable entry (3). The electrical connection may only be
Lay the cable properly and carefully to carried out by a suitably qualified engi-
ensure that the sensor and the wall neer.
are not damaged by water.
• Wire up the terminals as shown in the Danger!
diagram in fig. 10.1. Risk of fatal electric shock from
• Make sure the housing seal is correctly touching live connections. Before
fixed in the top section of the housing working on the control, turn off
(1) and push the top section onto the the power supply and secure
housing. against restart.

Installation Manual for VRC 400 weather compensator 33


10 Electrical installation

10.1 Connecting the weather com- Also follow the instructions for the boil-
pensator er. Do not remove the jumper between ter-
If the weather compensator is integrated minals 3 and 4 on the boiler.
directly in the boiler, the electrical con-
nection is directly through the pin bars 10.2 Connecting the outside sensor
that are introduced in the connecting The external probe is connected directly
plug in the boiler. on the boiler. Please observe the boiler
For wall mounting, the communciation to manual while connecting the control.
the boiler is through the eBus. All eBus-
connectors are designed to take at least
2 x 0.75 mm2 (recommended) per termi-
nal.
This means that the wires can be
swapped without impairing communica-
tion (fig. 10.1).

34 Installation Manual for VRC 400 weather compensator


Electrical installation 10, Start-up 11

11 Start-up
Certain system parameters have to be
set in order for them to best suit the
actual conditions. These system parame-
ters are all together in the intaller level
and should only be set by the heating
engineer.
The service/diagnostic level is also
intended for the engineer and is
designed to help during servicing.

Fig. 10.1 Electrical connection

Installation Manual for VRC 400 weather compensator 35


11 Start-up

11.1 Installer level Display Setting by turning the dial


Press the P button to access the installer Set-back temperature
level. Default setting: 15 °C
• Press the P button for 10 seconds. Adjustment range:
The spanner symbol and the first 5 ... 30 °C
parameter appear in the display.
• Press the dial. You can select all the Set hot water temperature
system parameters in turn. Default setting: 60 °C
• Turn the dial to set the values you Adjustment range:
35 ... 70 °C
want.
When you press the P button the display
returns to basic mode. Correction of actual room
temperature
Adjustment of the displayed
You can select and change the following value in the range of max.
parameters: +/- 3 °C
Factory setting 0 °C

36 Installation Manual for VRC 400 weather compensator


Start-up 11

Display Setting by turning the dial Display Setting by turning the dial

Anti-legionnaire’s disease Heating curve


system The heating curve repre-
1=Activate the anti-legion- sents the ratio between out-
naire‘s disease function. side temperature and target
Every Wednesday, one flow temperature.
hour before the first time Default setting: 1,2
window, a connected hot Room temperature modula-
water cyclinder is heated to tion (wall installation only)
70 °C, the circulation pump 1 = Room temperature
is switched on and oper- modulation
ated at 70 °C for at least 30 (including the room tem-
minutes. perature in the flow tem-
Default setting = 0 (off) perature calculation)
2 = Thermostat function
(switching off the heating
when the set room tempera-
ture is reached)
Default setting: 0 = No room
modulation

Installation Manual for VRC 400 weather compensator 37


11 Start-up

Display Setting by turning the dial Display Setting by turning the dial

Minimum temperature Outside temperature shut-


(foot point) down threshold
Adjustment range Shurtdown temperature for
15 ... 90 °C demand-based deactivation
Default setting: 15 °C of heating
Adjustment range:
Frost protection delay 5 ... 50 °C
Timed suppression of anti- Default setting: 22 °C
frost function
Outside temperature cor-
(activated at outside tem-
rection
peratures below 3 °C)
Corrects the temperature
Adjustment range: 0 ... 12 h
currently measured by the
Default setting: 0 h
set value to compensate for
outside influences
Adjustment range:
-5 ... +5 °C
Default setting: 0 °C

38 Installation Manual for VRC 400 weather compensator


Start-up 11

Display Setting by turning the dial Display Setting by turning the dial

Hydraulic switch Year setting


1 = Activation of sensor For activation of the
recording when the hydrau- calendar
lic switch is used, default
setting 0 = Off

Day setting Temperature level


For activation of the Activate the setting for
calendar different temperatures for
each time window.
0 = Temperaturel level off
1 = Temperature level on,
Month setting default setting: 0
For activation of the
calendar

Installation Manual for VRC 400 weather compensator 39


11 Start-up

Display Setting by turning the dial 11.2 Service/diagnostic level


Temperature level time
Access the service/diagnostic level by
window H1 pressing the P button and the dial.
• Press the P button and the dial simul-
(only when temperature taneously for 3 seconds.
levels are activated)
First, a heating request for 50 °C is trig-
Temperature level time gered to test communication with the
window H2 boiler.
Then you can select all the test options
(only when temperature lev-
els are activated) by pressing the dial (see table 11.2). When
you press the P button the display
Temperature level time returns to basic mode.
window H3

(only when temperature lev- You can select the following tests:
els are activated)

Table 11.1 System parameters

40 Installation Manual for VRC 400 weather compensator


Start-up 11

Dial Test Test procedure


Press and push Heating request A heating request of 50 °C is simulated. The burner on the
P button for 3 boiler starts up and the pump starts (only up to the maxi-
seconds mum flow temperature of the boiler).
Turn Hot water request A hot water request is activated, charging pump starts
working, all other elements are switched off.
Turn Circulation pump The circulation pump is activated (if connected). All other
elements are switched off.
Press Display test All display elements are displayed.
Press Software version The software version is displayed.
Table 11.2

Installation Manual for VRC 400 weather compensator 41


11 Start-up

Restore default settings 11.3 Handing over to the owner


• To restore the controller to its default The owner of the weather controller
condition, press the P button for 15 sec- must be instructed about its functions
onds. and how to operate it.
As soon as the display lights up twice, • Hand over any instructions intended
the controller is completely rest to its for the owner as well as the control
default settings. This means that you documents.
will have to perform all individual set- • Go through the operating manual with
tings again. the owner and answer any questions.
• Draw special attention to the safety
instructions which the owner must fol-
low.
• Tell the owner to keep the instruction
manuals near the controller.

42 Installation Manual for VRC 400 weather compensator


Technical data 12, Vaillant customer service 13

12 Technical data 13 Vaillant customer


service
Description Unit
Operating voltage Umax V 24 To ensure regular servicing, it is strongly
Maximum ambient tempera- °C 50 recommended that arrangements are
ture
made for a Maintenance Agreement.
Current consumption mA < 17
Please contact Vaillant service (0870
Minimum cross-section of mm2 0.75
wires 6060 777) for further details.
Level of protection IP 20
Protection class III

Dimensions
Height mm 97
Width mm 146
Depth mm 40
Table 12.1 Technical data

Installation Manual for VRC 400 weather compensator 43


EC declaration of conformity

44 Operating manual and installation manual for VRC 400 weather compensator
838587_00 GB 04 2005