Beruflich Dokumente
Kultur Dokumente
Slab-on-Ground
Floors Tilt-Up Panel
BY David L. Kelly
Tilt-Up Panel
Fig. 1: Tilt-up construction process: (a) wall panels are typically cast on a slab-on-ground floor; (b) each panel is lifted, rotated, and
translated to its final position; (c) crane rigging is removed after braces are tied to the panel and the panel is braced; and (d) the
braces are removed after the building’s lateral-force-resisting system is in place (based on Ref. 1)
For a 4 in. (100 mm) slab, the length required to The flexural stress from the resulting 5.5 ft (1.65 m)
provide sufficient weight to resist uplift is cantilever will be 281 psi (1.9 MPa). Although the 4 in.
(100 mm) thick slab can be used to anchor the panel
(633 lb/ft)/[0.33 ft(150 lb/ft3)] = 12.8 ft (in.-lb units) bracing, the thin slab will require that two slab panels are
tied and numerous ballasting drums are used. What if the
(9.2 kN/m)/[0.1 m(23.6 kN/m3)] = 3.9 m (SI units) slab designer had considered bracing effects?
But, can the 4 in. (100 mm) slab resist the uplift? The Design it
brace connection is centered in a 12.8 ft (3.9 m) bending If the slab designer had considered bracing effects, a
zone, so the amount of slab cantilevered from the brace 5 in. (125 mm) thick slab could have been required in the
point can be assumed to be half of this length. first bay. The brace spacing would then be a function of
The bending moment M will therefore be: the brace buckling and shoe capacities, not the brace
anchor capacity. The uplift force from the braces would
M = (0.33 ft)(150 lb/ft3) (6.4 ft)2 be resisted by a slab length of
2
(633 lb/ft)/[0.42 ft(150 lb/ft3)] = 10 ft (in.-lb units)
= 1014 ft-lb (in.-lb units)
ft (9.2 kN/m)/[0.125 m(23.6 kN/m3)] = 3.1 m (SI units)
M = (0.1 m)(23.6 kN/m3) (1.95 m)2
2
kN·m
= 4.49 (SI units)
m
The section modulus for a unit width (1 ft or 1 m) Fig. 4: Temporary tension ties across contraction joints allow
of a 4 in. (100 mm) thick slab will be 32 in.3 (1.67 x adjacent floor slab panels to resist sliding forces
106 mm3), so the flexural stress will be 380 psi (2.7 MPa).
Because this is a life-safety issue, a flexural strength
for the slab concrete of 5 (0.4 ) will be used. With
f ′c = 4000 psi (28 MPa), the flexural strength will there-
fore be 316 psi (2.1 MPa). The slab should be reinforced
for bending, but, in this case, it’s already in place.
Now what?
The uplift can be reduced by adding ballast near the
braces—a 55 gal. (200 L) drum filled with water will
reduce the net uplift by about 450 lb (2 kN) (Fig. 5).
Most floor anchors have an upward working load limit
of 3200 lb (14.2 kN) in 4 in. (100 mm) thick concrete, so Fig. 5: Temporary ballast installed adjacent to brace anchors
the maximum spacing between braces will be reduces uplift and flexural stresses in the slab-on-ground
Concrete international / july 2007 33
The resulting flexural stress would be only 188 psi would still be too great to be resisted by the first floor
(1.4 MPa). The slab would therefore require no flexural slab panel alone, it would be necessary to install only
reinforcing and no ballast. Although the sliding force light reinforcing across the first joint. Many projects have
been successfully completed using an 8 ft (2.4 m) width
of 6x6-W2.9xW2.9 (152x152-MW19xMW19) welded-
wire reinforcement at the critical contraction joint.
Alternatively, the tilt-up contractor could install temporary
ties across the first slab joint or shoring to the panel or
the footing (Fig. 6).
Typically Taller
As the tilt-up industry continues to grow, wall heights
grow as well. Multi-story tilt-up buildings are now becoming
a popular application, leading to wall heights exceeding
75 ft (23 m).
Fig. 6: Shores installed in the closure strip can transfer sliding Clearly, such tall walls are going to create numerous
forces to the panel foundation challenges that are outside the scope of this article.
Knowing that the elevation of the upper brace
connections will be about 60% of the panel height and
the distance from the face of the panel to the lower
brace connections will be 33 to 40% of the panel height,
the building designer should consider numerous
questions before the construction documents are
issued, including:
Where will the crane be located?
Will the panels be braced to the inside or the outside
of the building?
If panels are braced to the inside, will the braces
interfere with installation of intermediate floors?
If panels are braced to the outside, will the braces
interfere with the crane operations and traffic?
Will the panels be strong enough to span between the
bracing points?
Especially for tall structures, I recommend that the
Fig. 7: Concealed deadmen can restrain sliding forces while Engineer of Record design a bracing method into the
allowing unrestrained slab shrinkage structure. Available options include the use of:
Thickened slab panels at the areas affected by bracing;
Shores to transfer sliding forces to the panel foundation
(Fig. 6);
Concealed deadmen to transfer
sliding forces to the subgrade
(Fig. 7);
Integral deadmen comprising
continuous grade beams or
drilled piers (Fig. 8);
Discrete deadmen, consisting of
helical or toggle anchors that are
drilled or pressed into the earth
at the bracing angle and tied
directly to the brace, keeping
in mind that the panels will
Fig. 8: Integral deadmen can provide sufficient mass to resist uplift as well as sufficient probably need to be cast on a
bearing surface to resist sliding forces. For this and other options that affect the floor section,
such as thickened slabs or integral grade beams, it’s important to maintain a constant bottom separate casting slab or braced
elevation between the contraction joints to avoid inducing restraint cracking to the outside; and