GULF CONTRACTING CO.

WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME : CP-133

SURVEY REPORT - COORDINATE COMPARISION


SURVEY REPORT NUMBER : DATE: 11/25/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev.No. Instrument S.No.


A1154-133-SS-S-QA1.33PS0343 1 ACTIVITY : Columns Vertical Alignmen AREA-7
QA-1

Design Coordinates Bottom of the column Difference Top of the column Difference
POINTS
E N E N E N E N E N
1 19076.85 36336.806 19076.858 36336.800 0.008 -0.006 19076.858 36336.800 0.008 -0.006

2 19076.08 36339.130 19076.085 36339.127 0.005 -0.003 19076.085 36339.127 0.005 -0.003

3 19073.646 36345.796 19073.653 36345.791 0.007 -0.005 19073.653 36345.791 0.007 -0.005

4 19072.47 36349.016 19072.466 36349.010 -0.004 -0.006 19072.466 36349.010 -0.004 -0.006

5 19076.952 36337.562 19076.941 36337.557 -0.011 -0.005 19076.941 36337.557 -0.011 -0.005

6 19068.592 36359.638 19068.578 36359.625 -0.014 -0.013 19068.578 36359.625 -0.014 -0.013

7 19069.305 36357.467 19069.295 36357.460 -0.010 -0.007 19069.295 36357.460 -0.01 -0.007

8 19066.76 36364.619 19066.768 36364.625 0.008 0.006 19066.768 36364.625 0.008 0.006
Remarks / Comments:

GCC Surveyor PGQ Surveyor

Name Name

Signature Signature

Date Date
3

ertical Alignmen AREA-7

Remarks
r
GULF CONTRACTING CO.W.L.L

P.O.BOX.3886, DOHA - QATAR


CONTRACT NO: C1236 CONTRACT NAME:

SURVEY REPORT – COORDINATE COMPARISON


SURVEY REPORT NUMBER: DATE: 18-Jun-13 TIME:

Area / Building / Location Reference Drawing No. Rev. No. Instrument S.No:

DESIGN COORDINATES ACTUAL COORDINATES Difference


Remarks
EASTING NORTHING EASTING NORTHING E N

12512.125

Remarks / Comments

GCC Surveyor QC Inspector / Engineer PGQ Surveyor

Name: Name: Name:


Signature: Signature: Signature:
Date: Date: Date:

Form No.: GCC:QMS:F:022.03 Rev. 0


GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING
1 19142.405
36245.940
2 19144.166
36245.94
3 19147.545
36245.94
4 19142.169
36241.837
5 19143.583
36241.837
6 19142.516
36237.795
7 19143.551
36237.795
8 19142.036
36233.023
9 19143.783
36233.006
10 19147.554
36237.796
11 19147.554
36235.796
12 19148.169
36233.006
13 19149.932
36234.896
14 19149.932
36233.084
15 19156.125
36234.896
16 19156.125
36233.084
17 19157.817
36245.94
18 19157.924
36237.796
Survey by - GCC Surveyor Checked by - PGQ Surveyor
Form No.: GCC:QMS:F:022.03 Rev. 0
GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


Survey by - GCC
EASTING Surveyor
NORTHING EASTING NORTHING Checked
EASTINGby - PGQ NORTHING
Surveyor

Name: Nufail . Y Name:

Signature: Signature:

Date: 26/09/2013 Date:

Form No.: GCC:QMS:F:022.03 Rev. 0


GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING
19 19157.888
36233.006
20 19162.635
36252.31
21 19162.26
36247.326
22 19162.26
36245.94
23 19163.081
36241.837
24 19164.166
36241.837
25 19161.931
36237.795
26 19162.817
36237.795
27 19161.931
36235.796
28 19164.075
36235.796
29 19162.274
36233.006
30 19164.075
36233.492
31 19167.24
36252.31
32 19167.24
36249.72
33 19167.24
36247.326
34 19165.593
36245.942

Survey by - GCC Surveyor Checked by - PGQ Surveyor

Name: NUFAIL . Y Name:


Signature: Signature:
Form No.: GCC:QMS:F:022.03 Rev. 0
GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING

Date: 26/09/2013 Date:

Form No.: GCC:QMS:F:022.03 Rev. 0


GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING
19157.924
35
36235.796
36 19142.036
36234.884

Survey by - GCC Surveyor Checked by - PGQ Surveyor

Form No.: GCC:QMS:F:022.03 Rev. 0


GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING
Name: NUFAIL . Y Name:
Signature: Signature:

Date: 26/09/2013 Date:

Form No.: GCC:QMS:F:022.03 Rev. 0


GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING

Survey by - GCC Surveyor Checked by - PGQ Surveyor

Form No.: GCC:QMS:F:022.03 Rev. 0


GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING
Name: NUFAIL . Y Name:
Signature: Signature:

Date: 07/07/2013 Date:

Form No.: GCC:QMS:F:022.03 Rev. 0


GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING

Survey by - GCC Surveyor Checked by - PGQ Surveyor

Name: NUFAIL . Y Name:


Signature: Signature:
Form No.: GCC:QMS:F:022.03 Rev. 0
GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING

Date: 07/07/2013 Date:

Form No.: GCC:QMS:F:022.03 Rev. 0


GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING

Survey by - GCC Surveyor Checked by - PGQ Surveyor

Name: NUFAIL . Y Name:


Form No.: GCC:QMS:F:022.03 Rev. 0
GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING
Signature: Signature:

Date: 07/07/2013 Date:

Form No.: GCC:QMS:F:022.03 Rev. 0


GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING

Survey by - GCC Surveyor Checked by - PGQ Surveyor

Name: NUFAIL . Y Name:


Form No.: GCC:QMS:F:022.03 Rev. 0
GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING
Signature: Signature:

Date: 07/07/2013 Date:

Form No.: GCC:QMS:F:022.03 Rev. 0


GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING

Survey by - GCC Surveyor Checked by - PGQ Surveyor

Name: NUFAIL . Y Name:


Form No.: GCC:QMS:F:022.03 Rev. 0
GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING
Signature: Signature:

Date: 07/07/2013 Date:

Form No.: GCC:QMS:F:022.03 Rev. 0


GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING

Survey by - GCC Surveyor Checked by - PGQ Surveyor

Name: NUFAIL . Y Name:


Form No.: GCC:QMS:F:022.03 Rev. 0
GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING
Signature: Signature:

Date: 07/07/2013 Date:

Form No.: GCC:QMS:F:022.03 Rev. 0


GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING

Survey by - GCC Surveyor Checked by - PGQ Surveyor

Name: Name:
Form No.: GCC:QMS:F:022.03 Rev. 0
GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME: CP-133
SURVEY REPORT - COORDINATE COMPARISION
SURVEY REPORT NUMBER: DATE: 26/09/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev. No. Instrument S.No:
A1157-133-SS-S-VL1.33PS1016 1 ACTIVITY: C2 Columns vertical
alignment for wall partition
VL.1 - 3rd Floor

POINTS DESIGN COORDINATES ACTUAL COORDINATES TOP DEFERENCE REMARKS


EASTING NORTHING EASTING NORTHING EASTING NORTHING
Signature: Signature:

Date: Date:

Form No.: GCC:QMS:F:022.03 Rev. 0


GULF CONTRACTING C
P.O. BOX. 3886, DOHA
CONTRACT NO: C-1236 CONTRACT

SURVEY REPORT - COORDINATE COMPARISION


SURVEY REPORT NUMBER : DATE:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER


A1154-133-SS-S-QA1.33PS0343
QA-1

Design Coordinates Bottom of the column Difference


POINTS
E N E N E N
1 19076.85 36336.806 19076.858 36336.800 0.008 -0.006

2 19076.08 36339.130 19076.085 36339.127 0.005 -0.003

3 19073.646 36345.796 19073.653 36345.791 0.007 -0.005

4 19072.47 36349.016 19072.466 36349.010 -0.004 -0.006

5 19076.952 36337.562 19076.941 36337.557 -0.011 -0.005

6 19068.592 36359.638 19068.578 36359.625 -0.014 -0.013

7 19069.305 36357.467 19069.295 36357.460 -0.010 -0.007

8 19066.76 36364.619 19066.768 36364.625 0.008 0.006

Remarks / Comments:

GCC Surveyor

Name Name

Signature Signature

Date Date
ULF CONTRACTING CO. WLL
O. BOX. 3886, DOHA- QATAR
CONTRACT NAME : CP-133

DINATE COMPARISION
11/25/2013 Time:

Rev.No. Instrument S.No.


1 ACTIVITY : Columns Vertical Alignmen AREA-7

Top of the column Difference


E N E N Remarks
19076.858 36336.800 0.008 -0.006

19076.085 36339.127 0.005 -0.003

19073.653 36345.791 0.007 -0.005

19072.466 36349.010 -0.004 -0.006

19076.941 36337.557 -0.011 -0.005

19068.578 36359.625 -0.014 -0.013

19069.295 36357.460 -0.01 -0.007

19066.768 36364.625 0.008 0.006

PGQ Surveyor

Name

Signature

Date
GULF CONTRACTING C
P.O. BOX. 3886, DOHA
CONTRACT NO: C-1236 CONTRACT

SURVEY REPORT - COORDINATE COMPARISION


SURVEY REPORT NUMBER : DATE:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER


A1154-133-SS-S-QA1.33PS0247
QA-1

Design Coordinates Bottom of the column Difference


POINTS
E N E N E N
1 19099.216 36270.954 19099.211 36270.950 -0.005 -0.004
2 19099.216 36272.500 19099.211 36272.504 -0.005 0.004
3 19099.216 36277.563 19099.211 36277.567 -0.005 0.004
4 19099.216 36288.091 19099.211 36288.096 -0.005 0.005
5 19099.216 36288.400 19099.211 36288.395 -0.005 -0.005
19099.216 36289.200 19099.211 36289.195 -0.005 -0.005
0.000 0.000
1 19100.000 36270.954 19100.005 36270.950 0.005 -0.004
2 19102.450 36270.954 19102.453 36270.950 0.003 -0.004
3 19104.950 36270.954 19104.953 36270.950 0.003 -0.004
4 19107.450 36270.954 19107.455 36270.950 0.005 -0.004
5 19110.000 36270.954 19110.005 36270.950 0.005 -0.004
6 19111.504 36270.954 19111.507 36270.950 0.003 -0.004

Remarks / Comments:

GCC Surveyor

Name Name

Signature Signature

Date Date
ULF CONTRACTING CO. WLL
O. BOX. 3886, DOHA- QATAR
CONTRACT NAME : CP-133

DINATE COMPARISION
11/25/2013 Time:

Rev.No. Instrument S.No.


1 ACTIVITY : Columns Vertical Alignmen AREA-1

Top of the column Difference


E N E N Remarks
19099.208 36270.959 -0.008 0.005
19099.208 36272.493 -0.008 -0.007
19099.208 36277.567 -0.008 0.004
19099.208 36288.096 -0.008 0.005
19099.208 36288.395 -0.008 -0.005
19099.208 36289.195 -0.008 -0.005

19100.005 36270.950 0.005 -0.004


19102.453 36270.950 0.003 -0.004
19104.953 36270.944 0.003 -0.010
19107.455 36270.946 0.005 -0.008
19110.005 36270.946 0.005 -0.008
19111.507 36270.946 0.003 -0.008

PGQ Surveyor

Name

Signature

Date
GULF CONTRACTING C
P.O. BOX. 3886, DOHA
CONTRACT NO: C-1236 CONTRACT

SURVEY REPORT - COORDINATE COMPARISION


SURVEY REPORT NUMBER : DATE:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER


A1154-133-SS-S-QA1.33PS0383
QA-1 A1154-133-SS-S-QA1.33PS0382

Design Coordinates Bottom of the column Difference


POINTS
E N E N E N
1 19089.662 36314.433 19089.667 36314.438 0.005 0.005

2 19085.61 36314.613 19085.605 36314.608 -0.005 -0.005

3 19081.621 36314.792 19081.629 36314.796 0.008 0.004

1 19089.811 36317.469 19089.814 36317.473 0.003 0.004

2 19085.952 36318.527 19085.957 36318.523 0.005 -0.004

3 19080.384 36320.001 19080.381 36319.995 -0.003 -0.006

4 19080.154 36320.064 19080.151 36320.057 -0.003 -0.007

Remarks / Comments:

GCC Surveyor

Name Name

Signature Signature

Date Date
ULF CONTRACTING CO. WLL
O. BOX. 3886, DOHA- QATAR
CONTRACT NAME : CP-133

DINATE COMPARISION
11/25/2013 Time:

Rev.No. Instrument S.No.


1 ACTIVITY : Columns Vertical Alignmen AREA-5&4

Top of the column Difference


E N E N Remarks
19089.667 36314.438 0.005 0.005

19085.605 36314.608 -0.005 -0.005

19081.629 36314.796 0.008 0.004

19089.820 36317.483 0.009 0.014

19085.957 36318.523 0.005 -0.004

19080.381 36319.995 -0.003 -0.006

19080.151 36320.057 -0.003 -0.007

PGQ Surveyor

Name

Signature

Date
GULF CONTRACTING C
P.O. BOX. 3886, DOHA
CONTRACT NO: C-1236 CONTRACT

SURVEY REPORT - COORDINATE COMPARISION


SURVEY REPORT NUMBER : DATE:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER


A1154-133-SS-S-QA1.33PS0343
QA-1

Design Coordinates Bottom of the column Difference


POINTS
E N E N E N
1 19076.99 36336.857 19076.995 36336.865 0.005 0.008

2 19078.445 36337.388 19078.458 36337.381 0.013 -0.007

3 19081.124 36338.365 19081.119 36338.370 -0.005 0.005

4 19085.783 36339.99 19085.790 36339.998 0.007 0.008

5 19088.029 36340.888 19088.032 36340.893 0.003 0.005

6 19092.315 36342.432 19092.323 36342.420 0.008 -0.012

Remarks / Comments:

GCC Surveyor

Name Name

Signature Signature

Date Date
ULF CONTRACTING CO. WLL
O. BOX. 3886, DOHA- QATAR
CONTRACT NAME : CP-133

DINATE COMPARISION
11/25/2013 Time:

Rev.No. Instrument S.No.


1 ACTIVITY : Columns Vertical Alignmen AREA-7

Top of the column Difference


E N E N Remarks
19076.995 36336.860 0.005 0.003

19078.458 36337.380 0.013 -0.008

19081.119 36338.371 -0.005 0.006

19085.790 36339.998 0.007 0.008

19088.032 36340.893 0.003 0.005

19092.323 36342.420 0.008 -0.012

PGQ Surveyor

Name

Signature

Date
GULF CONTRACT
P.O. BOX. 3886, D
CONTRACT NO: C-1236

SURVEY REPORT - COORDINATE COMPARI


SURVEY REPORT NUMBER : DATE:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER


A1154-133-SS-S-QA1.33PS0343
QA-1

Design Coordinates Bottom of the column Difference


POINTS
E N E N LEVEL E N
c-1 19076.894 36336.902 19076.891 36336.904 22.235 -0.003 0.002
c-2 19076.849 36336.806 19076.848 363336.806 22.243 -0.001 0.000
c-3 19075.984 36339.175 19075.982 36339.168 22.404 -0.002 -0.007
c-4 19073.595 36345.936 19073.592 36345.931 22.189 -0.003 -0.005
c-5 19073.55 36345.840 19073.551 36345.836 22.222 0.001 -0.004
c-6 19072.419 36349.157 19072.414 36349.157 22.139 -0.005 0.000
c-7 19072.374 36349.061 19072.370 36349.062 22.096 -0.004 0.001
c-8 19069.350 36357.563 19069.338 36357.557 22.402 -0.012 -0.006
c-9 19069.305 36357.467 19069.295 36357.461 22.192 -0.010 -0.006
c-10 19068.596 36359.626 19068.579 36359.622 22.211 -0.017 -0.004
c-11 19068.547 36359.542 19068.535 36359.525 22.231 -0.012 -0.017
c-12 19066.748 36364.624 19066.758 36364.621 22.332 0.010 -0.003
c-13 19066.787 36364.525 19066.799 36364.522 22.217 0.012 -0.003

Remarks / Comments:

GCC Surveyor

Name Name

Signature Signature

Date Date
ULF CONTRACTING CO. WLL
O. BOX. 3886, DOHA- QATAR
CONTRACT NAME : CP-133

RDINATE COMPARISION
11/25/2013 Time:

Rev.No. Instrument S.No.


1 ACTIVITY : Columns Vertical Alignmen AREA-7

Top of the column Difference


E N E N LEVEL Remarks
19076.902 36336.889 0.008 -0.013 28.407 NORTH SIDE-C
19076.836 36336.821 -0.013 0.015 28.573
19075.963 36339.193 -0.021 0.018 28.539
19073.603 36345.925 0.008 -0.011 29.653
19073.510 36345.862 -0.04 0.022 29.881
19072.439 36349.155 0.02 -0.002 29.109
19072.344 36349.065 -0.03 0.004 30.554
19069.329 36357.565 -0.021 0.002 31.469
19069.286 36357.469 -0.019 0.002 31.600
19068.560 36359.635 -0.036 0.009 31.578
19068.536 36359.524 -0.011 -0.018 31.500
19066.750 36364.622 0.002 -0.002 31.745
19066.826 36364.519 0.039 -0.006 24..920

PGQ Surveyor

Name

Signature

Date
GULF CONTRACTING CO. WLL
P.O. BOX. 3886, DOHA- QATAR
CONTRACT NO: C-1236 CONTRACT NAME : CP-133

SURVEY REPORT - COORDINATE COMPARISION


SURVEY REPORT NUMBER : DATE: 11/25/2013 Time:

AREA / BUILDING / LOCATION REFERENCE DRAWING NUMBER Rev.No. Instrument S.No.


A1154-133-SS-S-QA1.33PS0343 1 ACTIVITY : Columns Vertical Alignmen AREA-7
QA-1

Design Coordinates Bottom of the column Difference Top of the column Difference
POINTS
E N E N LEVEL E N E N E
c-1 19076.894 36336.902 19076.891 36336.904 22.235 -0.003 0.002 19076.902 36336.889 0.008
c-2 19076.849 36336.806 19076.848 363336.806 22.243 -0.001 0.000 19076.836 36336.821 -0.013
c-3 19075.984 36339.175 19075.982 36339.168 22.404 -0.002 -0.007 19075.963 36339.193 -0.021
c-4 19073.595 36345.936 19073.592 36345.931 22.189 -0.003 -0.005 19073.603 36345.925 0.008
c-5 19073.55 36345.840 19073.551 36345.836 22.222 0.001 -0.004 19073.510 36345.862 -0.04
c-6 19072.419 36349.157 19072.414 36349.157 22.139 -0.005 0.000 19072.439 36349.155 0.02
c-7 19072.374 36349.061 19072.370 36349.062 22.096 -0.004 0.001 19072.344 36349.065 -0.03
c-8 19069.350 36357.563 19069.338 36357.557 22.402 -0.012 -0.006 19069.329 36357.565 -0.021
c-9 19069.305 36357.467 19069.295 36357.461 22.192 -0.010 -0.006 19069.286 36357.469 -0.019
c-10 19068.596 36359.626 19068.579 36359.622 22.211 -0.017 -0.004 19068.560 36359.635 -0.036
c-11 19068.547 36359.542 19068.535 36359.525 22.231 -0.012 -0.017 19068.536 36359.524 -0.011
c-12 19066.748 36364.624 19066.758 36364.621 22.332 0.010 -0.003 19066.750 36364.622 0.002
c-13 19066.787 36364.525 19066.799 36364.522 22.217 0.012 -0.003 19066.826 36364.519 0.039
Remarks / Comments:

GCC Surveyor PGQ Surveyor

Name Name

Signature Signature

Date Date
AME : CP-133

Time:

.
mns Vertical Alignmen AREA-7

Difference
N LEVEL Remarks
-0.013 28.407 NORTH SIDE COLUMN

0.015 28.573 WEST SIDE COLUMN

0.018 28.539 WEST SIDE COLUMN

-0.011 29.653 NORTH SIDE COLUMN

0.022 29.881 WESTSIDE COLUMN

-0.002 29.109 WEST SIDE COLUMN

0.004 30.554 WEST SIDE COLUMN

0.002 31.469 WEST SIDE COLUMN

0.002 31.600 NORTH SIDE COLUMN

0.009 31.578 WEST SIDE COLUMN

-0.018 31.500 NORTH SIDE COLUMN

-0.002 31.745 WEST SIDE COLUMN

-0.006 24..920 NORTH SIDE COLUMN


Q Surveyor