ABSTRACT
In today’s day to day life the energy requirement growth will increasing rapidly. The use of renewable energy is
important to provide rapid increased energy demand. Solar energy provides free energy from sun which is pollution
free, clean and maintenance free energy. This paper aims to analyse the performance analysis of grid connected
solar farm. This analysis consists of load flow analysis, active power flow at different irradiance, reactive power
analysis and short circuit analysis on impact of 1-ϕ and 3-ϕ. To accomplish this proposed system modelling is done
in ETAP (Electrical Transient Analyzer Program) software.
Keywords:ETAP (Electrical Transient Analyzer Program), load flow analysis, solar farm, short circuit analysis.
IJSRSET1733169| 20 June 2017 | Accepted :30 June 2017 | May-June-2017[(2)3: 633-637] 633
Figure 3. Equivalent circuit of solar array
The equivalent circuit of solar cell is shown in fig. 2. In ETAP, load flow analysis was performed power flow
Where Iph is current source, Rsh is shunt resistance and analysis for individual networks and voltage drop
Rs is series resistance. The Rsh value is very large and calculations with accurate and reliable results. In this
Rs value is small, so for simplification these values are paper adaptive Newton-Raphson method was executed
neglected. K presents Boltzmann constant, N is for the load flow analysis. Active power flow at grid
represents diode ideality factor and T represents the cell was around 6448 KW and for individual network active
temperature. The equivalent circuit of solar array is power flow was 1623 KW.
shown in fig. 3. The load current equation is shown Table I
below [4]. Active power flow
[ ] (1) Network Actual (KW) Simulation
(KW)
Total (At Grid) 7560 6448
Network 1 1890 1623
Table II
Active power at different irradiance
Irradiation Active power output
(W/m2) (KW)
147 881
237 1435
660 3957
854 5054
892 5265
912 5375
Figure 7.Reactive power drawn from the grid
937 5513
950 5584 For balancing the output and to improve efficiency of
the solar farm, the compensation of reactive power is
very much important. To overcome this capacitor bank
The simulated analysis shows that the active power was implemented in the system. Capacitor bank was
output of the solar plant varies with changes in incident designed with appropriate parameters to improve
irradiance. The analysis shows that higher incident
irradiance gives higher active power as shown in table 2.
International Journal of Scientific Research in Science, Engineering and Technology (ijsrset.com)
635
stability with reducing the reactive power drawn from
the grid.