(MOCP) Motor over Current Protection= not more than Largest

OCPD + (∑) Summation of other motor Loads

MOCP= 110 A + 20.5 + 20.5 + 2.84

= 153.84 A

Therefore,

Use 175 AT, 3P, Inverse Time Delay MCCB, The nearest to the
standard ampere circuit breaker rating.

(Per NEC 2017, Table 240.6 (A) Standard ampere rating for fuses
and Inverse Time circuit breakers)

Sizing of ATS Black Start Motor Loads and Branch Feeder


Conductors

Calculation:

Branch Feeder Conductor not less than 125% IFL

(per NEC 430.22 (A), PEC 4.30.2.2 (A))

Motor no. 1 - C.T Fan No.3 = 1.25 (41.78 A) = 52.225 A

Use Cable 1 x 3C 16 mm² Cu/XLPE/PVC + 1C 16 mm² ECC

Motor no. 2 - Engine Cooling no.5 = 1.25 (20.5) = 25.625 A

Use Cable 2 sets x 3C 6 mm² Cu/XLPE/PVC + 1C 6 mm² ECC

Motor no. 3 - Transfer pump no.3= 1.25 (20.5) = 20.625 A

Use Cable 2 x 3C 6 mm² Cu/XLPE/PVC + 1C 6 mm² ECC

Motor no.4 – Motorized Valve = 1.25 (2.84) = 3.55 A

Use Cable 1 x 2C 4 mm² Cu/XLPE/PVC + 1C 4 mm² ECC