UL Listings
W-J-1128 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
W-J-1175 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
W-J-1191 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
W-J-1222 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
W-J-1226 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
W-J-3190 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7
W-J-5136 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
W-J-7085 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
W-J-7109 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
W-L-1367 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
W-L-1389 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
W-L-7159 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
W-L-8019 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

CP 606 Firestop acrylic sealant


Product Data Sheet for CP 606 Flexible Firestop Sealant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
UL Certificate of Compliance for CP 606 Flexible Firestop Sealant . . . . . . . . . . . . . . . . . . . . . . . . . . 23
LEED Information for CP 606 Flexible Firestop Sealant . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 24

CP 620 Firestop foam


Product Data Sheet for CP 620 Fire Foam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
UL Certificate of Compliance for CP 620 Fire Foam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
LEED Information for CP 620 Firestop Foam . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

CP 648-E firestop endless wrap strips


Product Data Sheet for CP 648-E Firestop Wrap Strip . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
UL Certificate of Compliance for CP 648-E and CP 648-S Firestop Wrap Strip . . . . . . . . . . . . . . . . . 29
LEED Information for CP 648-S and CP 648-E Firestop Wrap Strip . . . . . . . . . . . . . . . . . . . . . . . . . . 30

CP 675 Firestop board


Product Data Sheet for CP 675T Firestop Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
UL Certificate of Compliance for CP 675T Firestop Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
Material Information Statement for Firestop Products . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33
LEED information for CP 675 Firestop Board . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 34

FS-ONE MAX
Product Data Sheet for FS-ONE MAX Intumescent Firestop Sealant . . . . . . . . . . . . . . . . . . . . . . . . . 35
Buy American Certification for FS-ONE MAX Intumescent Firestop Sealant . . . . . . . . . . . . . . . . . . . 36
LEED Information for FS-ONE MAX Intumescent Firestop Sealant . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Mineral wool
Product Data Sheet for Mineral Wool . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38
S IFI
AS

WJ 1128
System No. W-J-1128
CL

ED
C US F Rating — 2 Hr
Classified by
Underwriters Laboratories, Inc.
T Rating — 0 Hr
to UL 1479 and CAN/ULC-S115 L Rating At Ambient — Less Than 1 CFM/sq ft
L Rating At 400 F — Less Than 1 CFM/sq ft

1. Wall Assembly — Min 5 in. thick reinforced lightweight or normal weight (100-150 pcf) concrete. Wall may also be constructed of any UL Classified
Concrete Blocks*. Max diameter of opening 31-7/8 in.
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers
2. Through Penetrant — One metallic pipe, conduit or tubing installed concentrically or eccentrically within the firestop system. Pipe, conduit or tube to
be rigidly supported on both sides of wall assembly. The annular space between the pipe, conduit or tube and periphery of the opening shall be min
0 in (point contact) to max 1-7/8 in. The following types and sizes of metallic pipes, conduit or tube may be used:
A. Steel Pipe — Nom 30 in. diam (or smaller) Schedule 40 (or heavier) steel pipe.
B. Iron Pipe — Nom 30 in. diam (or smaller) cast or ductile iron pipe.
C. Conduit — Nom 4 in. diam (or smaller) steel electrical metallic tubing (EMT) or 6 in. diam steel conduit.
D. Copper Tube — Nom 6 in. diam (or smaller) Type L (or heavier) copper tube.
E. Copper Pipe — Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe.
3. Fill, Void or Cavity Material*-Sealant — Min 1-1/4 in. thickness of fill material applied within the annulus, flush with both surfaces of wall. At the point
contact location between pipe and wall, a min ½ in. diam bead of fill material shall be applied at the pipe/wall interface.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP606 Flexible Firestop Sealant
*Bearing the UL Classification Mark

Reproduced by HILTI, Inc. Courtesy of


Underwriters Laboratories, Inc.
July 09, 2010

1
2
3
4
5
6
S IFI
AS

WJ 3190
CL
System No. W-J-3190

ED
C US
ANSI/UL1479 (ASTM E814) CAN/ULC S115
Classified by
Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115 F Ratings — 2 and 3 Hr (See Item 3) F Ratings — 2 and 3 Hr (See Item 3)
T Rating — 0 Hr FT Rating — 0 Hr
FH Ratings — 2 and 3 Hr (See Item 3)
FTH Ratings — 0 Hr
1

3
A
3

SECTION A-A

1. Wall Assembly — Min 6 in. (152 mm) thick lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be
constructed of any UL Classified Concrete Blocks*. Max diam of opening is 4 in. (102 mm).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.
2. Cables — Aggregate cross-sectional area of cable in opening to be max 45 percent of the cross-sectional area of the opening. The annular space
between the cable bundle and the periphery of the opening to be min 0 in. (point contact) to max 7/8 in. (22 mm) Cables to be tightly bundled and
rigidly supported on both sides of the wall assembly.. Any combination of the following types and sizes of copper conductor cables may be used:
A. Max 7/C No. 12 AWG with polyvinyl chloride (PVC) insulation and jacket.
B. Max 25 pair No. 24 AWG telephone cable with PVC insulation and jacket.
C. Max 4 pr No. 22 AWG Cat 5 or Cat 6 computer cables.
D. Type RG/U coaxial cable with polyethylene (PE) insulation and PVC jacket having a max outside diameter of ½ in. (13 mm).
E. Max RG 6/U coaxial cable with fluorinated ethylene insulation and jacketing.
F. Multiple fiber optical communication cable jacketed with PVC and having a max OD of 5/8 in. (16 mm).
G. Max three copper conductor No. 8 AWG Metal-Clad Cable+.
H. Max 3/C (with ground) (or smaller) No. 8 AWG copper conductor cable with PVC insulation and jacketing.
I. Through Penetrating Product* — Any cables, Metal-Clad Cable+ or Armored Cable+ currently Classified under the Through Penetrating
Products category.
3. Fill, Void or Cavity Material*— Sealant — Fill material applied within the annulus, flush with both surfaces of wall. A min 5/8 in. (16 mm) thickness
of sealant is required for 2 hr F Rating. A min 1 in. (25 mm) thickness of sealant is required for the 3 hr F Rating. An additional 1/2 in. (13 mm)
diam bead of fill material shall be applied at the point contact location of cable bundle/concrete interface on both surfaces of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — CP606, FS-One Sealant or FS-ONE MAX Intumescent Sealant
* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.
+Bearing the UL Listing Mark

Reproduced by HILTI, Inc. Courtesy of


Underwriters Laboratories, Inc.
October 14, 2015
Hilti Firestop Systems

7
8
9
S IFI
AS

WJ 7085
System No. W-J-7085
CL

ED
C US F Rating - 2 Hr
Classified by
Underwriters Laboratories, Inc.
T Rating - 1/2 Hr
to UL 1479 and CAN/ULC-S115
1
3B
A

3A

A
3B SECTION A-A
1. Wall Assembly — Min 6 in. (152 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also
be constructed of any UL Classified Concrete Blocks*. Max size of opening is 625 sq in. (4032 cm2) with a max dimension of 25 in. (635 mm).

See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.

2. Steel Duct — Nom. 24 in. by 24 in. (610 by 610 mm) (or smaller) No. 24 gauge (or heavier) galv. steel duct to be installed within the firestop
system. An annular space of min 1/2 in. (13 mm) to max 1 in. (25 mm) is required within the firestop system. As an option, the min annular space
at the bottom of the duct may be 0 in. (point contact). Steel duct to be rigidly supported on both sides of wall assembly

3. Firestop System — The firestop system shall consist of the following:

A. Packing Material — Min 5 in. (127 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt insulation firmly packed into opening as a
permanent form. Packing material to be recessed from both surfaces of wall to accommodate the required thickness of fill material.
B. Fill Void or Cavity Materials* - Sealant — Min 1/2 in. (13 mm) thickness of sealant applied within annulus, flush with both surfaces of wall
assembly. Min 1/4 in. (6 mm) diam bead of sealant shall be applied at the duct/concrete interface at any point contact location, on both
surfaces of wall assembly.
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC — CP 606 Sealant

*Bearing the UL Classification Mark

Reproduced by HILTI, Inc. Courtesy of


Underwriters Laboratories, Inc.
November 29, 2005

10
S IFI
AS

WJ 7109
CL
System No. W-J-7109

ED
C US
Classified by
ANSI/UL1479 (ASTM E814) CAN/ULC S115
Underwriters Laboratories, Inc.
to UL 1479 and CAN/ULC-S115 F Rating — 2 Hr F Rating — 2 Hr
T Rating — 0 Hr FT Rating — 0 Hr
L Rating At Ambient — Less Than 1 CFM/sq ft FH Rating — 2 Hr
L Rating At 400 F — Less Than 1 CFM/sq ft FTH Rating — 0 Hr
L Rating At Ambient — Less Than 1 CFM/sq ft
L Rating At 400 F — Less Than 1 CFM/sq ft

A 3B 3C 3B

1B
A 2 SECTION A-A

1. Wall Assembly — Min 6 in. (152 mm) thick reinforced lightweight or normal weight (100-150 pcf or 1600-2400 kg/m3) concrete. Wall may also be
constructed of any UL Classified Concrete Blocks*. Max area of opening is 73.7 sq ft (6.85 m2) with a max dimension of 104 in. (2.64 m).
See Concrete Blocks (CAZT) category in the Fire Resistance Directory for names of manufacturers.

Reproduced by HILTI, Inc. Courtesy of


Underwriters Laboratories, Inc.
October 30, 2017
Hilti Firestop Systems Page: 1 of 2

11
WJ 7109
System No. W-J-7109

2. Steel Duct — Max 100 in. by 100 in. (2.5 by 2.5 m) galv steel duct to be installed either concentrically or eccentrically within the firestop system.
The duct shall be constructed and reinforced in accordance with SMACNA construction standards. The space between the steel duct and
periphery of opening shall be min 0 in. (point contact) to max 2 in. (51 mm). Steel duct to be rigidly supported on both sides of the wall assembly.
2A. Through-Penetrants — Coated Ducts* — As an alternate to Item 2, rectangular steel air duct supplied coated with BW11 coating material. Max
40 by 40 in. (1.02 by 1.02 m) duct size. One duct to be installed within the firestop system with an annular space of min 0 in. (point contact) to max
2 in. (51 mm). Reinforcement stiffener or transverse joint with bolted flanges shall be located approximately at the mid depth of the annular space.
Duct to be rigidly supported on both sides of the wall assembly. Duct sections shall be assembled using bolted flanges or SMACNA approved
Transverse Joint Reinforcements.
FIRESPRAY INTERNATIONAL LTD — FLAMEBAR BW11 FIRE RATED DUCTWORK
3. Firestop System — The firestop system shall consist of the following:
A. Packing Material — (Optional, Not Shown) — Polyethylene backer rod, mineral wool batt insulation or fiberglass batt insulation friction fitted
into annular space. Packing material to be recessed from both surfaces of wall to accommodate the required thickness of fill material.
A1. Packing Material — Required as specified in Table below. Min 3-3/4 in. (95 mm) thickness of min 4 pcf (64 kg/m3) mineral wool batt
insulation firmly packed into opening as a permanent form. Packing material to be recessed from both surfaces of wall to accommodate the
required thickness of fill material.
B. Fill, Void or Cavity Material* — Sealant — Min 5/8 in. (16 mm) thickness of fill material applied within the annulus, flush with both surfaces of
wall. Min 1/4 in. (6 mm) diam bead of fill material shall be applied at the point contact location between the duct and the wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC — FS-ONE Sealant or FS-ONE MAX Intumescent Sealant or CP606
C. Steel Retaining Angles — Min No. 16 gauge galv steel angles sized to lap steel duct a min of 2 in. (51 mm) and to lap wall surfaces a min of 1
in. (25 mm). When max duct dimension does not exceed 48 in. and duct area does not exceed 1300 in2, angles may be min No. 18 gauge
galv steel. Angles attached to steel duct or coated duct on both sides of wall with min No. 10 by 1/2 in. (13 mm) long steel sheet metal screws
located a max of 1 in. (25 mm) from each end of duct and spaced a max of 6 in. (152 mm) OC. Steel angles are optional for those sides of
duct that do not exceed the dimension specified in Table below, dependent on packing material and annular space as specified.

Angle (Item 3C)


Max Duct Dimension Duct Thickness Annular Space Packing Material
Required
1/2 in. min to 1 in. max
24 in. (610 mm) 24 ga or heavier Item 3A1 No
(13 to 25 mm)

* Indicates such products shall bear the UL or cUL Certification Mark for jurisdictions employing the UL or cUL Certification (such as Canada),
respectively.

Reproduced by HILTI, Inc. Courtesy of


Underwriters Laboratories, Inc.
October 30, 2017
Hilti Firestop Systems Page: 2 of 2

12
13
14
15
S IFI
AS

WL 7159
System No. W-L-7159
CL

ED
C US F Rating — 1 or 2 Hr (See item 1)
Classified by
Underwriters Laboratories, Inc.
T Rating — 1/2 Hr
to UL 1479 and CAN/ULC-S115

1
3
A

A
2

SECTION A-A

1. Wall Assembly — The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner
described in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following
construction features:
A. Studs — Wall framing to consist of min 3-1/2 in. (89 mm) wide steel channel studs, fabricated from 25 MSG galv steel, spaced
max 24 in. (610 mm) OC.
B. Gypsum Board* — One or two layers of nom 5/8 in.(16 mm) thick gypsum board, as specified in the individual Wall and
Partition Design. Max area of opening is 144 sq in.(903 cm2) with max dimension of 12 in.(306 mm)
The hourly F Rating of the firestop system is equal to the hourly f rating of the wall assembly.
2. Steel Duct — Nom 10 in by 10 in.(254 by 254 mm) (or smaller) No. 28 gauge (or heavier) galv steel duct to be installed either concentrically
or eccentrically within the firestop system. The annular space shall be min ¼ in. to max 1 in. Duct to be rigidly supported on both sides of
the wall assembly.
3. Fill, Void or Cavity Material - Sealant* — Min 5/8 in.(16mm) thickness of fill material applied within annular space, flush with both surfaces of
wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF
HILTI INC — FS-ONE Sealant
*Bearing the UL Classification Mark

Reproduced by HILTI, Inc. Courtesy of


Underwriters Laboratories, Inc.
May 24, 2007

16
S IFI
AS

WL 8019
System No. W-L-8019
CL

ED
C US F Rating -- 1 and 2 Hr (See Items 1, 3 and 4)
Classified by
Underwriters Laboratories, Inc.
T Rating -- 0, 1/2, 1, 1-1/2 and 2 Hr (See Item 2)
to UL 1479 and CAN/ULC-S115

D
F C
E
B

F
C
G D
B A

E G A

3
4A
2

3
2 4B
1

FIRESTOP CONFIGURATION A FIRESTOP CONFIGURATION B

Reproduced by HILTI, Inc. Courtesy of


Underwriters Laboratories, Inc.
April 22, 2005
Hilti Firestop Systems Page: 1 of 5

17
S IFI
AS

WL 8019
System No. W-L-8019
CL

ED
C US F Rating -- 1 and 2 Hr (See Items 1, 3 and 4)
Classified by
Underwriters Laboratories, Inc.
T Rating -- 0, 1/2, 1, 1-1/2 and 2 Hr (See Item 2)
to UL 1479 and CAN/ULC-S115

3A 2
2

3
3B

FIRESTOP CONFIGURATION C FIRESTOP CONFIGURATION D

4
2 3

3 1

FIRESTOP CONFIGURATION E FIRESTOP CONFIGURATION F

Reproduced by HILTI, Inc. Courtesy of


Underwriters Laboratories, Inc.
April 22, 2005
Hilti Firestop Systems Page: 2 of 5

18
S IFI
AS

WL 8019
System No. W-L-8019
CL

ED
C US F Rating -- 1 and 2 Hr (See Items 1, 3 and 4)
Classified by
Underwriters Laboratories, Inc.
T Rating -- 0, 1/2, 1, 1-1/2 and 2 Hr (See Item 2)
to UL 1479 and CAN/ULC-S115

2
1

FIRESTOP CONFIGURATION G

1. Wall Assembly -- The 1 or 2 hr fire-rated gypsum board/stud wall assembly shall be constructed of the materials and in the manner described in
the individual U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall include the following construction features:
A. Studs -- Steel studs 3-1/2 in. deep, fabricated from 25 MSG galv steel, spaced max 24 in. OC.
B. Gypsum Board* -- The gypsum board type, number of layers, fastener type and sheet orientation shall be as specified in the individual Wall
and Partition Design. Max area of opening is 450 sq in with max dimension of 30 in.
The hourly F Rating of the firestop system is equal to the hourly fire rating of the wall asembly in which it is installed.
2. Through Penetrants -- A max of seven firestop configurations may be installed within the opening. The space between firestop configurations.
Unless otherwise indicated, the space between firestop configurations and periphery of opening shall be min 3/8 in. Pipe, conduit, tubing or cables
to be rigidly supported on both sides of floor or wall assembly. The T Rating of the sytem is dependent on the firestop configurations, as shown in
the table below. Any combination of the following firestop configurations detailed herein may be used:
1 Hr F Rating 2 Hr F Rating
Firestop Configuration
T Rating Hr T Rating Hr
A 0 1/2
B 1 1-1/2
C 1/2 1
D 0 0
E 1 2
F 0 0
G 0 0

Reproduced by HILTI, Inc. Courtesy of


Underwriters Laboratories, Inc.
April 22, 2005
Hilti Firestop Systems Page: 3 of 5

19
S IFI
AS

WL 8019
System No. W-L-8019
CL

ED
C US F Rating -- 1 and 2 Hr (See Items 1, 3 and 4)
Classified by
Underwriters Laboratories, Inc.
T Rating -- 0, 1/2, 1, 1-1/2 and 2 Hr (See Item 2)
to UL 1479 and CAN/ULC-S115

2. Cables -- Max 4 in. diam tightly bundled cable. The min space between adjacent penetrants shall be 4 in. Cable bundle may be any combination
of the following types and sizes of cables:
G. Max 25 pair No. 24 AWG copper telephone cable with polyvinyl chloride (PVC) insulation and jacket materials.
H. Max 7/C No. 12 AWG cable with PVC insulation and jacket materials.
I. Multiple fiber optical communication cables with PVC jacket material and having a max outside diameter of 3/8 in.
J. Max 3/C No. 12 AWG steel clad cables with PVC insulation and jacket materials.
K. Max 3/C No. 8 AWG cablew with ground with PVC insulation and jacket materials.
L. Max RG 59 coaxial cables with PVC insulation and jacket materials.
3. Fill, Void or Cavity Material* - Foam -- Fill materiial applied within annulus flush with both surfaces of the wall. Min fill material thickness for 1 hr F
Rating is 4-3/4 in. Min fill material thickness for 2 hr F Rating is 6 in.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- CP 620 Fire Foam

Firestop Configuration B
2. Copper Tuber or Pipe -- Nom 1 in. diam (or smaller) Type L copper tube or nom 1 in diam (or smaller) Regulary (or heavier) copper pipe. Min
space between adjacent penetrants shall be 3 in.
3. Tube Insulation - Plastics+ -- Nom 3/4 in. thick acrylonitrile butadiene/polyvinyl chloride (AB/PVC) flexible foam furnished in the form of tubing.
The min space between adjacent penetrants shall be 1-1/2 in.
See Plastics+ (QMFZ2) category in the Plastics Recognized Component Directory for names of manufacturers. Any Recognized Component
tube insulation material meeting the above specifications and having a UL 94 Flammability Classificationof 94-5VA may be used.
4. Firestop System -- The firestop system shall consist of the following:
A. Fill, Void or Cavity Material* - Wrap Strip -- Nom 3/16 in thick by 1 in wide intumescent wrap strip. The wrap strip is continuously wrapped
around the outer circumference of the pipe covering one time and held in place with tape. Wrap strips are installed flush with each side of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- CP 648-E W45/1-3/4 Wrap Strip
B. Fill, Void or Cavity Material* - Foam -- Fill material applied within annulus flush with both surfaces of the wall. Min fill material thickness for 1
hr F Rating is 4-3/4 in. Min fill material thickness for 2 hr F Rating is 6 in.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- CP 620 Fire Foam

Firestop Configuration C
2. Polyvinyl Chloride (PVC) Pipe -- Nom 2 in. diam (or smaller) Schedule 40 solid or cellular core PVC pipe for use in closed (process or supply) or
vented (drain, waste or vent) piping system. The min space between non-metallic penetrants shall be 1 in. The min space between metallic
penetrants shall be 3-1/2 in.
3. Firestop System -- The firestop shall consist of the following:
A. Fill, Void or Cavity Material* - Wrap Strip -- Nom 3/16 in thick by 1 in wide intumescent wrap strip. The wrap strip is continuously wrapped
around the outer circumference of the pipe covering one time and held in place with tape. Wrap strips are installed flush with each side of wall.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- CP 648-E W25/1" Wrap Strip
B. Fill, Void or Cavity Material* - Foam -- Fill material applied within annulus flush with both surfaces of the wall. Min fill material thickness for 1
hr F Rating is 4-3/4 in. Min fill material thickness for 2 hr F Rating is 6 in.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- CP 620 Fire Foam

Reproduced by HILTI, Inc. Courtesy of


Underwriters Laboratories, Inc.
April 22, 2005
Hilti Firestop Systems Page: 4 of 5

20
S IFI
AS

WL 8019
System No. W-L-8019
CL

ED
C US F Rating -- 1 and 2 Hr (See Items 1, 3 and 4)
Classified by
Underwriters Laboratories, Inc.
T Rating -- 0, 1/2, 1, 1-1/2 and 2 Hr (See Item 2)
to UL 1479 and CAN/ULC-S115

Firestop Configuration D
2. Through Penetrant -- One metallic pipe, conduit or tube to be installed either concentrically or eccentrically within the firestop system. The min
annular space between the pipe, conduit or tube and the periphery of the opening shall be min. 0 in. (point contact). The annular space between
adjacent penetrants shall be min 3-1/2 in. The following types and sizes of metallic pipes, conduits or tubes may be used:
Steel Pipe -- Nom 4 in. diam (or smaller) Schedul 10 (or heavier) steel pipe.
Iron Pipe -- Nom 4 in. diam (or smaller) cast or ductile iron pipe.
Conduit -- Nom 4 in. diam (or smaller) rigid steel conduit.
Conduit -- Nom 4 in. diam (or smaller) steel electrical metallic conduit.
Copper Tubing -- Nom 4 in. diam (or smaller) Type L (or heavier) copper tubing.
Copper Pipe -- Nom 4 in. diam (or smaller) Regular (or heavier) copper pipe.
3. Fill, Void or Cavity Material* - Foam -- Fill material applied within annulus flush with both surfaces of the wall. Min fill material thickess for 1 hr F
Rating is 4-3/4 in. Min fill material thickness for 2 hr F Rating is 6 in.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- CP 620 Fire Foam

Firestop Configuration E
2. Steel Pipe -- Nom 8 in. diam (or smaller) Schedule 40 (or heavier) steel pipe.
3. Pipe Covering Materials* -- Nom 1-1/2 in. thick hollow cylindrical heavy density (min 3.5 pcf) glass fiber units jacketed on the outside with an
all-service jacket. Longitudinal joints sealed with metal fasteners or factory-applied, self-sealing lap tape. Transverse joints secured with metal
fasteners of with butt tape supplied with product. The min space between adjacent penetrants shall be 2 in.
See Pipe and Equipment Covering - Materials (BRGU) Category in the Building Materials Directory for names of manufacturers. Any pipe
covering meeting the above specifications and bearing the UL Classification Marking with a Flame Spread Index of 25 or less and a Smoke
Developed Index of 50 or less may be used.
4. Fill, Void or Cavity Mateiral* - Foam -- Fill material applied within annulus flush with both surfaces of the wall. Min fill material thickness for 1 hr F
Rating is 4-3/4 in. Min fill material thickness for 2 hr F Rating is 6 in.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- CP 620 Fire Foam

Firestop Configuration F
2. Flexible Conduit -- Nom 1 in. diam (or smaller) flexible steel conduit. The min space between adjacent penetrants shall be 3-1/2 in.
3. Fill, Void or Cavity Mateiral* - Foam -- Fill material applied within annulus flush with both surfaces of the wall. Min fill material thickness for 1 hr F
Rating is 4-3/4 in. Min fill material thickness for 2 hr F Rating is 6 in.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- CP 620 Fire Foam

Firestop Configuration G
2. Steel Duct -- Nom 6 in. diam (or smaller) No. 28 gauge (or heavier) galve steel duct. The min space between adjacent penetrants shall be 1-1/2
in.
3. Fill, Void or Cavity Material* - Foam -- Fill material applied within annulus flush with both surfaces of the wall. Min fil material thickness for 1 hr F
Rating is 4-3/4 in. Min fill material thickness for 2 hr F Rating is 6 in.
HILTI CONSTRUCTION CHEMICALS, DIV OF HILTI INC -- CP 620 Fire Foam
*Bearing the UL Classification Mark

Reproduced by HILTI, Inc. Courtesy of


Underwriters Laboratories, Inc.
April 22, 2005
Hilti Firestop Systems Page: 5 of 5

21
Product Information

Flexible Firestop Sealant


(CP 606)

Introduction
Product description
■■ An acrylic based firestop sealant that provides movement
capability in fire rated joints and seals through-penetrations
applications

Product features
■■ Silicone free
■■ Halogen, asbestos and solvent free
■■ Paintable

Applications and Products


■■ Tested up to 33% movement with 500 cycles in accordance to UL
2079 and ASTM 1966
■■ Smoke and fume resistant
■■ Easy clean up with water Technical Data* CP 606
■■ Single component systems available Chemical basis Acrylic based firestop sealant
■■ Meets LEED™ requirements for indoor environmental quality credit Color Available in red, white and gray
4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paints Application temperature 40°F to 104°F (5°C to 40°C)
and Coatings
Skin-forming time Approx. 15 min
Areas of application Curing time Approx. 3 mm / 3 days
■■ Sealing construction/expansion joints Average volume shrinkage 22.2%
■■ Top-of-wall joints (ASTM C1241)
■■ Metal pipes Movement capability Approx. 10%

Selector Guide
■■ Cable bundles Temperature resistance –22°F to 176°F (–30°C to 80°C)
■■ HVAC penetrations Surface burning characteristics Flame Spread: 10
(ASTM E 84-96) Smoke Development: 0
For use with Sound transmission classification 56
■■ Various base materials such as masonry, concrete, gypsum, etc. (ASTM E 90-99) (Relates to specific construction)
■■ Wall and floor assemblies rated up to 3 hours Tested in accordance with
• UL 2079 • ASTM E 814 • ASTM E 1966
Examples • ASTM E 84 • UL 1479 • ASTM G21
■■ Where a gypsum wall assembly meets the underside of a metal or
*At 73°F (23°C) and 50% relative humidity
concrete deck

Through-Penetration
■■ Sealing expansion joints to impede the passage of fire, smoke and
FILL, VOID OR CAVITY MATERIAL
toxic fumes FOR USE IN THROUGH-PENETRATION
FM
■■ Sealing around HVAC penetrations through fire-rated assemblies FIRESTOP SYSTEMS AND
JOINT SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY $33529('
66Y7 )RU3HQHWUDWLRQ)LUH6WRSV
&RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH

Installation instructions for CP 606


Notice permanently marked with an identification plate and Storage
• Before handling, read Material Safety Data Sheet and fastened in a visible position next to the seal. • Store only in the original packaging in a location
product label for safe usage and health information. protected from moisture at a temperature of 40°F to
Not for use 77°F (5°C to 25°C)
• Instructions below are general guidelines — always • On areas immersed in water
refer to the applicable drawing in the UL Fire • Observe expiration date on package
Resistance Directory or Hilti Firestop Systems Guide
for complete installation information
• The use of backing material is recommended to

Joint
JOINT

control the sealant depth and help ensure assembly


seal is complete
Firestop
System

Opening
1. Clean the opening. Surfaces to which CP 606 will
be applied should be cleaned of loose debris, dirt, 1. Clean opening 2. Insert backing 3. Apply CP 606 4. Smooth CP 606 5. Fasten identification
oil, wax and grease. The surface should be moisture material compressed plate (if required)
per UL System FILL, VOID OR CAVITY MATERIALS
and frost free.
CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
Application of firestop FOR USE IN TROUGH-PENETRATION
2. Insert fill of mineral wool or backer (as required). R FIRESTOP SYSTEMS
DUCT

SEE UL FIRE RESISTANCE DIRECTORY


3. Apply firestop over backer.
Reference Data

66Y7
4. Smooth firestop sealant with a trowel before the skin
forms. Once cured, CP 606 can only be removed Firestop

mechanically.
System

5. For maintenance reasons, a penetration seal can be 1. Clean opening 2. Insert backing 3. Apply CP 606 4. Smooth CP 606 5. Fasten identification
material plate (if required)

Hilti. Outperform. Outlast.


Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti Firestop Systems Guide
22
CERTIFICATE OF COMPLIANCE
Certificate Number 20160930-R13240
Report Reference R13240
Issue Date 2016-September-30

Issued to: Hilti Construction Chemicals, Div of Hilti Inc.


5400 S 122nd East Ave
Tulsa, OK 74146

This is to certify that Fill, Void or Cavity Materials


representative samples of Fill, Void or Cavity Materials Certified for Canada

CP 606 Sealant for use in Through-Penetration Firestop,


Joint in wall and partition Systems as currently decribed in
the UL Fire Resistance Directory and in the Products
Certified for Canada Directory.

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: ANSI/UL 1479, "Fire Tests of Through-Penetration


Firestops,"
ANSI/UL 2079, "Tests for Fire Resistance of Building Joint
Systems,"
CAN/ULC-S115, "Standard Method of Fire Tests of Firestop
Systems."
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information

Only those products bearing the UL Certification Mark should be considered as being covered by UL's
Certification and Follow-Up Service.

Look for the UL Certification Mark on the product.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 1 of 1

23
February 26, 2010

To Whom It May Concern:

Re: Hilti CP 606 Flexible Firestop – LEEDs Info.

The Hilti CP 606 Flexible Firestop Sealant is manufactured in Germany.

The CP 606 pail is made of polyethylene and can be completely recycled. There is no post-
consumer or post-industrial content in CP 606 and it cannot be recycled. The CP 606 does not
contain any Rapidly Renewable Materials. The VOC content for CP 606 is 71.0 grams/liter.

CP 606 is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for
the disposal of non-regulated industrial waste can vary from state to state and even city to city.
For this reason, you should consult your local and state regulatory agencies for direction on
disposal.

Please feel free to contact me at (918) 872-3704 if you have questions.

Sincerely,

Jerry Metcalf MPH, CHMM


Safety/Environmental Manager
Hilti Inc.
918 872 3704
jerry.metcalf@hilti.com

Rev. Date: 2/26/10

Hilti, Inc.
5400 South 122 n d East Avenue
Tulsa, OK 74146

1-800-879-8000
www.hilti.com

24
Product Information

Fire Foam CP 620


Brands
chutzb

(CP 620)
esc hichtu
sodfm,e ng
v iJdjfiwh
riuh. N|o
4i5kirdw WE
u9+‰12 iloi4jtf-|x-.v
oeoo bvbvh,
ireiv

Product description
■■ Innovative firestopping solution for complex applications

Product features
■■ Up to 6 times expansion of can yield
■■ Repenetrable
■■ Cures within 60 seconds
■■ Easy handling for difficult to reach applications
■■ Paintable
■■ Virtually impervious to smoke
■■ Mold resistant
■■ No additional materials required Technical Data* CP 620
■■ Execllent water vapor resistance Chemical basis Two component polyurethane

■■ Meets LEED™ requirements for indoor environmental quality credit Color Red
4.1 Low Emitting Materials, Sealants and Adhesives and 4.2 Paints Fire foam yield Up to 110 in3
and Coatings Application temperature Substrate: 32°F to 104°F (0°C to 40°C)
Product: 50°F to 104°F (10°C to 40°C)
Areas of application Curing time* Non-tacky after Approx. 35 seconds
■■ Sealing small to medium size openings Ready to cut after Approx. 1 minute
■■ Cables and cable trays Thermal insulation (R-value) 2.8–3.0 per inch of thickness
■■ Non-combustible pipes Temperature resistance of cured foam –22°F to 212°F (–30°C to 100°C)
■■ Combustible pipes when used in conjunction with Hilti Wrap Strips Sound transmission classification 50 (Relates to specific construction)
■■ Where cables, steel, copper, cast iron or plastic pipes all pass (ASTM E90-97)
through the same opening Structure-borne sound insulation Pipe/wall 30–50%

For use with floor and wall assemblies Surface burning characteristics Flame spread: 0
(ASTM E84-01) Smoke development: 15
■■ Concrete, drywall and masonry
Tested in accordance with
Examples • UL 1479 • ASTM E 814 • ASTM E 84 • ASTM G21
■■ Multiple penetrations *At 73°F (23°C) and 50% relative humidity
■■ Insulated metal pipes
FILL, VOID OR CAVITY MATERIAL
FOR USE IN THROUGH-PENETRATION FM
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY $33529('
66Y7 )RU3HQHWUDWLRQ)LUH6WRSV
&RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH

Installation instructions for CP 620


Notice 6. For maintenance reasons, the application can be • Pieces of cured excess CP 620 Fire Foam which have
• Before handling, read Material Safety Data Sheet and permanently marked with an installation plate. Mark been cut off can be laid in the next opening and fresh
product label for safe usage and health information. the installation plate and fasten it in a visible position CP 620 Fire Foam can be applied around these.
• Instructions below are general guidelines — always next to the seal.
Not for use
refer to the applicable drawing in the UL Fire Re-installing cables or pipes • Exposed to weather
Resistance Directory or Hilti Firestop Systems Guide • Additional cables or pipes can be installed later • Exposed to UV
for complete installation information without difficulty.
Application • Use a suitable tool to create an opening. Push the Storage
cable or pipe through and then seal the remaining • Store only in the original packaging in a dry place
1-4.
opening carefully with CP 620 Fire Foam. at a temperature of 40°F to 77°F (5°C to 25°C).
Prepare dispenser and cartridges as shown below. See technical data for application and substrate
The Fire Foam from the first few strokes of the Notes temperatures. Partly-used ­cartridges can be stored
dispenser should be discarded until the Fire Foam in • The CP 620 Fire Foam can be cut back to no less with mixer attached until they are ­required again.
the mixer has a consistent red color. than the minimum specified installation depth (see When re-using a partially used cartridge, simply
5. Apply the CP 620 Fire Foam in the opening. applicable UL systems for depths). ­attach a new mixer andOR
FILL, VOID dispense accordingly.
CAVITY MATERIALS
• Begin applying CP 620 Fire Foam at the back of CLASSIFIED BY
UNDERWRITERS LABORATORIES, INC.
the opening and work toward the front. Fill the FOR USE IN TROUGH-PENETRATION
opening completely with CP 620 Fire Foam. R FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY
• When dispensed slowly, the Fire Foam can be 66Y7
easily built up.
• When dispensed quickly, the consistency of the
Fire Foam is more liquid allowing it to flow better Aus-
fhrungsschild

between the cables. Note: The CP 620 Fire Foam


1. Hold the cartridge 2. Fit the mixer and 3. Release the 4. Insert the cartridge 5. Apply CP 620 Fire 6. Attach the
becomes warm for a short time after application. in the upright position screw in a clockwise dispenser and pull in the dispenser. Foam, building up a seal installation plate
and unscrew the cap. motion until secure. back the piston rod. by working from the (if required).
back towards the front.

Hilti Firestop
Saving lives
through innovation
and education

Hilti. Outperform. Outlast.


Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti Firestop Systems Guide
25
CERTIFICATE OF COMPLIANCE
Certificate Number 20160829-R13240
Report Reference R13240
Issue Date 2016-August-29

Issued to: Hilti Construction Chemicals, Div of Hilti Inc.


5400 S 122nd East Ave
Tulsa, OK 74146

This is to certify that Fill, Void or Cavity Materials


representative samples of Fill, Void or Cavity Materials Certified for Canada

CP 620 Fire Foam for use in Through-Penetration Firestop


Firestop Systems as currently decribed in the UL Fire
Resistance Directory and in the Products Certified for
Canada Directory.

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: ANSI/UL 1479, "Fire Tests of Through-Penetration


Firestops,"
CAN/ULC-S115, "Standard Method of Fire Tests of Firestop
Systems."
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information

Only those products bearing the UL Certification Mark should be considered as being covered by UL's
Certification and Follow-Up Service.

Look for the UL Certification Mark on the product.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 1 of 1

26
September 24, 2015

To Whom It May Concern:

Re: Hilti CP 620 Fire Foam – LEED Info.

Item Number:

338725

The Hilti CP 620 Fire Foam is manufactured in Germany.

The CP 620 tube is made of polyethylene and can be completely recycled. There is no post-consumer or post-industrial content in
CP 620 and it cannot be recycled. The CP 620 does not contain any Rapidly Renewable Materials. The VOC content for CP 620
is 15.0 grams/liter.

CP 620 is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-regulated
industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and state
regulatory agencies for direction on disposal.

Please feel free to contact me at (918) 872-3704 if you have questions.

Sincerely,

Jerry Metcalf MPH, CHMM


Sr. Manager, Safety/Environmental
Hilti Inc.
918 872 3704
jerry.metcalf@hilti.com

Rev. Date: 7/17/14

The manufacturing plant location on this certificate has been provided for LEEDS reporting purposes only. It should never be used
for Country of Origin certification or a representation of compliance/non-compliance with Buy American or Buy America
requirements, as those requirements differ.

The manufacturing plant location(s) identified on the certificate represent standard Hilti catalog products only. “Specially” produced
non-catalog Hilti products may have differing manufacturing plant locations.

Contact your Hilti representative in cases of “specially” produced products for a custom LEEDS certificates

Hilti, Inc.
5400 South 122 n d East Avenue
Tulsa, OK 74146

1-800-879-8000
www.hilti.com

27
Product Information

Firestop Wrap Strip


(CP 648-E)
Product description
■■ An intumescent, flexible firestop wrap strip for plastic and
insulated pipe penetrations

Product features
■■ Highly Intumescent
■■ Long length avoids waste
■■ Can be continuously wrapped
■■ Cost effective tzm
an
sc
h.

■■ Quick and easy closure without tools


hu
sc
nd WE
Bra N|o uze
648 iuh. Ā
CP whr 288u27 , ireiv
djfi
v iJ 4e‰0 bvbvh

■■ Ideal for very tight installations


fm,e |p3i x-.v
sod 23aw i4jtf-|
Z8Z irdwilo o
4i 5k eo
‰12o
u9+

Areas of application
Technical Data* CP 648-E
■■ Firestopping combustible pipe penetrations
Density Approx. 1.35 g/cm3
■■ Difficult applications where space is limited
Dimensions (approximate) 3/16" x 1" x 33 ft or
■■ Penetrations through concrete over metal deck
3/16" x 1-3/4" x 33 ft
■■ Plastic and insulated penetrations using
Color Black with foil backing
PVC, CPVC, ABS, FRPP and PEX
Temperature resistance –40°F to 212°F (–40°C to 100°C)
For use with Intumescent activation Approx. 320°F (160°C)
■■ Concrete, masonry, wood floor and gypsum wall assemblies Expansion ratio (unrestricted) 1:40
■■ Wall and floor assemblies rated up to 4 hours Tested in accordance with
• UL 1479 • ASTM E 814 • ASTM G21
Examples
■■ Waste water pipes *At 73°F (23°C) and 50% relative humidity

■■ Fresh water pipes


■■ Decking penetrations FILL, VOID OR CAVITY MATERIAL
FOR USE IN THROUGH-PENETRATION FM
FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY $33529(' Visit fbcsystemcompatible.com.
)RU3HQHWUDWLRQ)LUH6WRSV FBC™ is a trademark of
66Y7
&RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH
the Lubrizol Corporation.

Installation instructions for CP 648-E


Notice Opening Application of firestop system
• Before handling, read Material Safety Data Sheet and 1. Clean the plastic or insulated pipe penetration. 2. Tightly wrap the required number of strips
product label for safe usage and health information. Expansion of the intumescent material during a fire continuously around the penetrant, and hold in place
• Instructions below are general guidelines — always closes the plastic or insulated pipe penetration. Very with tape.
refer to the applicable drawing in the UL Fire dirty pipes (ie: with remains of mortar) may lead to 3. Push the Hilti Wrap Strip into the opening until it is
Resistance Directory or Hilti Firestop Systems Guide a delay in this closing action. Soiled ­plastic pipes flush with the substrate surface unless otherwise
for complete installation information or insulated pipe penetrations should, therefore, be required by the UL system. It may be required by
cleaned in the area where the CP 648-E Firestop the UL system to clamp, wire or use a Hilti Retaining
Wrap Strip is to be installed. Collar to secure the wrap strip in place for some
applications. FILL, VOID OR CAVITY MATERIALS
CLASSIFIED BY
4. If the UL system requires a
UNDERWRITERS cold smoke
LABORATORIES, seal, then
INC.
apply the proper
FORamount of Hilti FS-ONE sealant in
USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS
the opening over the wrap strip. DIRECTORY
R

SEE UL FIRE RESISTANCE


66Y7
5. For maintenance reasons, a penetration seal can be
permanently marked with an identification plate and
fastened in a visible position next to the seal.
Firestop
System Not for use
• In highly corrosive surroundings
1. Clean penetration 2. Wrap strips around 3. Push Wrap Strips 4. Seal penetration against 5. Fasten installation plate
pipe the specified number into hole smoke with FS-ONE (If required) • With unapproved retaining collars, anchors/fasteners
of times
• Outdoors

Storage
• Store only in the original packaging in a location
protected from moisture at temperatures between
23°F and 86°F (–5°C and 30°C).

Hilti Firestop
Saving lives
through innovation
and education

Hilti. Outperform. Outlast.


Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti Firestop Systems Guide
28
CERTIFICATE OF COMPLIANCE
Certificate Number 20160829-R13240
Report Reference R13240
Issue Date 2016-August-29

Issued to: Hilti Construction Chemicals, Div of Hilti Inc.


5400 S 122nd East Ave
Tulsa, OK 74146

This is to certify that Fill, Void or Cavity Materials


representative samples of Fill, Void or Cavity Materials Certified for Canada

CP 648E and CP 648S (Product number may be suffixed to


denote size) Wrap Strip for use in Through-Penetration
Firestop Firestop Systems as currently decribed in the UL
Fire Resistance Directory and in the Products Certified for
Canada Directory.

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: ANSI/UL 1479, "Fire Tests of Through-Penetration


Firestops,"
CAN/ULC-S115, "Standard Method of Fire Tests of Firestop
Systems."
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information

Only those products bearing the UL Certification Mark should be considered as being covered by UL's
Certification and Follow-Up Service.

Look for the UL Certification Mark on the product.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 1 of 1

29
September 24, 2015

To Whom It May Concern:

Re: CP 648 E&S Firestop Wrap Strips – LEED Information

Item Numbers:

304303 304307
304304 304308
304305 304309
304306

The Hilti CP 648 E & S Firestop Wrap Strips are manufactured in Germany.

The Hilti CP 648 E & S Firestop Wrap Strips have a VOC content of 3.1 grams/liter.

The amount of post-consumer or post-industrial content in CP 648 E & S Firestop Wrap Strips is not known. The packaging is
recyclable. The CP 648 E & S Firestop Wrap Strips do not contain any Rapidly Renewable Materials.

The CP 648 E & S Firestop Wrap Strips are not regulated as a hazardous waste by the Federal EPA Standards. The regulations
for the disposal of non-regulated industrial waste can vary from state to state and even city to city. For this reason, you should
consult your local and state regulatory agencies for direction on disposal.

Please feel free to contact me at (918) 872-3704 if you have questions.

Sincerely,

Jerry Metcalf MPH, CHMM


Sr. Manager, Safety/Environmental
Hilti Inc.
(918) 872 3704
jerry.metcalf@hilti.com

Rev. Date: 8/14/15

The manufacturing plant location on this certificate has been provided for LEEDS reporting purposes only. It should never be used
for Country of Origin certification or a representation of compliance/non-compliance with Buy American or Buy America
requirements, as those requirements differ.

The manufacturing plant location(s) identified on the certificate represent standard Hilti catalog products only. “Specially” produced
non-catalog Hilti products may have differing manufacturing plant locations.

Contact your Hilti representative in cases of “specially” produced products for a custom LEEDS certificates.

Hilti, Inc.
5400 South 122 n d East Avenue
Tulsa, OK 74146

1-800-879-8000
www.hilti.com

30
Product Information

Firestop Board
(CP 675T)

Introduction
Product description
■■ Ready to use Firestop Board designed for large openings with
cable trays and multiple penetrations

Product features
■■ Lightweight design
■■ Satisfies a wide range of application scenarios
■■ Allows for high flexibility and eases re-penetration/cable mining
from one side of the wall

Applications and Products


■■ Easy and fast cable re-penetration and cable mining with reduced
labor and materials
■■ Labor saving “one person, one sided installation” method
■■ Polyurethane foam material, easy to cut without electric tools Technical Data CP 675T
■■ No dust, no fibers, no mess Color Red
■■ Same system for all types of wall materials Dimensions (LxWxH) 26" x 39" x 1" (Large Board)
(660 mm x 990 mm x 25 mm)
Areas of application 26" x 28" x 1" (Small Board)
■■ Temporary or permanent sealing of cables and cable tray (660 mm x 711 mm x 25 mm)
penetrations Density 320 kg/m3
■■ Sealing single or multiple penetrations in large openings Application temperature -22°F to 176°F (-30°C to 80°C)
■■ Temporary or permanent sealing of large blank openings Temperature resistance -22°F to 176°F (-30°C to 80°C)
Surface burning characteristics Flame Spread Index: 5
For use with

Selector Guide
(ASTM E 84-00) Smoke Development Index: 10
■■ Concrete, concrete block, and gypsum wall assemblies
Tested in accordance with
■■ Concrete floor assemblies • UL 1479 • ASTM E 814 • ASTM E 84 • ASTM G21
Examples
■■ Locations where telecommunications and electrical applications FIRESTOP DEVICE
FOR USE IN THROUGH-PENETRATION
FM
are modified on a regular basis such as central office facilities, FIRESTOP SYSTEMS
SEE UL FIRE RESISTANCE DIRECTORY $33529('
computer data centers, commercial buildings, healthcare facilities, 5N76
)RU3HQHWUDWLRQ)LUH6WRSV
&RQVXOWWKH)DFWRU\0XWXDO5HVHDUFK&RUSRUDWLRQ$SSURYDO*XLGH
and laboratories
■■ New buildings under construction and during renovation

Through-Penetration
Installation Instructions for CP 675T Firestop Board
Notice 5. Attach Firestop Board with approved Hilti anchors as 4. Cut Firestop Boards to size +1/2" vertically. Use the
• Before handling, read Material Safety Data Sheet and specified in accordance with the applicable firestop extra 1/2" to compress the FS 657 Firestop Block
product label for safe usage and health information. system. When two Firestop Boards come together, partition and provide a tight fit into the opening.
• Instructions below are general guidelines — always seal intersection with CP 619T Putty Roll or FS-ONE Place CP 675T Distance Holders around Firestop
refer to the applicable drawing in the UL Fire (per firestop system requirements). Board at a maximum of every 8" . With downward
Resistance Directory or Hilti Firestop Systems Guide 6. Fasten identification plate (if required). pressure, press top of inside Firestop Board into
for complete installation information opening and push flush with back edge of Z-Frame
7. Repeat steps on other side of wall.
followed by outside Firestop Board inserted flush
Surface mounted installation (wall) Frame mounted installation (wall) with wall surface.FILL, VOID OR CAVITY MATERIALS
1. Clean the opening. 1. Clean the opening. 5. Secure front ofUNDERWRITERS
Firestop Board
CLASSIFIED BY
with Z-Frame
LABORATORIES, INC.
2. Measure the size of the opening. Cut the 2. Measure the size of the opening. Cut the CP 675T Latches every 8" . Apply CP 619T Putty Roll over
FOR USE IN TROUGH-PENETRATION
FIRESTOP SYSTEMS

Joint
Firestop Board to size (check system for overlap
R

Z-Frame component to size and attach to top the intersectionSEE


between the Board
UL FIRE RESISTANCE and the Frame.
DIRECTORY
requirements) with a utility knife, hand saw, circular and both sides of opening as specified by firestop Fill voids around penetrating 66Y7
items within FS 657
saw, jig saw, or table saw. system with appropriate Hilti fasteners. Apply Firestop Block partition with Hilti Firestop Putty.
3. If penetrants run through the opening, cut the CP 619T Putty Roll to back lip of Z-Frame inside Refer to UL systems for complete details.
Firestop Board correspondingly (max. annular space opening. 6. Fasten identification plate (if required).
between Board and penetrant: 1/2" ). The Board can 3. Apply a maximum of three rows (6") of FS 657
be cut into two pieces or just cut to allow space for Not for use
Firestop Blocks in the opening above and below
the penetrant(s). • In wet rooms, outdoors or in areas exposed to the
cable tray (lengthwise). Cut the CP 675T T-Separator
weather or UV radiation.
4. Apply CP 619T Putty Roll around edges of Bar to the width of the opening and put it on top of
the Firestop Board next to the wall. In case of the FS 657 Firestop Blocks (T-edge against back of Storage
penetrants, the cables and cable trays have to be opening). Apply CP 619T Putty Roll to the backward • Store only in the original packaging in a location
Reference Data

sealed with CP 619T Putty Roll at their interface with T-Bar edge protruding above the FS 657 Firestop protected from moisture and direct sunlight
the Firestop Board. Block section and around back lip of frames.

Hilti Firestop
Saving lives
through innovation
and education

Hilti. Outperform. Outlast.


Hilti, Inc. (U.S.) 1-800-879-8000 • www.us.hilti.com • en español 1-800-879-5000 • Hilti Firestop Systems Guide
31
CERTIFICATE OF COMPLIANCE
Certificate Number 20160829-R15431
Report Reference R15431
Issue Date 2016-August-29

Issued to: Hilti Construction Chemicals, Div of Hilti Inc.


7250 Dallas Pky, Legacy Tower Ste 1000
Plano, TX 75024 USA

This is to certify that Firestop Devices


representative samples of Firestop Devices Certified for Canada

CP 675T Firestop Board, CP 675T Distance Holders,


CP 675T Z-Frame, CP 675T Z-Frame Latches, CP 675T
T-Bars , CP675T T-Bar Latches for use in Through-
Penetration Firestop Firestop Systems as currently decribed
in the UL Fire Resistance Directory and in the Products
Certified for Canada Directory.

Have been investigated by UL in accordance with the


Standard(s) indicated on this Certificate.

Standard(s) for Safety: ANSI/UL 1479, "Fire Tests of Through-Penetration


Firestops,"
CAN/ULC-S115, "Standard Method of Fire Tests of Firestop
Systems."
Additional Information: See the UL Online Certifications Directory at
www.ul.com/database for additional information

Only those products bearing the UL Certification Mark should be considered as being covered by UL's
Certification and Follow-Up Service.

Look for the UL Certification Mark on the product.

Bruce Mahrenholz, Director North American Certification Program

UL LLC

Any information and documentation involving UL Mark services are provided on behalf of UL LLC (UL) or any authorized licensee of UL. For questions, please
contact a local UL Customer Service Representative at http://ul.com/aboutul/locations/

Page 1 of 1

32
Material Information Statement for Manufactured Articles

According to 1907/2006/EC, article 32


Revision: 05.04.2017 Version: 4

1 : Identification of the manufactured articles and of the company undertaking


1.1. Product identifier
Trade name  Hilti Firestop Bandage CFS-B  Hilti Firestop Plug Seal CFS-T RRS
 Hilti Firestop Block CFS-BL / CFS-BL P  Hilti Firestop Wedge Seal CFS-T WD120
 Hilti Firestop Back Pan Strip CFS-BPS  Hilti Firestop Top Track Seal CFS-TTS
 Hilti Firestop Cable Collar CFS-CC / CFS-RCC / CFS-  Hilti Smoke & Acoustic Track Seal CS-TTS
RCC EXT SA
 Hilti Firestop Cast-In Device CFS-CID  Hilti Firestop Wrap Strip CFS-W EL / SG / P
 Hilti Firestop Collar CFS-C / CFS-C P  Hilti Foil Tapes CS-FT all
 Hilti Firestop Endless Collar CFS-C EL  Hilti Multifunctional Tapes CS-MFT all
 Hilti Firestop Composite Sheet CFS-COS  Hilti Joint Sealing Tapes CS-JST all
 Hilti Firestop Drop-In Device CFS-DID  CP 643
 Hilti Firestop Module Box CFS-MB  CP 644
 Hilti Firestop Plug CFS-PL  CP 646
 Hilti Firestop Speed Sleeve CFS-SL  CP 648
 Hilti Firestop Gangplate CFS-SL GP  CP 651N
 Hilti Firestop Retrofit Sleeve CFS-SL RK  CP 653
 Hilti Firestop Sleeve Kit CFS-SL SK  CP 657
 Hilti Firestop Cable Module CFS-T  CP 658
 Hilti Firestop Filler Module CFS-T FB  CP 675
 Hilti Firestop Plug Seal CFS-T RR  CP 680
 CP 681

1.2. Application of the manufactured articles


Construction industry.
Refer to Hilti product literature, technical data sheets, 3rd party published listings and national approvals for specific application information. For
more details please contact your local Hilti organization through http://www.hilti.com.

1.3. Manufacturer / Supplier


Hilti AG
Feldkircherstr. 100
FL-9494 Schaan
Liechtenstein

Customer Service
Phone +423 (0)844 84 84 85
Fax +423 (0)844 84 84 86

2 : Other information

A Safety Data Sheet is not required due to the classification of these products as “manufactured articles” according to Regulation (EC) No.
1907/2006 of 18 December 2006 (EU) / 29CFR 1910.1200 (U.S.A.). Consequently, these products are exempted from CLP / OSHA Labeling and
SDS requirements.

These data are based on our present knowledge. However, they shall not constitute a guarantee for any specific product features and shall not
establish a legally valid contractual relationship.

Informing department:
chemicals.hse@hilti.com

03/01/2017 EN (English) 1/1

33
August 13, 2013

To Whom It May Concern:

Re: Hilti CP 675T Firestop Board – LEED Info

The Hilti CP 675T Firestop Board is manufactured in Hungary.

The amount of post-consumer recycled content and pre-consumer recycled content used in the
manufacture of Hilti CP 675T Firestop Board is not known. The VOC content of Hilti CP 675T
Firestop Board is 1.9 g/L.

Hilti CP 675T Firestop Board is not regulated as a hazardous waste by the Canadian EPA
Standards. The regulations for the disposal of non-regulated industrial waste can vary from
province to province and even city to city. For this reason, you should consult your local and
provincial regulatory agencies for direction on disposal.

Please feel free to contact me at (918) 872-3704 if you have questions.

Sincerely,

Jerry Metcalf MPH, CHMM


Sr. Manager Safety, Environmental, and Facilities
Hilti Inc.
918 872 3704
jerry.metcalf@hilti.com

Rev. Date: 6/7/11

Hilti, Inc.
nd
5400 South 122 East Avenue
Tulsa, OK 74146

1-800-879-8000
www.hilti.com

34
Product information

High-performance intumescent firestop


sealant FS-ONE MAX
Applications
■■ For effectively sealing most common through penetrations in a variety
of base materials
■■ For use on concrete, masonry and drywall
■■ Mixed and multiple penetrations
■■ Metal pipe penetrations: copper, steel and EMT
■■ Insulated metal pipe penetrations: steel and copper
■■ Plastic pipe penetrations: closed or vented

Advantages
■■ US-produced: “Buy American” compliant
■■ One product for a variety of common through penetrations
■■ Cost-effective, easy-to-use solution
■■ Water-based and paintable Technical data
■■ Industry-leading VOC results Chemical basis Water-based acrylic dispersion
■■ Ethylene glycol-free
Approx. Density 84.3 lb/ft³

Color Red

Application temperature range 41 - 104 °F

Approx. cure time 1)


4 mm/3 days

Temperature resistance range -4 to 212 °F

Chemical Mold and mildew Mold and mildew performance Class 0 (ASTM G21-96)
resistant resistant
Mold and mildew resistance Yes
FILL, VOID OR CAVITY MATERIAL Surface burning characteristics Flame spread: 0
FOR USE IN THROUGH-PENETRATION
FIRESTOP SYSTEMS
UL 723 (ASTM E84) Smoke development: 10
SEE UL FIRE RESISTANCE DIRECTORY Tested in accordance with UL 1479, ASTM E814, ASTM E84,
66Y7
CAN/ ULC-S115, ASTM G21, ASTM E90
California State fire marshal approval CSFM Listing 4485-1200:0108 for
FS-ONE MAX Intumescent Firestop
Sealant
Expansion ratio (unrestricted, up to) 1:5

1)
at 75°F/24°C, 50% relative humidity

Order Designation Package Content Item number


FS-ONE MAX 20oz foil (3 case + disp) 1x Foil pack dispenser manual CS 270-P1, 75x Firestop sealant FS-ONE MAX 20 oz foil 3530252
FS-ONE MAX 10oz tube (1 case) 12x Firestop sealant FS-ONE MAX 10 oz cartridge 3530249
FS-ONE MAX 5 gallon (18 pails) 18x Firestop sealant FS-ONE MAX 5 gallon pail 3530263
FS-ONE MAX 20oz foil (1 case) 25x Firestop sealant FS-ONE MAX 20 oz foil 3530250
FS-ONE MAX 20oz foil (3 cases) 75x Firestop sealant FS-ONE MAX 20 oz foil 3530251
FS-ONE MAX 20oz Foil-Pallet 600x FSONE-MAX 20 oz foil, 290x Bulk Shipping Condition 3534713
FS-ONE MAX 10 oz cartridge 2101531
12/16 DBS

FS-ONE MAX 5 gallon pail 2101533

Hilti. Outperform. Outlast.


Hilti, Inc. (USA) 1-800-879-8000 I www.us.hilti.com I en español 1-800-879-5000 I Hilti (Canada) Corp. 1-800-363-4458 I www.hilti.ca

35
36
August 26, 2015

To Whom It May Concern:

Re: Hilti FS-ONE Max Firestop – LEED Info.

Item Numbers:

2101531
2101532
2101533

The Hilti FS-ONE MAX Firestop is manufactured in the United States

There is no post-consumer or post-industrial content in FS-ONE MAX and it cannot be recycled. The VOC content for FS-ONE
MAX is 9 grams/liter.

FS-ONE MAX is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-
regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and
state regulatory agencies for direction on disposal.

Please feel free to contact me at (918) 872-3704 if you have questions.

Sincerely,

Jerry Metcalf MPH, CHMM


Sr. Manager, Safety/Environmental
Hilti Inc
(918) 872 3704
jerry.metcalf@hilti.com

Rev. Date: 7/31/15

The manufacturing plant location on this certificate has been provided for LEEDS reporting purposes only. It should never be used
for Country of Origin certification or a representation of compliance/non-compliance with Buy American or Buy America
requirements, as those requirements differ.

The manufacturing plant location(s) identified on the certificate represent standard Hilti catalog products only. “Specially” produced
non-catalog Hilti products may have differing manufacturing plant locations.

Contact your Hilti representative in cases of “specially” produced products for a custom LEEDS certificates.

Hilti, Inc.
nd
5400 South 122 East Avenue
Tulsa, OK 74146

1-800-879-8000
www.hilti.com

37
Fire Containment Insulation Thermafiber® Safing™

+ Exceptional performance in Perimeter


Fire Containment Systems

+ Provides life saving fire protection in


rated assemblies

+ F
ire resistant to temperatures above
2,000°F (1,093°C)

+ E
asy to fabricate for through
penetrations and firestopping

+ Conserves energy, reduces


greenhouse gas emissions

+ Resists moisture

+ Controls noise and sound

LEED v2009 Green Building Credits


®

Energy & Materials Indoor Innovation in


Minimum Atmosphere & Resources Environmental Design

70%
Quality
1 2.1, 2.2 9 1
Recycled 4.1, 4.2
Content1 5.1, 5.2
Thermafiber Safing and FireSpan® insulation provide the critical components of
the perimeter fire containment system in the 111 South Wacker Building in Chicago,
IL. Thermafiber insulation also contributed to the building’s LEED® Gold Rating.

Thermafiber® SafingTM is compression fitted between FireSpan® insulation and


the concrete slab edge to create a perimeter fire containment system.
38
Thermafiber® SafingTM Insulation
THERMAFIBER SafingTM products are designed to provide life saving fire protection in perimeter fire containment
Description: systems, floor and wall penetrations, construction joints, and other firestopping applications. These products are
noncombustible, moisture-resistant, noncorrosive, nondeteriorating, mildew-proof and vermin-proof. Thermafiber Safing
provides thermal insulation, fire protection, and acoustical control in many different UL and Intertek (formerly OPL) listed
fire containment assemblies of 1, 2, and 3-hr ratings.
• Safing 4.0 pcf, 2” or greater thickness, is available with or without a vapor retarding foil facing.
Product Options: • Safing 6.0 pcf, 1.5” or greater thickness, is available with or without a vapor retarding foil facing.
• Recycled Content Options1:
EPA Choice Fiber (US Government Buildings)......... Minimum 75%
Standard Fiber..................................................................... 70%
1
Recycled content options other than Standard must be specified at time of order.

All firestopping insulation should be installed per the architectural specification or system specific test description. All
Installation: compressed Safing insulation should be installed per the listed assembly.
• Perimeter Installation: SafingTM insulation should be compression fitted between the slab edge and the FireSpan
curtain wall insulation, leaving no voids.
• Penetration Application: Safing insulation should be cut slightly larger than the opening and compression fitted into the
opening, leaving no voids.
• Construction Joint Application: Safing insulation should be compression fitted into the joint opening, leaving no voids.

Standard Sizes: Thickness* Widths** Lengths**


Safing 4.0 pcf 1”- 7” 16”, 24”, 36” 48”, 60”
Safing 6.0 pcf 1”- 7” 16”, 24”, 36” 48”, 60”
Tolerances +1/4” - 1/8” ±1/8” ±1/2”
*Thicknesses are available in ½” increments. **Custom sizes are available upon request.

Technical Data: Tested to ASTM E 84


Tested to ASTM C 518 Unfaced Foil Faced
Product Actual “k” @ 75° [24°C] “R” value per Flame Smoke Flame Smoke
Designation Density
BTU.in/hr.sq. ft. °F inch of thickness*** Spread Developed Spread Developed

TF612/Rev 03-15 Copyright 2015, Thermafiber, Inc. All Rights Reserved. LEED® is a registered trademark of U.S. Green Building Council.
Safing 4.0 pcf 0.24 ‘R’= 4.2 0 0 25 0
Safing 6.0 pcf 0.24 ‘R’= 4.2 0 0 25 0
***R = thickness divided by ‘k’

SafingTM insulation is a critical component of any perimeter fire containment system. Thermafiber® has performed decades
Fire-Containment Tests of testing in all of the containment systems listed below. For more complete test information, see SA707, THERMAFIBER
Per ASTM E 2307 Life-Safety Fire Containment Systems technical catalog or UL® and Intertek® (formerly OPL) Directories. For a full listing of
containment systems visit www.thermafiber.com and click on Fire Rated Assemblies. UL Reference = TYPE SAF
• Aluminum Spandrel Curtain Wall Fire Containment
• Steel Stud-Framed/Gypsum Sheathing Curtain Wall Fire Containment
• Glass Spandrel Curtain Wall Fire Containment
• Granite Spandrel Curtain Wall Fire Containment
• Precast Concrete Spandrel

SafingTM Insulation meets the following:


Standards Compliance: ASTM C 665 Non-corrosive, Type I, III
ASTM C 612 Type IA, IB, II
ASTM E 136 Rated Non-combustible per NFPA Standard 220
CAN/ULC S114 Complies
ASTM E 96 Unfaced, 50 Perms as tested
ASTM E 96 Foil Faced, 0.02 Perms as tested
ASTM C 1104 Absorbs less than 1% by volume
CAN/ULC S102 Flame Spread 0, Smoke Developed 0
ASTM E 814 or UL 1479 Safing Insulation used in conjunction with an approved fill, void, or cavity material
sealant or other approved material in through – penetration firestop systems - Complies
UL 2079 Safing Insulation used in conjunction with an approved fill, void or cavity material
in construction joint systems - Complies
CAN/ULC S115 Complies
Safing products are approved by: New York City Board of Standards & Appeals – (under BSA 39-74-SM & accepted by
MEA-209-82-M, Vol. 4).

Thermafiber offers industry leading technical and engineering assistance to architects, specifiers, and contractors.
Thermafiber® Insolutions®: These services include CAD drawings, engineering judgments, LEED® Credit Information, product recommendations,
and customized products. Contact our technical services department at
1-888-834-2371, or email technicalservice@owenscorning.com
For additional information about these or other Thermafiber products contact us at 1-888-834-2371 or visit our
For Further Information: website www.thermafiber.com.
THERMAFIBER, Inc. shall not be liable for incidental and consequential damages, directly or indirectly sustained, nor for any loss caused by application of
Notice: these goods not in accordance with current printed instructions or for other than the intended use. THERMAFIBER liability is expressly limited to replacement of
defective goods. Any claim shall be deemed waived unless made in writing within thirty (30) days from date it was or reasonably should have been discovered.

Submittal Approvals: Job Name

Contractor Date

3711 Mill Street | Wabash, IN 46992 | 888-TFIBER1 [834-2371] | [260] 563-2111 | www.thermafiber.com
39
THERMAFIBER SafingInsulation
Submittal Sheet ®
07840

UL- and OPL-labeled* safing insulation for firestops and fire-containment systems
• Firestop product for curtain wall fire and smoke containment systems, floor and wall penetrations,
head-of-wall, and other construction joint systems.
• Fire resistant and noncombustible.
• Economical; installs quickly and easily.
• Aids sound control in many assemblies.
• Available in unfaced felt (plain) or with a tough scrim-reinforced foil facing (FSP).
• Durable; nondeteriorating and noncorrosive.
Description THERMAFIBER® Safing Insulation is a mineral-wool-type insulation that resists temperatures up to
2,000 °F (1,093 °C), thus offering superior fire protection in a wide variety of fire-rated applications. It is
a UL- and OPL-labeled product especially intended for tested UL and OPL Designs, as well as many other
fire- and smoke-tested assemblies. This product is noncombustible per Standard NFPA 220 when tested
in accordance with ASTM E 136, and moisture-resistant, noncorrosive, nondeteriorating, mildew-proof
and vermin-proof. It permits dry construction for all-year-round work. Also, THERMAFIBER Safing
Insulation is available plain, or with scrim-reinforced foil facing (FSP) that serves as a vapor retarder
and/or smoke barrier.

THERMAFIBER Safing Insulation is compatible with both THERMAFIBER® Curtain Wall CW Insulations and
THERMAFIBER FIRESPAN™ Insulations.

Perimeter Fire Containment,


Penetrations and Construction Joints
THERMAFIBER Safing Insulation is a key element in a wide variety of fire-tested construction assemblies.
It is used with THERMAFIBER Curtain Wall and FIRESPAN Insulations in applications to contain both fire
and smoke to the area of origin. Especially for mid- and high-rise buildings, where fire and smoke must
be prevented from spreading to the next floor. Since the floor assembly is typically fire-rated, one route
for the fire spread is through and up the exterior curtain wall system. THERMAFIBER Safing Insulation is
also used in conjunction with various sealants and caulks, in wall and floor penetration (poke-through)
applications, head-of-wall construction joints, and other construction joints.

It is important to note that one of the most valuable yet misunderstood applications of
THERMAFIBER Safing Insulation is its use in exterior curtain wall assemblies to safe-off the opening
between concrete floor slabs and the curtain wall assemblies. Many people still believe the myth that all
thermal insulations are the same when used in the curtain wall spandrel panels as long as
THERMAFIBER Safing Insulation is used in the assembly. This is simply not true. Actual fire tests have
proven that low-melt-point insulations, such as glass fiber types, will disintegrate quickly once exposed
to fire, leaving the curtain wall unprotected. Then, as the now-unprotected curtain wall disintegrates or
falls away, the safing insulation will no longer be supported, and the fire will spread to the floor(s) above.
Effective perimeter fire containment can only be achieved when a fire-compatible product with the ability
to resist high temperatures (such as THERMAFIBER Curtain Wall Insulations or THERMAFIBER
FIRESPAN Insulations) is used in conjunction with the THERMAFIBER Safing Insulation, acting together as
a system. (See TF685, TF686 and TF871 for additional information).

Installation Perimeter Installation In curtain wall fire-containment applications, THERMAFIBER Safing Insulation fills the void between the
slab edge and the curtain wall insulation to contain fire. Foil-faced insulation impedes the passage of
smoke and noxious gases. Install THERMAFIBER Safing Insulation, of proper width (2" to 8" max.
opening), compression fit in safe-off area (foil side up, if required) between THERMAFIBER FIRESPAN or
CW Curtain Wall Insulation and floor slabs, on safing "Z" clips spaced as required in the design (24" or
12" o.c. maximum), leaving no voids. Compression fitting the safing insulation is critical to assuring a
tight seal. See specific test description for proper installation details. Install proper topping material,
such as THERMAFIBER SMOKE SEAL Compound, or other approved smoke sealants as indicated in the spe-
cific test description or architectural specification.

Penetration Application THERMAFIBER Safing Insulation provides a noncombustible, fire-resistant forming/packing material for
many types of penetrations in walls and floor/ceilings. In all poke-through penetrations, clean substrate
of dirt, dust, grease, oil, efflorescence, loose material or other matter. With a serrated knife, cut
THERMAFIBER Safing Insulation slightly wider than the opening. Compress and tightly fit the minimum
thickness and density of insulation required (per system specification) completely around penetrant. For
floor slab openings, compress or install THERMAFIBER Safing Insulation according to details indicated in
the specific test description or architectural specification to seal completely around cables, ducts, piping
or other utilities.

Construction Joint THERMAFIBER Safing Insulation is also used as a forming material in head-of-wall, floor to floor, floor to
Application wall, and wall to wall construction joints. It is compressed and slid into joint openings to completely fill
the gap between the intersection of the walls, floor, etc.
* UL is an abbreviation for Underwriters Laboratories Inc.; OPL is an abbreviation for Omega Point Laboratories, Inc.

40
Technical Data Surface Burning Product Designation Flame Spread Smoke Developed
Characteristics Safing, Regular (Unfaced) 0 0
(According to ASTM E 84) Safing (Foil-Faced) 25 0
Products have a class A interior finish rating per NFPA 101, life safety code.

Product Density
Product Actual Density Minimum Application
Designation Density Tolerance-pcf(1) Thickness Method
Safing 4.0 -0.5 +1.0 1" safing clips and/or compression fit
Safing 6.0 -0.75 +2.0 1-1/2" safing clips and/or compression fit
Safing 8.0 -1.0 +2.0 1" safing clips and/or compression fit
(1) On packaging weight basis.

For the most up-to-date technical data, please refer to our website at www.thermafiber.com

Product Data Standards Compliance THERMAFIBER Safing Insulation meets the following:

ASTM C 665 - Federal Specification HH-I-521F–Safing insulation as Types I and III, Class A, Category 1.

ASTM C 612-00 - Federal Specification HH-I-558B–Safing insulation as Types IA, IB and II.

ASTM E 136 - Rated noncombustible as defined by NFPA Standard 220 when tested according to
ASTM E 136.

ASTM E 814 or UL 1479 - Safing insulation used in conjunction with SMOKE SEAL Compound,
or other approved material in through - penetration firestop systems.

UL 2079 - Safing insulation used in conjunction with various sealants and caulks in construction joint
systems.

ASTM C 553 - THERMAFIBER Insulations absorb less than 1% moisture by weight and volume.

Safing insulation products are approved by: New York City Board of Standards & Appeals– 39-74-SM &
MEA 209-82-M, Vol. II.

Composition and THERMAFIBER blankets are a mineral fiber material manufactured from blast furnace slag, a by-product of
Materials iron ore reduction, and naturally occurring rock. THERMAFIBER blankets contain greater than 80% post-
industrial recycle content. This product contains No Asbestos.

Warranty System performance following substitution of materials or compromise in assembly design cannot be
certified and may result in failure of fire performance under certain conditions. Products and systems
provided by Thermafiber Inc. are warranted to be free from defects in material workmanship. Contact
Thermafiber Inc. for complete warranty details.

Storage Store in a cool, dry place.

Submittal
Approvals:
Job Name

Contractor Date
Trademarks Note Notice Safety First! Health Aspects
THERMAFIBER, FIRESPAN and THE Products described here may not be THERMAFIBER INC. shall not be Follow good safety and industrial Information about health aspects of
NAME IN MINERAL WOOL are trade- available in all geographic markets. liable for incidental and consequential hygiene practices while handling and using THERMAFIBER® Curtain Wall
marks of Thermafiber Inc. SMOKE Consult your local sales office or rep- damages, directly or indirectly installing products and systems. Insulation products are thoroughly
SEAL is a trademark of United States resentative for information. sustained, nor for any loss caused by Take necessary precautions and wear explained in North American
Gypsum Company. application of these goods not in the appropriate personal protective Insulation Manufacturers
accordance with current printed equipment as needed. Read material Association’s (NAIMA) Health and
instructions or for other than the safety data sheets and related litera- Safety facts for rock and slag wool
intended use. THERMAFIBER’S ture on products before specification insulation document #63. Contact
liability is expressly limited to and/or installation. Thermafiber, Inc. for more details.
replacement of defective goods. Any
claim shall be deemed waived unless
made in writing within thirty (30)
days from date it was or reasonably
should have been discovered.

3711 West Mill Street


Wabash, IN 46992-8687

THERMAFIBER MADE FROM


INC

1-888-TFIBER1 (834-2371)
RECYCLED MATERIALS MADE IN USA

www.thermafiber.com

TF612/Rev 11/06
Copyright 2004, Thermafiber Inc.
Printed in U.S.A.

41
42
September 24, 2015

To Whom It May Concern:

Re: Hilti Mineral Wool-LEED Information

Item Number:

236993

The Hilti Mineral Wool is manufactured in Wabash, Indiana.

The post-consumer recycled content in the Hilti Mineral Wool is 0%. The pre-consumer recycled content in the Hilti Mineral Wool
is 90%. There is no detectable VOC content in this product.

Hilti Mineral Wool is not regulated as a hazardous waste by the Federal EPA Standards. The regulations for the disposal of non-
regulated industrial waste can vary from state to state and even city to city. For this reason, you should consult your local and
state regulatory agencies for direction on disposal.

Please feel free to contact me at (918) 872-3704 if you have questions.

Sincerely,

Jerry Metcalf MPH, CHMM


Sr. Manager, Safety/Environmental
Hilti Inc.
918 872 3704
jerry.metcalf@hilti.com

Rev. Date: 9/24/15

The manufacturing plant location on this certificate has been provided for LEEDS reporting purposes only. It should never be used
for Country of Origin certification or a representation of compliance/non-compliance with Buy American or Buy America
requirements, as those requirements differ.

The manufacturing plant location(s) identified on the certificate represent standard Hilti catalog products only. “Specially” produced
non-catalog Hilti products may have differing manufacturing plant locations.

Contact your Hilti representative in cases of “specially” produced products for a custom LEEDS certificates.

Hilti, Inc.
5400 South 122 n d East Avenue
Tulsa, OK 74146

1-800-879-8000
www.hilti.com