Description Page
Type designation 1
Technical data
- General 2
- Specification 3
- Installation instruction 3
N - V - O - N - F - O - B
N Position 1 : Product group Ordering example :
N = air volume control terminals N V O N F O B 1 6 0 R 0 5 0 0
O = not applicable
V = VAV Induction terminal
W = VAV Induction terminal with controlled induction
1 = non standard , specify separately
N Position 4 : Outlet
O = not applicable
A = rectangular outlet
C = 4 circular outlets ('Octopus')
G = rectangular outlet and provision for integral hot water reheat coil Ordering codes " Specials "
J = 4 circular outlets and provision for integral hot water reheat coil
N = rectangular outlet and provision for integral electric reheat coil N..1... - 3010 = 4 balancing dampers in
Q = 4 circular outlets and provision for integral electric reheat coil ' Octopus’ outlet
1 = non standard, specify separately N..1... - 3006 = ‘Octopus’ with 6 outlets
instead of 4
N..1... - 3016 = ‘Octopus’ with 6 outlets
F Position 5 : Reheat coil incl. balancing dampers
N..1... - FL = Flange connection 30
O= without reheat coil mm for rectangular
A= 1-row hot water reheat outlet
B= 2-row hot water reheat
D= 4-row hot water reheat
E= 1-stage 230VAC/1-phase electric reheat coil
Ordering information :
F= 2-stage 230VAC/1-phase electric reheat coil
G= 3-stage 230VAC/1-phase electric reheat coil
H= 1-stage 400VAC/3-phase electric reheat coil Standard terminals:
J= 2-stage 400VAC/3-phase electric reheat coil
- quantity of terminals
1= non standard, specify separately
- complete 7 digit code
- terminal size or model
O Position 6: Controls ( type & function ) - air volume setting (V max , V min etc)
- control handing (standard right side)
O = without controls - if applicable, electric reheat coil
For controls, contact our sales staff capacity
B Positon 7: Sensor
Non standard terminals:
1
Changes w/o notice or obligation
Rev 100426
Induction VAV Technical data
air volume control terminals Type (NV.....)
N V OA
®
Application ● Flo-Cross , 2 x 12 points Controls:
averaging and signal amplifying Suitable for use with pneumatic,
Types NV rectangular pressure- airflow sensor, better than 2.5% analogue electronic or DDC
independent VAV air volume accuracy even with irregular duct controllers. Controls can be
control terminals are designed approach . factory fitted, wired and calibrated .
particularly for systems with high ● Maintenance free . Controls enclosure ( galvanised
variations in heat load . The sheet steel ) can be provided
terminals induce room air and mix Technical information optionally .
it with conditioned primary air,
maintaining a nearly constant air Casing : Delivery format:
volume to the room thus providing Air-tight construction made of
sufficient air movement necessary galvanized sheet steel with low Delivery format:
to maintain occupant comfort even casing leakage rate. ● The VAV or CAV terminal will be
in extreme load variations.This supplied as a single mounting
specific characteristic means that Insulation : assembly.
cold air ‘dumping’ will not occur The rectangular discharge section Optional ordered distribution
and that extremely low primary air is internally insulated . plenum, reheat coil and/or
temperatures can be used, without controls are factory fitted, wired
producing excessive differences Damper : and calibrated. The terminal can
between the supply and the room Damper blade : made of steel , be directly installed and
air temperature. The primary air is sandwich construction with twin commissioned when delivered to
controlled by the patented airflow blades and a neoprene gasket with site.
®
sensor type Flo-Cross . The low leakage .
Induction VAV terminals can be Damper shaft : aluminium,Φ ● Controls location and hot water
used for supply air applications in 12mm with self lubricating nylon or electric connections are as
new or refurbishment projects. bearings. standard fitted on the right hand
The terminals can optionally be side of the terminal when looking
supplied with a distribution plenum Flo-Cross ®: in the direction of the airflow .
and a built-in hot water or electric Extruded aluminium construction On request, the terminal can be
reheat coil. with nylon core and feet . delivered with connections on
the left hand side.
Features: Distribution plenum :
● Pressure independent control
Made of galvanised sheet steel ● When terminals are ordered
functions . with 13 mm internal isolation. with controls, these will be
● Volume control range 100% to
Plenum with standard rectangular factory fitted, wired and
10% . or multiple (4 x circular) outlet calibrated upon request .
● Low pressure loss over the
construction. Optional 1,2,3 or 6
terminal . circular outlets are possible .
● Factory fitted distribution Outlet spigots are made of
plenum with built - in hot water galvanised steel and optionally
or electric reheat coil . can be provided with volume
● Oval shaped damper blade for
control dampers .
linear control characteristics .
● Low leakage damper, less than
Reheat coil :
1% of Vnom at 750 Pa . Choice of 1, 2 or 4-row hot water
● Low noise level .
reheat coil or electric reheat coil
● Suitable for all control functions
(230VAC/1-phase or 400VAC/3-
(VAV, CAV, shut-off, etc.) To phase).
maximise system energy savings.
2
Changes w/o notice or obligation
Rev 100426
Induction VAV Technical data
air volume control terminals Type (NV.....)
N V OJ
3
Changes w/o notice or obligation
Rev 100426
Induction VAV Model overview
air volume control terminals Type (NV.....)
Type N V OA . OB Type N V OC . OB
Kv values
air volume
1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Talbe 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct. Model
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated
discharge sound and case radiated sound. Figures by “- -”.
less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections,
table 1 for downstream ductwork including a please contatct our technical staff.
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined
with the assumptions as mentioned in table 1 for Discharge (dB)
ceiling plenum and suspended ceiling absorption. Radiated (dB)
6
Changes w/o notice or obligation
Rev 100426
Induction VAV Type (NVOAOOB)
air volume control terminals
Sound data Δp = 250 Pa
data refering to discharge sound radiated sound
inlet spigot
Lp values Lp values
air volume
1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Talbe 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct. Model
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated
discharge sound and case radiated sound. Figures by “- -”.
less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections,
table 1 for downstream ductwork including a please contatct our technical staff.
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined
with the assumptions as mentioned in table 1 for Discharge (dB)
ceiling plenum and suspended ceiling absorption. Radiated (dB)
7
Changes w/o notice or obligation
Rev 100426
Induction VAV Type (NVOCOOB)
air volume control terminals
Sound data Δp = 150 Pa
data refering to discharge sound radiated sound
inlet spigot
Lp values Lp values
air volume
1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Talbe 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct.
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated
discharge sound and case radiated sound. Figures by “- -”.
less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections,
table 1 for downstream ductwork including a please contatct our technical staff.
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined
with the assumptions as mentioned in table 1 for Discharge (dB)
ceiling plenum and suspended ceiling absorption. Radiated (dB)
8
Changes w/o notice or obligation
Rev 100426
Induction VAV Type (NVOCOOB)
air volume control terminals
Sound data Δp = 250 Pa
data refering to discharge sound radiated sound
inlet spigot
Lp values Lp values
air volume
1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Talbe 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct.
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated
discharge sound and case radiated sound. Figures by “- -”.
less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections,
table 1 for downstream ductwork including a please contatct our technical staff.
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined
with the assumptions as mentioned in table 1 for Discharge (dB)
ceiling plenum and suspended ceiling absorption. Radiated (dB)
9
Changes w/o notice or obligation
Rev 100426
Induction VAV Type NVOG . OB NVON . OB
air volume control terminals
Sound data Δp = 150 Pa
data refering to discharge sound radiated sound
inlet spigot
Lp values Lp values
air volume
1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Talbe 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct.
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated
discharge sound and case radiated sound. Figures by “- -”.
less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections,
table 1 for downstream ductwork including a please contatct our technical staff.
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined
with the assumptions as mentioned in table 1 for Discharge (dB)
ceiling plenum and suspended ceiling absorption. Radiated (dB)
10
Changes w/o notice or obligation
Rev 100426
Induction VAV Type NVOG . OB NVON . OB
air volume control terminals
Sound data Δp = 250 Pa
data refering to discharge sound radiated sound
inlet spigot
Lp values Lp values
air volume
1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Talbe 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct.
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated
discharge sound and case radiated sound. Figures by “- -”.
less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections,
table 1 for downstream ductwork including a please contatct our technical staff.
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined
with the assumptions as mentioned in table 1 for Discharge (dB)
ceiling plenum and suspended ceiling absorption. Radiated (dB)
11
Changes w/o notice or obligation
Rev 100426
Induction VAV T ype NVOJ . OB NVOQ . OB
air volume control terminals
Sound data Δp = 150 Pa
data refering to discharge sound radiated sound
inlet spigot
Lp values Lp values
air volume
1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Talbe 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct.
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated
discharge sound and case radiated sound. Figures by “- -”.
less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections,
table 1 for downstream ductwork including a please contatct our technical staff.
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined
with the assumptions as mentioned in table 1 for Discharge (dB)
ceiling plenum and suspended ceiling absorption. Radiated (dB)
12
Changes w/o notice or obligation
Rev 100426
Induction VAV Type NVOJ . OB NVOQ . OB
air volume control terminals
Sound data Δp = 250 Pa
data refering to discharge sound radiated sound
inlet spigot
Lp values Lp values
air volume
1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Talbe 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct.
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated
discharge sound and case radiated sound. Figures by “- -”.
less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections,
table 1 for downstream ductwork including a please contatct our technical staff.
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined
with the assumptions as mentioned in table 1 for Discharge (dB)
ceiling plenum and suspended ceiling absorption. Radiated (dB)
13
Changes w/o notice or obligation
Rev 100426