NV series

Induction VAV air volume control terminals


Induction VAV
Table of contents
air volume control terminals

Description Page

Type designation 1

Technical data

- General 2

- Specification 3

- Installation instruction 3

Model overview / dimensions 4-5

Sound data NVOAOOB... 6-7

Sound data NVOCOOB... 8-9

Sound data NVOG.OB / NVON.OB 10 -11

Sound data NVOJ.OB / NVOQ . OB... 12 -13

Changes w/o notice or obligation


Rev 100426
Induction VAV Type designation
air volume control terminals NV.....

Composition type designation:

N - V - O - N - F - O - B
N Position 1 : Product group Ordering example :
N = air volume control terminals N V O N F O B 1 6 0 R 0 5 0 0

V Position 2 : Function See above Model Heater capacity

O = not applicable
V = VAV Induction terminal
W = VAV Induction terminal with controlled induction
1 = non standard , specify separately

O Position 3 : Controls ( manufacturer )


O = without controls
For controls , contact our sales staff

N Position 4 : Outlet
O = not applicable
A = rectangular outlet
C = 4 circular outlets ('Octopus')
G = rectangular outlet and provision for integral hot water reheat coil Ordering codes " Specials "
J = 4 circular outlets and provision for integral hot water reheat coil
N = rectangular outlet and provision for integral electric reheat coil N..1... - 3010 = 4 balancing dampers in
Q = 4 circular outlets and provision for integral electric reheat coil ' Octopus’ outlet
1 = non standard, specify separately N..1... - 3006 = ‘Octopus’ with 6 outlets
instead of 4
N..1... - 3016 = ‘Octopus’ with 6 outlets
F Position 5 : Reheat coil incl. balancing dampers
N..1... - FL = Flange connection 30
O= without reheat coil mm for rectangular
A= 1-row hot water reheat outlet
B= 2-row hot water reheat
D= 4-row hot water reheat
E= 1-stage 230VAC/1-phase electric reheat coil
Ordering information :
F= 2-stage 230VAC/1-phase electric reheat coil
G= 3-stage 230VAC/1-phase electric reheat coil
H= 1-stage 400VAC/3-phase electric reheat coil Standard terminals:
J= 2-stage 400VAC/3-phase electric reheat coil
- quantity of terminals
1= non standard, specify separately
- complete 7 digit code
- terminal size or model
O Position 6: Controls ( type & function ) - air volume setting (V max , V min etc)
- control handing (standard right side)
O = without controls - if applicable, electric reheat coil
For controls, contact our sales staff capacity

B Positon 7: Sensor
Non standard terminals:

O =not applicable - for non standard terminals a full


B =Flo-cross ®, 2 x 12 point averaging and signal description and / or drawing are
amplifying air flow sensor (standard) requested.
1 =non standard, specify separately

1
Changes w/o notice or obligation
Rev 100426
Induction VAV Technical data
air volume control terminals Type (NV.....)

N V OA

®
Application ● Flo-Cross , 2 x 12 points Controls:
averaging and signal amplifying Suitable for use with pneumatic,
Types NV rectangular pressure- airflow sensor, better than 2.5% analogue electronic or DDC
independent VAV air volume accuracy even with irregular duct controllers. Controls can be
control terminals are designed approach . factory fitted, wired and calibrated .
particularly for systems with high ● Maintenance free . Controls enclosure ( galvanised
variations in heat load . The sheet steel ) can be provided
terminals induce room air and mix Technical information optionally .
it with conditioned primary air,
maintaining a nearly constant air Casing : Delivery format:
volume to the room thus providing Air-tight construction made of
sufficient air movement necessary galvanized sheet steel with low Delivery format:
to maintain occupant comfort even casing leakage rate. ● The VAV or CAV terminal will be
in extreme load variations.This supplied as a single mounting
specific characteristic means that Insulation : assembly.
cold air ‘dumping’ will not occur The rectangular discharge section Optional ordered distribution
and that extremely low primary air is internally insulated . plenum, reheat coil and/or
temperatures can be used, without controls are factory fitted, wired
producing excessive differences Damper : and calibrated. The terminal can
between the supply and the room Damper blade : made of steel , be directly installed and
air temperature. The primary air is sandwich construction with twin commissioned when delivered to
controlled by the patented airflow blades and a neoprene gasket with site.
®
sensor type Flo-Cross . The low leakage .
Induction VAV terminals can be Damper shaft : aluminium,Φ ● Controls location and hot water
used for supply air applications in 12mm with self lubricating nylon or electric connections are as
new or refurbishment projects. bearings. standard fitted on the right hand
The terminals can optionally be side of the terminal when looking
supplied with a distribution plenum Flo-Cross ®: in the direction of the airflow .
and a built-in hot water or electric Extruded aluminium construction On request, the terminal can be
reheat coil. with nylon core and feet . delivered with connections on
the left hand side.
Features: Distribution plenum :
● Pressure independent control
Made of galvanised sheet steel ● When terminals are ordered
functions . with 13 mm internal isolation. with controls, these will be
● Volume control range 100% to
Plenum with standard rectangular factory fitted, wired and
10% . or multiple (4 x circular) outlet calibrated upon request .
● Low pressure loss over the
construction. Optional 1,2,3 or 6
terminal . circular outlets are possible .
● Factory fitted distribution Outlet spigots are made of
plenum with built - in hot water galvanised steel and optionally
or electric reheat coil . can be provided with volume
● Oval shaped damper blade for
control dampers .
linear control characteristics .
● Low leakage damper, less than
Reheat coil :
1% of Vnom at 750 Pa . Choice of 1, 2 or 4-row hot water
● Low noise level .
reheat coil or electric reheat coil
● Suitable for all control functions
(230VAC/1-phase or 400VAC/3-
(VAV, CAV, shut-off, etc.) To phase).
maximise system energy savings.

2
Changes w/o notice or obligation
Rev 100426
Induction VAV Technical data
air volume control terminals Type (NV.....)

N V OJ

Specify as: Installation Instructions : 5 . Additional manual volume


control
Example: The HC Barcol-Air VAV terminals dampers ( VCD ' s ) before the
Supply and install, induction shall be installed using at least unit inlet should not be used.
variable air volume terminals with two support brackets, with anti- 6 . All connections shall be
distribution plenum with 4 circular vibration rubber under the thermally isolated .
outlets, constructed from terminal. Each of these brackets 7 . Pressure sensing tubes of
galvanized sheet steel. The VAV shall be fixed with two threaded FloCross airflow sensor shall
terminals shall have a special ‘jet- rods to the ceiling slab above . not be " kinked " or otherwise
tronic’ low leakage damper blade obstructed by the external
and an aluminium damper shaft The installation method : duct insulation .
with self lubricating Nylon 1 . Shall prevent the body of the
bearings. VAV terminal from high See drawing below.
mechanical tension, which
A centre averaging airflow sensor could damage the construction
with at least 2 x 12 test points and and performance of the
amplified signal air flow sensor, terminal .
®
type Flo-Cross shall control the 2 . Shall prevent torsion on the
airflow with an accuracy not less induction VAV terminals, which
than 2.5%. The terminals shall be could cause malfunction of the
supplied with 1-row hot water damper blades.
reheat coil. 3 . Provides some flexibility to the
final location of the VAV
The controller shall be I / A Series, terminals .
DDC controller : 4 . Use at least one diameter
LonMark compatible, type MNL- straight duct length before the
V2RVx VAV inlet .
or suspension bracket for duct ( with anti-vibration
rubber against vibration and to avoid thermal bridge)
BACnet, type MNB-V2.
‘Slip & Drive connections’
Controls must be factory fitted,
wired and calibrated according to
the following requirements:

Miximum air volume 250 l/s


Minimum air volume 60 l/s
Minimum air volume 120 l/s (in
case of reheat)
Terminal size 200 mm
Max. discharge sound index
<NC25 (@250Pa Δp) OP TIONAL MOUNTING S TANDARD MOUNTING
Max. radiated sound index < NC25
(@250Pa Δp)

Ordering example : type - model - anti-vibration rubber inlay


mounting rail M8
handing= NVOJAOB - 200R ring M8
hexagonal nut M8
Manufacturer: HC Barcol-Air threaded end M8
optional: 4x duct fixing hook contact
HC Barcol-Air for further details

3
Changes w/o notice or obligation
Rev 100426
Induction VAV Model overview
air volume control terminals Type (NV.....)

Type N V OA . OB Type N V OC . OB

Kv values

Changes w/o notice or obligation


Rev 100426
Induction VAV Model overview
air volume control terminals Type (NV.....)

Type NVOG . OB Type NVOJ . OB

Type NVON . OB Type NVOQ . OB

For dimensions see page 4

Changes w/o notice or obligation


Rev 100426
Induction VAV Type (NVOAOOB)
air volume control terminals
Sound data Δp = 150 Pa
data refering to discharge sound radiated sound
inlet spigot
Lp values Lp values

air volume

1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Talbe 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct. Model
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated
discharge sound and case radiated sound. Figures by “- -”.
less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections,
table 1 for downstream ductwork including a please contatct our technical staff.
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined
with the assumptions as mentioned in table 1 for Discharge (dB)
ceiling plenum and suspended ceiling absorption. Radiated (dB)

6
Changes w/o notice or obligation
Rev 100426
Induction VAV Type (NVOAOOB)
air volume control terminals
Sound data Δp = 250 Pa
data refering to discharge sound radiated sound
inlet spigot
Lp values Lp values

air volume

1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Talbe 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct. Model
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated
discharge sound and case radiated sound. Figures by “- -”.
less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections,
table 1 for downstream ductwork including a please contatct our technical staff.
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined
with the assumptions as mentioned in table 1 for Discharge (dB)
ceiling plenum and suspended ceiling absorption. Radiated (dB)

7
Changes w/o notice or obligation
Rev 100426
Induction VAV Type (NVOCOOB)
air volume control terminals
Sound data Δp = 150 Pa
data refering to discharge sound radiated sound
inlet spigot
Lp values Lp values

air volume

1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Talbe 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct.
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated
discharge sound and case radiated sound. Figures by “- -”.
less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections,
table 1 for downstream ductwork including a please contatct our technical staff.
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined
with the assumptions as mentioned in table 1 for Discharge (dB)
ceiling plenum and suspended ceiling absorption. Radiated (dB)

8
Changes w/o notice or obligation
Rev 100426
Induction VAV Type (NVOCOOB)
air volume control terminals
Sound data Δp = 250 Pa
data refering to discharge sound radiated sound
inlet spigot
Lp values Lp values

air volume

1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Talbe 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct.
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated
discharge sound and case radiated sound. Figures by “- -”.
less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections,
table 1 for downstream ductwork including a please contatct our technical staff.
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined
with the assumptions as mentioned in table 1 for Discharge (dB)
ceiling plenum and suspended ceiling absorption. Radiated (dB)

9
Changes w/o notice or obligation
Rev 100426
Induction VAV Type NVOG . OB NVON . OB
air volume control terminals
Sound data Δp = 150 Pa
data refering to discharge sound radiated sound
inlet spigot
Lp values Lp values

air volume

1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Talbe 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct.
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated
discharge sound and case radiated sound. Figures by “- -”.
less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections,
table 1 for downstream ductwork including a please contatct our technical staff.
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined
with the assumptions as mentioned in table 1 for Discharge (dB)
ceiling plenum and suspended ceiling absorption. Radiated (dB)

10
Changes w/o notice or obligation
Rev 100426
Induction VAV Type NVOG . OB NVON . OB
air volume control terminals
Sound data Δp = 250 Pa
data refering to discharge sound radiated sound
inlet spigot
Lp values Lp values

air volume

1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Talbe 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct.
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated
discharge sound and case radiated sound. Figures by “- -”.
less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections,
table 1 for downstream ductwork including a please contatct our technical staff.
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined
with the assumptions as mentioned in table 1 for Discharge (dB)
ceiling plenum and suspended ceiling absorption. Radiated (dB)

11
Changes w/o notice or obligation
Rev 100426
Induction VAV T ype NVOJ . OB NVOQ . OB
air volume control terminals
Sound data Δp = 150 Pa
data refering to discharge sound radiated sound
inlet spigot
Lp values Lp values

air volume

1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Talbe 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct.
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated
discharge sound and case radiated sound. Figures by “- -”.
less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections,
table 1 for downstream ductwork including a please contatct our technical staff.
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined
with the assumptions as mentioned in table 1 for Discharge (dB)
ceiling plenum and suspended ceiling absorption. Radiated (dB)

12
Changes w/o notice or obligation
Rev 100426
Induction VAV Type NVOJ . OB NVOQ . OB
air volume control terminals
Sound data Δp = 250 Pa
data refering to discharge sound radiated sound
inlet spigot
Lp values Lp values

air volume

1. Sound data is determined in a reverberation 5. Lp values are including a room absorption of 10 Talbe 2 : Insertion Loss
room at an independent sound laboratory, dB/Oct.
according to ISO3741 and ISO 5135 standards. 6. DB(A), NC and NR index figures are sound
2. Lw in dB/Oct.(re 1pW) are sound power levels for pressure levels. Figures less than 20 are indicated
discharge sound and case radiated sound. Figures by “- -”.
less than 17 dB are indicated by “-”. 7. Δps is static pressure drop across VAV air
3. The discharge sound pressure levels are volume control terminal with damper fully open.
determined with the assumptions as mentioned in 8. For non standard applications and/or selections,
table 1 for downstream ductwork including a please contatct our technical staff.
diffuser with insulated plenum box. Table 1 : Assumptions for additional attenuation
4. The radiated sound pressure levels are determined
with the assumptions as mentioned in table 1 for Discharge (dB)
ceiling plenum and suspended ceiling absorption. Radiated (dB)

13
Changes w/o notice or obligation
Rev 100426