Power Boiler CFB
Description for
I N S T R. C O N T R O L D I A G R A M S
2 2005 - 05 - 10 E. Karru
Muut. Pvm Laatinut Pvm Tarkastanut Pvm Hyväksynyt
Rev. Date Prepared by Date Reviewed by Date Approved by
KLY-1 1997-05 P:\582-RAPP-PB3\int\Kayttoonotto\koulutus\Training Manuals\Folder 1\3.1 Control
descriptions.doc
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
2.1 Tank level is measured with three DP-transmitters. For the level control
operator can select a signal from one separate transmitter or average value
of all the correct transmitters.
Normally the level control should be selected to the average signal. If a signal
fault occurs, the selection is changed anyway automatically to the average
signal of the correct transmitters.
Feedwater tank level is controlled with make-up water valve. When level
limit L>max is valid, the make-up water valve closes.
2.2 There is a own level control for overflow valve. Level measurement 0..100 %
is calculated part of tank's upper side. Set-point should be 50 % and gain
(P-parameter) so calibrated that output is 100 % when measurement is 100 %
and output is 0 % when the measurement is 0 %.
2.3 Level limits L>min are for feedwater pump interlocks and level limits L<max
are for tank filling interlocks.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
5.1 The drum level is measured with three DP-transmitters. Level signals are
connected to the BMS-cabinet for interlocks L>min and L<max.
For the level control (DCS), operator can select pressure compensated signal
from one separate transmitter or average value of all the correct transmitters.
Normally the level control should be selected to the average signal. If a signal
fault occurs, the selection is changed anyway automatically to the average
signal of the correct transmitters.
5.2 Feedwater flow control is set to Remote & Auto by operator and the level
control gives set-point to the flow control. The level control can be at Man or
Auto mode, operator's choice.
Steam flow is connected to the level controller's output, it means that the
feedwater flow control will follow the steam flow and the level control has a
correction influence. With this connection, steam flow variations will be noted
in the feedwater flow and the level in the drum should be more stable.
5.3 There is a valve selection for operator and own hand-stations for both valves.
At the same time only one valve can be selected to the control.
"new" selected valve will get exactly same signal as the "old" valve. When the
selection is done, the "old" valve closes (shut-off valve not close) at the same
time when the "new" valve will continue with control. Of course the feedwater
flow will decrease temporary but the flow will rise to normal before boiler trip
from low drum level.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
5.4 When the level increases to the interlock limit L>max, the feedwater valve is
interlocked to close after 10s delay. FIC's control mode does not change with
the interlock, because the level control must be active when the level decreases
below the interlock limit (time delay to the boiler trip, see interlocking dwg).
Average signal is connected to the drum level compensation and steam temp.
control.
7.1 After the first spray cambers (1, 2) there is temperature loops with Local
and Remote selections, when cascade (Remote) is selected:
- remote set-point is coming from the temperature loop after sec. superheating
- there is a max-selector so, that the set-point is limited to the minimum heating
(saturated steam temperature is based on the drum pressure + 20 C)
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
7.3 After the second spray cambers (3, 4) there is temperature loops with Local
and Remote selections, when cascade (Remote) is selected:
- remote set-point is coming from the temperature loop after tert. superheating
7.5 Parameters will slide according to the steam flow, control action will be faster
when the steam flow rises.
8.1 Main steam valve is interlocked to close if opening permission from by-pass
valve is not o.k or drum level L>max has been valid over 10 min
8.2 Steam drum drain valve is interlocked to close if opening permission from
on-off valve is not o.k or drum pressure P>max is valid.
Start-up steam flow is estimated with a curve, based on the valve position
and the steam pressure.
There is a damping for the sootblowing steam flow, because the flow is
based on the sootblower's start/stop operation.
The total steam flow is connected to the other loops as shown in the
diagram.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
10.1 Main steam pressure control gives set-point values to all solid fuel feeding
motors via ratio set bark / coal.
10.2 There is a common M/A-selection for bark feeding and a common M/A-
selection for coal feeding.
This means that with a special situation whole bark feeding or whole coal
feeding can be controlled manually with one setting.
This means that with a special situation each bark feeding group can be
controlled separately with own manual setting.
This means that with a special situation each coal feeding group can be
controlled separately with own manual setting.
10.5 Set-point for solid fuel feeding 1 = sum of Bark 1 and Coal 1
10.6 Set-point for solid fuel feeding 2 = sum of Bark 2 and Coal 2
10.7 Set-point for solid fuel feeding 3 = sum of Bark 3 and Coal 3 & 4
10.8 Normally when all selections are at Auto-mode, the speed of all motors
will follow the output from main steam pressure control (PIC eitherAuto
or Man-mode).
For the pressure control, operator can select one separate transmitter or
average value of all the correct transmitters.
11.2 Main steam pressure is kept in a suitable value with the solid fuel amount.
1. The output can not increase if any of the following conditions is valid
- main steam flow F>max
- flue gas fan 1 speed >95 %
- flue gas fan 2 speed >95 %
fuel group
4. The control can be selected to Auto-mode when inside any feeding group
all M/A-selections are selected to Auto-mode and last motor in same group
is running = there is real possibility for pressure control
5. The control output will increase 15 % with failure stop of any fuel conveyor
1..3 when any fuel conveyor 1..3 is still running
11.3 There is a hand-station for BARK ratio set adjustment. With a factor 1,0 the
bark part will be 100 % and Coal part 0 %. With the factor <1,0 the bark part
will decrease and the coal part will increase so that with the factor 0,0 the bark
part is 0 % and the coal part is 100 %.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
12.1 Each feeding group has a own ratio set correction possibility and a hand-station
with M/A-selection.
The feeding set-point must be interlocked to the last feeding motor's run-status
because otherwise there can be set-point commands for common motors
without real supply.
When the last feeding motor stops, the M/A-station is set to Man-mode (pulse)
and so the last feeding set-point stays valid for corresponding running motors U U
so long that conveyors/screws are empty (delay eg 40 s). After that delay, the
>> M/A-station set-point is set to 0 % by a pulse. So new feeding start will happen
with Man-mode and minimum speed. Or before new start, operator can set
controls to Auto-mode if necessary.
Also signal to air demand will follow the corresponding feeding set-point.
When corresponding last feeding motor is running, the speed set-point is given at
the same time all motors inside same feeding group, by the main steam pressure
control or by operator (Man-mode).
12.2 The Coal Feeding 3 and 4 are limited so much as the capacity of the mixing
screw 3 exceed 420 m3/h.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
>> Each feeding group has a min-selector for Total Power/Solid Fuel/Combustion
Air limiting.
When the limiting has been valid 10 s, there is a status and alarm indication
for operator and the main steam pressure control is forced to Man-mode with
output limiting so long as the power or air limiting is valid (see 11.2.3).
Total power limiting is valid when all fans are running. When one or more fan(s)
is stopped (by a failure or by operator), the total power limiting is replaced by
solid fuel limiting (see point 14.5).
When the solid fuel limiting is activated, and in trip moment the calculated solid
fuel power is higher than limiting value, so at the same time all hand-stations
of corresponding feeding groups are set to Man-mode (1) by a pulse and "old"
output value is corrected with correction factor and the new (corrected) value is
set to hand-station's set-point.
With correction, the solid fuel feeding volume decreases without any delay with
same factor in every running feeding groups.
(1) Some hand-stations can be already at Man-mode when solid fuel limiting
is activated.
Because the hand-stations of all feeding groups are set to Man-mode, the main
steam pressure control is also set to Man-mode because control possibility is
lost (see page 11.2.4).
13.1 TOTAL power calculation and monitoring is based on the main steam flow
including so oil power and solid fuel power.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
Solid fuel power (bark + coal) = total power minus oil power
There is also %-display for BARK and COAL parts from sum of both powers.
>> 14.1 There is a fixed total power value for a "blind" controller. Normally (all fans
running), when the total power is lower than the fixed value, the output of
controller is 100 % and not any solid fuel feeding limiting.
If the total power is higher than the fixed value, the output will decrease and
the limiting of solid fuel feeding will start from highest group. The limiting will
continue so long that the total power decreases to allowed level.
14.2 There is a fixed combustion air minimum value for a "blind" controller.
Normally when the real combustion air flow is higher than remote set-point sum
of combustion air flow controls, the output of controller is 100 % and not any
solid fuel limiting.
If the balance between real air flow/remote set-points is lower than the fixed
value, the output will decrease and the limiting of solid fuel feeding will start
from highest group. Because combustion air curves are based on the solid fuel
amount, the limiting will continue so long that there is allowed balance between
the real combustion air flow and remote set-points.
There are calculated %-part displays for each air flow compared to total fresh
air flow.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
>> 14.3 Oil burning power is limited when only one sec. air fan is running (14.6).
When the solid fuel limiting is activated, the total power limiting is replaced
by a "blind" solid fuel controller. Fixed set-points 370 MW or 210 MW are
based to the status of running fans (see 14.5).
Reset to normal total power monitoring happens when all the fans are again
running.
If the solid fuel power is higher than the corresponding fixed value, the output
will decrease and the limiting of solid fuel feeding will start from highest group.
The limiting will continue so long that the solid fuel power decreases to allowed
level.
Normally when all of the fans are running, the solid fuel limiting is reseted and
the total power monitoring is activated (pulse).
A When one flue gas fan stops or one primary air fan stops, the solid fuel
limiting 210 MW (40 %) is activated by a pulse as following
- if the solid fuel power in trip moment is higher than that 210 MW
- hand-stations of every solid fuel feeding groups are set to Man-
mode and set-points are corrected as point 12.4
(= solid fuel feeding volume decreases without any delay)
Correction factor = 210 MW per actual solid fuel power
- after 1 min delay (calculated main steam power is decreased),
the 210 MW set-point is given to the "blind" solid fuel controller
and at the same time the total power monitoring is replaced by
solid fuel monitoring
- if the solid fuel power in trip moment is lower than that 210 MW
- only 210 MW set-point is given to "blind" solid fuel controller
and at the same time the total power monitoring is replaced by
solid fuel monitoring
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
B When one sec. air fan stops but both flue gas fans are running and both
primary air fans are running
Similar principle as above but solid fuel limiting value is 370 MW (70 %).
C Oil power is limited to 150 MW when only one sec.air fan is running.
Normally when both sec. air fans are running, the measurement is zero and
output is 100 %.
When only one sec. air fan is running, measurement is released to calculated
oil power. If the oil power is higher than the fixed value, the output will decrease
so long that oil flow (power) to running burners decreases to allowed level.
Limiting is reseted when both sec. air fans are again running.
There is a own air curve for bark and coal. Primary air demand is a sum of
both curves.
For operator there is a hand-station for ratio set correction and a hand-station
for balance setting between LEFT and rigt primary air flow.
Balance setting; with a correction factor 1,0 same signal is given to both air
flow controls. If the correction factor is <1,0 signal to the LEFT air flow control
will decrease and signal to the RIGHT air flow control will increase. Vice versa
when the factor is >1,0.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
There is a own air curve for bark and coal. Total air demand is a sum of
both curves
There is a hand station for total air correction by operator. The total air demand
is also corrected by oxygen control.
There is a own air curve for bark and coal. Lower sec. air demand is a sum of
both curves.
For operator there is a hand-station for ratio set correction and a hand-station
for balance setting between FRONT and rear lower sec. air flow.
Balance setting; with a correction factor 1,0 same signal is given to both air
flow controls. If the correction factor is <1,0 signal to the FRONT air flow control
will decrease and signal to the REAR air flow control will increase. Vice versa
when the factor is >1,0.
Upper secondary air flow control's remote set-point is a signal from total air
demand minus real primary air and real lower sec. air.
For operator there is a hand-station for balance setting between RIGHT (must)
and left (rest) upper sec. air flow. Balance setting; with a correction factor 1,0
the right flow will be 100 % and the left flow will be 0 %. With the factor <1,0 the
right flow will decrease and the left flow will increase.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
Cooling water on-off valve opens (Auto-mode) and stay open so long than
temperature from tank is T>max.
>>
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
Primary air pressure is kept in a suitable value with this control loop.
Primary air temperature is kept in a suitable value with this control loop.
Steam valve closes when both primary air fans are stopped.
When both fans are started, flow control damper's interlocks are released
after starting delay and the flow controls are set to Remote & Auto-mode
automatically by a pulse.
The remote set-points are coming from the primary air curve via balance
setting left/right.
Boiler purge:
- dampers close, FIC to Man-mode (Local) and output to 0 %
- after the purge, FIC are set again to Remote & Auto (pulse) and FIC are
released to normal control
Air flow limits F>min must be valid for the fluidized bed interlock and burners.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
Secondary air pressure is kept in a suitable value with this control loop.
When any fan is started, the flow control is set to Remote & Auto-mode
automatically by a pulse.
The remote set-point is coming from the lower sec. air curve via balance
setting front/rear.
Boiler purge:
- damper closes, FIC to Man-mode (Local) and output to 0 %
- after the purge, FIC is set again to Remote & Auto (pulse) and FIC is
released to normal control
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
When any fan is started, the flow control is set to Remote & Auto-mode
automatically by a pulse.
The remote set-point is coming from the upper sec. air calculation via coal
amount correction.
Boiler purge:
- damper is set to purge position, FIC to Man-mode (Local) and output to
same value as purge position
- after the purge, FIC is set again to Remote & Auto (pulse) and FIC is
released to normal control
The flow limit F>min must be valid for the burner interlocks.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
When the burner stops, FIC is set to the Man-mode and output to stop
value by pulse (= burner is stopped but control is free for operator).
Boiler purge:
- damper is set to the purge position, FIC to Man-mode and output to
the purge value
- after the purge, FIC stays at Man-mode and damper is set back to the
stop value by pulse
For the preesure control, operator can select signal from one separate
transmitter or average value of all the correct transmitters.
When the fan stops, the corresponding speed control signal is set to 0 %.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
When a measurement loop fault occurs, alarm and the selection is changed
automatically to the average value of correct transmitters.
Flue gas oxygen control gives a correction to the total air demand signal.
Flue gas CO<max must be valid for the Electro Static Precipitators (ESP).
Fluo seal air pressure is kept in a suitable value with this control loop.
Fluo seal air flow is kept in a suitable value with this control loop.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
Level limits and output limit of control are for pump control.
With the bed cooling, flue gas recirculation flow is controlled by a curve.
Operator can set the desired reference temperature and the curve is based
on the difference between operator's value and the average of 3 max value.
Bed height (solid bed part and full bed) is a calculated value as shown in
the diagram.
Pressure limit P>min is for on-off damper and the control as above.
When the fan stops, the control is interlocked to Man-mode and output to 0 %
>> Remote set-point is coming from recirculation gas curve via balance setting
left/right.
When the fan stops, the both controls are interlocked to Man-mode and
output to 10 %
The speed set-point is also corrected by the level control under the silo.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
Each metering screw has a own hand-station for ratio set adjustment and
a hand-station with M/A-selection.
Failure operations:
U
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
When the metering screw 3 stops, the level control i set to Man-mode and
output to 50 % (= 1,0 not any correction) by a pulse. The level control will
be selected to Auto-mode again by operator.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
Each metering screw has a own hand-station for ratio set adjustment and
a hand-station with M/A-selection.
Failure operations:
U
When the metering screw 6 stops, the level control i set to Man-mode and
output to 50 % (= 1,0 not any correction) by a pulse. The level control will
be selected to Auto-mode again by operator.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
Each metering screw has a own hand-station for ratio set adjustment and
a hand-station with M/A-selection.
Failure operations:
U
When the metering screw 9 stops, the level control i set to Man-mode and
output to 50 % (= 1,0 not any correction) by a pulse. The level control will
be selected to Auto-mode again by operator.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
>> The heavy oil temperature is kept in a suitable value with this control loop,
either by steam heaters or electric heater, according to operator's selection.
>> The valves close and signal to electric heater is set to 0 % when both oil pumps
are stopped.
The heavy oil pressure is kept in a suitable value with this control loop.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
The diesel oil pressure is kept in a suitable value with this control loop.
Heavy oil temperature limit T>min must be valid for burners when
heavy oil is selected.
Pressure air, MP-steam and instr. air pressure limits P>min must be valid
for burners.
Ign. gas pressure limits P>min and P<max must be valid for igniters
and starting of burners.
70.1 Oil pressure is kept in a suitable value with this control loop.
Oil pressure limit P>min and P<max must be valid for burner interlock.
To avoid a pressure drop with starting, valve position will increase for
a certain time (pulse) when heavy oil is selected.
70.2 There is one special situation with diesel oil selection and burner starting:
- return oil valve closes when diesel oil is selected
- before starting, there must be oil pressure P>min and P<max
- when start happens with diesel oil:
- operator must set pressure control to Man-mode and oil valve to
ignition position, eg. 40 % open
- when the burner is running, operator can set the pressure control
to desired control mode
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
70.3 When the return oil valve is closed, oil flow signal is given to
- air flow control
- oil flow calculation
>> 70.4 If the oil limiting is on, and oil power of running burners will exceed the fixed
value, the output of "blind" controller will decrease the oil valve positions
(from highest value first) so long that sum of oil power is in allowed level.
When the valve position is limited, status information to operator and the oil
pressure control is forced to Man-mode. When the limiting is off, the pressure
control is released to same control mode as before limiting.
The temp. limit T<max must be valid for bottom ash removal conditions.
>> Sum of speed set-points is given to speed control of bottom ash drag conveyor.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
In the common cooling water line is a flow limit F>min for monitoring
(alarm only) of the bottom ash cooling heat exchanger.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
>> The pressure limit P>min must be valid for starting of limestone
heater burner.
>> Temp. control will operate according to the burner status as following:
- after 5s from burner stop, the control is forced to Man-mode and output
is set to ignition value, eg. 40 % (waiting for start)
- after 10s delay when the burner is running, the control is set to Auto-mode
by a pulse and the control is free for operator, at Auto-mode the control output
is minimum limited so that the burner flame does not go out.
This document is the exclusive intellectual property of Kvaerner Power Oy and is furnished for the sole purpose of operating and maintaining of the specific project, and re-use of the document for any other project or
purpose is prohibited. The document or the information shall not be reproduced or copied, or disclosed to a third party without prior written consent of Kvaerner Power Oy.
Limestone feeding is based on the coal amount. For operator there is:
- hand-station with A/M-selection
- hand-station for ratio set correction.
- SO2 control with limited correction influence
When the M/A-hand station is selected to Auto-mode; the screw speed will
follow the coal amount and corrected with SO2-control (Auto-mode) and
corrected with ratio set by operator.
The M/A-hand station in Man-mode; operator can set desired screw speed.