Sie sind auf Seite 1von 5

Dynamic Behavior Analysis of Hu-Liao HVDC and

AC Parallel Transmission System

Peng Ye Yuqiu Sui Yinghua Yuan Xiaoming Li Jiaqi Tao


Northeast Electric Power Research Institute Co. Ltd Northeast China Grid Company Limited
Shenyang, China Shenyang, China

Abstract—In this paper, dynamic behavior analysis was were demonstrated with simulation examples. Results show
focused on the Hu-Liao HVDC and AC parallel transmission that HVDC schemes in parallel operation with AC transmission
system. The Hu-Liao HVDC project was introduced; Simulation are prone to both transient swing angle and voltage instabilities.
method and mathematic models of AC and DC systems were And the risks of instability will increase during disturbances. In
studied as well as corresponding regulators and controllers. The reference [7-9], research on advance control strategy for a
dynamic performance and the interaction between AC and DC
systems during serious disturbance were researched by detail
HVDC scheme in parallel operation with AC systems was
simulation. Comparison was also made under different operation discussed. By these unconventional control strategies, the
schemes. The research will bring important and significant HVDC scheme can actively participate in the instantaneous
reference for further operation and stability control of Hu-Liao rescheduling of power and improve the dynamic performance
HVDC and AC system. of power network. In reference [10-11], a real AC and DC
parallel transmission system in South China was studied from
Keywords-HVDC;transient stability;control strategy;digital
operation and control aspects.
simulation
The HuLunbeier-Liaoning (abbreviated as Hu-Liao
I. INTRODUCTION hereinafter) HVDC project was the first AC/DC parallel
Since the first High Voltage Direct Current transmission transmission system in North China, which was employed to
project was commissioned into commercial operation in 1954, transfer electricity from Hulunbeier energy center to Liaoning
HVDC has been developed so rapidly that it has been widely province. In particular, in the sending side of HVDC,
applied in such fields as large power transmission over long Hulunbeier has a very weak network. As a result, the stability
distance, interconnecting two asynchronous systems, power problem in operation is very critical. It is a challenge work for
transmission through submarine cables for supplying power to the operator to keep such a special AC/DC parallel
islands and the like. Compared with three-phase AC transmission system operating in an economic and secure state.
transmission systems, conventional HVDC is superior in the
In this paper, dynamic behavior analysis was focused on the
following aspects[1]:Firstly, HVDC need less cost in
Hu-Liao HVDC and AC parallel transmission system. The
constructing and operating; Secondly, it needs not keep
Hu-Liao HVDC project was introduced; Simulation method
operating synchronously between the two AC systems; Thirdly,
and mathematic models of AC and DC systems were studied as
it is easy to control and adjust power flow, etc.
well as corresponding regulators and controllers. The dynamic
Among the many HVDC long transmission schemes performance and the interaction between AC and DC systems
around the world, very few operate in parallel to AC during serious disturbance were researched by detail simulation.
transmission of comparable capacity. Problems for parallel Comparison was also made under different operation schemes.
AC/DC operation primarily resolve around the coordination The research will bring important and significant reference for
between the two power flows and how each system reacts to further operation and stability control of Hu-Liao HVDC and
any disturbance [2].It is well known that AC transmission AC system.
systems have the inherent means to reschedule their power
flows and to provide timely and sufficient synchronizing torque II. HU-LIAO HVDC AND AC PARALLEL SYSTEM
to secure such flows following disturbances such as AC faults, Northeast China Electric Power Network System consists
load rejection or generator tripping, etc. How a HVDC in of four provincial networks, Liaoning, Jilin, Heilongjiang and
parallel to AC system reacts in those situations has always been East of Inner Mongolia. These networks have been linked with
a central question, particularly for planning and daily operation 500kV transmission lines. And Liaoning electric network is
of such a complex scheme. In reference [3-6], the interaction connected with Huabei network by back-to-back HVDC links
action between AC and DC parallel transmission system were with a rated capacity of 1500MW. Fig.1 shows the schematic
studied, the theory and operation rules of such power system of Hu-Liao HVDC and AC parallel transmission system.

This paper is supported by key project of State Grid Cooperation of China


Ye Peng is with Shenyang University of Technology, Now he is doing his
postdoctor work in Northeast China Grid Company

978-1-4244-4813-5/10/$25.00 ©2010 IEEE


capability. Up to now, three new power plants, Yimin 3,
Hulunbeier Energy
(2×60) Hulunber Energy and Ewenke, are set up. The electric power
capacity is 3600MW and they are mainly transferred to
Liaoning province by Hu-Liao HVDC system.
Ewenke
Bayantuohai
(2×60) There are disconnecting switches between the buses of
Heilongjiang network Yimin 1, 2 and Yimin 3 power plants. When they are closed,
Yimin 1, 2 Hu-Liao HVDC and AC system are operating in parallel. There
(2×50, 2×60) TCSC is power exchanging through AC and DC system. Generally,
Fengtun
when AC and DC system is operated in parallel, the fault
Yimin
Yimin 3 occurred in either AC or DC system would lead to
(2×60)
instantaneous or permanent power imbalance in power system,
and quantity of power will shift through AC and DC system,
which would be a great impact to transient stability. It is a
Jilin network challenge for system operation, especially due to such a weak
delivering side.
Hu-Liao HVDC
III. MATHEMATIC MODELS AND CRITERIAN IN SIMULATION
The electromechanical transient simulation of this AC and
DC hybrid system was made through PSASP. Northeast
Huabei network Mujia electric power network data include about 1500 buses, 330
generators and two groups of DC lines. Only 500kV and
Gaoling
220kV voltage network are considered in calculation. As
PSASP offered adequate mathematics models for each type of
Liaoning network electric elements, a majority of them are defined by PSASP
Jiangjiaying
according to the require of the simulation. Individuals are
developed through user program interface such as DC and
TCSC controllers. The details are as follows:
Fig.1 schematic of Hu-Liao HVDC and AC parallel transmission system
A. Models For AC System
Hulunbeier is rich in coal, large scale power plants are
For most of generators, five-order model is adopted, in
under constructing. Liaoning province is a rapid developing
which the variations of Eq˝, Ed˝ and Eq΄ are considered. They
province in economic but much lack of energy. So based on the
are fit for detail simulation of salient pole synchronous
mutual interest and the idea of optimizing resources, Hu-Liao
generators. As for the individual small hydroelectric equipment,
HVDC project is put into operation.
two-order model is adopted, in which it is approximately hold
Hu-Liao HVDC transmission is a bipolar 12-pulse HVDC that Eq΄ could keep constant. Most of wind turbines are
transmission system with rated DC voltage ±500kV, rated modeled as doubly-fed direct-drive wind power generators.
power 3000MW, rated current 2500A. Overhead lines have a The models of the corresponding regulators such as excitation
length of 908km long. Yimin converter station locates at east system, speed control system and PSS, are selected and defined
of Inner Mongolia, which is 10km away from Yimin power in the software according to the practical case.
plants. It acts normally as a rectifier and its AC side rated For system load, it is described as combination of fifty
voltage is 500kV. Mujia converter station is in the center of percent constant impedance and fifty percent induction motor
Liaoning province and connected with Anshan 500kV station during dynamic simulation. Three-order model of induction
with two 21km lines. It acts principally as an inverter and its motor is used here to simulate the dynamic features of loads.
AC side rated voltage is also 500kV. The Hu-Liao HVDC The parameter of stator leakage reactance is selected as 0.18pu.
transmission system operation modes include bipolar mode,
monopolar ground return mode, monopolar metallic return The electric distance is relatively near between TCSC and
model and monopolar parallel line ground return model. The DC lines. The Yi-Feng TCSC is composed of two parts: fixed
HVDC system can be operated both on rated voltage and on part and variable part. The fixed part occupies thirty percent of
lower voltage. The Hu-Liao HVDC transmission normally the total transmission line capacity and the variable part
operates in P mode (constant power control mode). I mode occupies fifteen percent. In the dynamic process, the TCSC
(constant current control mode) can be used as a back-up acts as follows: The fixed part is sure not to be bypassed when
mode. fault occurred in transmission lines; The variable part is to be
bypassed when three or two phase fault occurred in the line;
As mentioned above, large scale power plants are under while when single phase fault occurred, the fault phase is
construction in Hulunbeier. Before Hu-Liao HVDC bypassed and the forced compensation will take action in
implemented, there are two power plants, namely: Yimin 1 and normal phase; The forced compensation will also take action
2, with altogether capacity of 2200MW. Electric power is when fault occurred in neighbor line. The bypass time of
transferred to the west of Heilongjiang province through two TCSC is 0.05s after fault occurring. The control logic of the
500kV lines. At Fengtun station, Thyristor Controlled Series variable part is shown in Fig.2.Where, P and v are measured
Compensation (TCSC) is installed to improve the transfer power and voltage, which is used for oscillation control; ttrigger
is the signal of beginning time and Tforced is the continuous time correspond to the rectifier ignition angle and inverter
of the action. The maximum compensation capacity is extinction angle.
forty-five percent.
Vdr
Id Vdi
PL0 _
cosβ
PL + cosα

Oscillation Control
v controller logic

+ Idorder Idorder-Im
_
v0 + +
Id ΔI Id ΔI
_ ∑ Current Current
xTCSC xTCSC controller _ ∑
Inertia controller
∑ max ∑
And
limter Imod
xTCSC Rdc
ttrigger ttrigger
Id _
Transient protection Bypass ∑ +
Tfored stability controllor Tfored controllor Vdorder ΔV
controllor + ∑ voltage
Current limiter _ controller

Fig.2 control scheme of TCSC Vdi +


γ0
B. Models for DC System Idorder +
The DC model used in steady state calculation is shown Vd γ Δγ
P/V ∑ γ
Pmod _
as the following equation, in which approximation was made controller
in reactive power calculation and in this way the equation
form was much simplified. Pdorder
⎧ Pac = U d I d
⎪ Fig.3 control scheme of DC system
⎨ Qac = Pac tan ϕ (1)
⎪cos ϕ ≈ U / U When situation needed, additional control will be joined
⎩ d d0 through Pmod or Imod to fully exert the DC features of fast
Where, Ud0 is the converter transformer no-load DC voltage, power control and improve the dynamic performance of AC
Pac and Qac is the active and reactive power from AC to DC. Id system.
and Ud is the current and voltage of DC line.
C. Criterian forTransient Stabality
In normal operation, HVDC links required to transmit a According to power system stability guideline of China, to
scheduled power. In such an application, the master control keep transient stability, the following conditions must be
layer receives the power schedule, modifies by auxiliary power satisfied at the same time:
control and then converts the power signal into the coordinated
bi-pole current order commensurate with the DC voltage. Pole Angle stability: after disturbance, any rotor angle between
control is the core of HVDC control and activates the two generators in the same AC system takes on a damping
appropriate controller of the rectifier and inverter station oscillation.
according to the state of AC/DC systems. Then it produces the
Voltage stability: the continuous time of low voltage under
firing angle for both rectifier and inverter stations. The control
0.75pu is within 1s. The voltage of pivot buses is above 0.8pu
scheme is shown in Fig.3.
when the fault is clear.
Pole control at the rectifier side has a current controller,
Frequency stability: the frequency collapse will not happen
which takes the maximum and minimum current constrains and
with secure measures such as loads shedding and generator
the VDCOL into consideration. The minimum firing angle
tripping. The frequency can restore to the normal level and the
control is embedded implicitly in the current controller by
large unit operation will not be affected.
angle limits. Pole control at the inverter station includes a
voltage controller, a constant current controller and a constant IV. DYNAMIC BEHAVIOR ANALYSIS
extinction angle controller. Current error Im provides a
transition between the current control and voltage control to Transient stability criterion for the studied system requires
facilitate control stabilization. The shift logic of these the system to be stable after clearing of any single fault by
controllers is implemented by: clearing or reclosing it successfully. Amount of simulations
were done on this system. For AC system, the worst condition
U d 0r cosα −U d 0i cosγ occurs when three phase permanent fault happens near Yimin
Id = (2) power plants. For DC system, the worst condition occurs when
d xr + Rd − d xi bipolar blocking happens. Stability measures are necessary for
Where:dxr,dxi are the equivalent resistance of the rectifier most cases.
and inverter. Rd is the resistance of DC line. α and γ
A. Dynamic Behavor when AC Faults
600
The typical case was studied when a permanent three phase 500
DC-3000MW
fault occurred in the exit of 500kV Yi-Feng line. The steady 400
DC-2200MW
state condition is 6 units for DC power sending and DC 300 DC-1800MW

angle
capacity 3000MW. Stability measure is that three unit tripping 200
in Yimin plants and AC/DC separated within 150m. Because 100
the close electric distance with Yimin bus, AC bus voltage of 0
Yimin converter reduced a lot and is close to zero in the fault -100 0 5 10 15 20
instant. As a result, DC voltage brought down along with AC t(s)
voltage till it can not work its way and quitted temporarily. The
misbalance between energy and power of AC system in Yimin Fig.7 rotor angle variation of Yimin unit under different DC power
and Hulunbeier areas was further increased and the instability
of the system became even worse. After one second the fault Table.1, stability measures under different DC power
line is cleared, the AC voltage is recovered. When condition is DC capacity Measures To Keep stability
permitted, DC system restarted and DC power is restored, 3000MW No measures needed
which is much helpful for AC system stability. Voltage, rotor two units tripping in Yimin plants and AC/DC
angle and DC power curves during the disturbance were shown 2200MW separated within 150ms
in Fig.4, Fig.5 and Fig.6. 1800MW
three unit tripping in Yimin plants and AC/DC
separated within 150ms

1.2
1 B. Dynamic Behavor when DC Faults
0.8 When fault occurred in DC line, the bipolar blocking is the
0.6 Fentun most serious one. In this case, mass power shifts to Yi-feng
v(pu)

0.4 Yimin lines and make a great impact on AC system. If DC can restart
0.2 successfully, the oscillation can be appeased and AC system
0 keeps stable; Else, AC system will lose stability without secure
-0.2 0 2 4 6 8 10 control measures.
t(s)

Fig.4 voltage variation of Yimin and Fengtun bus


60
Yimin
80 40
angle

40 Yimin 20
0
angle

0
-40 0 2 4 6 8 10
0 2 4 6 8 10
-80 t(s)
-120
t(s)
Fig.8 rotor angle variation of Yimin unit

Fig.5 rotor angle variation of Yimin unit


30
Id Pd
40 Id Pd 20
I/P(pu)

30
10
I/P(pu)

20
10 0
0 0 2 4 6 8 10
-10
-10 0 2 4 6 8 10
t(s)
t(s)
Fig.9 DC power and current variation
Fig.6 DC power and current variation
In the above simulation, The DC system experiences a
To study the influence of DC power to AC stability, restart failure for the first time and a success start over a
simulation was done under 4 units and different DC power. lowering voltage for the second time. Along with DC restore,
Results were shown in Fig.7 without measure and in table.1 the AC system got a smooth resumption. To keep stability, the
with necessary measure. Results showed that power control measures under different DC powers are listed in the
exchanging from AC to DC system is advantageous to improve following table in case of bipolar blocking and failure restart.
AC system stability. Results showed that the severity of the fault is closely related
with the exchanging power between AC and DC system and V. CONCLUSIONS
the unit boot mode of Yimin plants. In this paper, dynamic behavior analysis was carried out
focus on the Hu-Liao HVDC and AC parallel transmission
Table.2, stability measures under different DC power in bipolar blocking system. The dynamic performance and the interaction between
DC capacity Measures To Keep stability AC and DC systems during serious disturbance were
6 unit, 3000MW 5 units tripping researched by detail simulation. Only several examples are
3 units tripping
showed and discussed here as space limited. Results showed
4 unit, 3000MW
that:
4 unit,2200MW 2 units tripping
4 unit,1800MW 2 units tripping 1, As for the weak network of Hu-Liao rectifier side and the
limit of AC transfer capacity, transient stability problem is
rather serious. The dynamic interaction between AC and DC
C. Addional Controls for AC/DC Hybrid System
system during disturbance is intense.
The following simulation was done in such an operation: 4
units for DC power sending and DC power 1800MW. First, to 2, The exchanging power between AC and DC system have
research the features of additional controls for AC/DC hybrid a corresponding influence on dynamic performance and control
system, simulations were calculated by three cases: that is no strategies for keeping transient stability. Power exchanging
additional control, with TCSC forced compensation control and from AC to DC system is advantageous to improve AC system
with DC emergency power control. Results were shown in stability.
Fig.10. When the additional control of TCSC and DC is 3, By proper control, TCSC forced compensation and DC
activated, the transient stability can be improved but in a limit emergent power transfer can improve system stability.
compared with unit tripping under such serious faults. Compared with generator tripping, they are only a subsidiary
control method for the researched system.
100
The research will bring important and significant reference
for further operation and stability control of Hu-Liao HVDC
50
and AC system. Further research still remained on the topics
such as the optimal operation of AC and DC system, DC
angle

0 separated operation and control, strategies design for stability


0 2 4 6 8 10 control and the like.
-50
REFERENCES
-100 t(s) [1] IEEE committee, “AC-DC Economics and Altematives-1987 Panel
Session Report”. IEEE Trans on Power Delivery, volume 5, october,
with DC power improving
pp.1956-1976
with TCSC forced control [2] J Hauer, “Controllable ac/dc Dynamics of Western US Power System”,
No additional control CIGRE Symposium on ac/dc transmissions interactions and comparisons,
paper 200-11, Boston September, 1987
Fig.10 additional control effect for AC and DC hybrid system [3] IEEE committee, “HVDC controls for system dynamic performance “,
IEEE Trans PWRS, May 1991,pp.743-752
1.03 [4] C Grund, J Recve “Increased Performance of HVDC Power Modulation
with DC power improving by active and reactive power coordination and modern control”, IEE
1.02 AC&DC transmission, London 1981.
withought DC power improving [5] K To, A David and A Hammad, “A Robust Coordinated Control Scheme
for HVDC Transmission with Parallel AC system”.IEEE Trans PWRD,
f(pu)

1.01 July, 1994, pp.1710-1716


[6] A Hammad, “Stability and control of parallel AC/DC transmission” ,
CIGRE SC14 Johannesburg, sept 1997.
1
[7] A E Hammad, “Stability and control of HVDC and AC transmission in
parallel”, IEEE Trans on Power Delivery, volume 14, no.4 october
0.99 1999, pp.1545-1551,
0 10 20 t(s) 30 40 50 [8] Hammad, K Sadek “Advanced control strategy for a HVDC scheme in
parallel operation with AC system. and control of parallel AC/DC
transmission”,. ICPST Beijing China, 1994,pp:459-464
Fig.11 Ewenke frequency when AC and DC is separated [9] Quan Bailu, “Stability of Tian-Guang HVDC and HVAC Transmission
system.”, ICPST Beijing China, 1994, pp:761-765
Secondly, frequency restore will meet problem when
[10] Jing Yong, Hou Wendong, Yu Wenqi, “Research on Transmission
AC/DC is separated during dynamic process. It is mainly due Capability of Tian-Guang AC and DC Hybrid System”, International
to the AC simple structure in the rectifier side of DC system conference on electrical engineering 2002
and the mismatch power between the DC system and AC [11] Jing Yong, Li Licheng, Ren Zhen, “Stability control of Tian-guang AC
islands system. The frequency simulation was done in two and DC parallel transmission System”, Automation of Electric Power
cases: without additional DC control and improving DC power Systems. Vol 26, No.1 2002, pp:49-52
by 15%. Results show that frequency can be recovered in a
acceptable range with DC control. Advanced controller is still
needed for delicate control.

Das könnte Ihnen auch gefallen