Product data sheet LV432750

Characteristics circuit breaker Compact NSX400H - Micrologic


1.3 M - 320 A - 3 poles 3d

Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Main
Range Compact
Product name Compact NSX
Product or component type Circuit breaker
Device short name Compact NSX400H
Device application Motor
Poles description 3P
Protected poles description 3t
Network type AC
Network frequency 50/60 Hz
[In] rated current 320 A ( 65 °C )
400 A ( 40 °C )
[Ui] rated insulation voltage 800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage 8 kV
[Ue] rated operational voltage 690 V AC 50/60 Hz
Breaking capacity code H (70 kA) AC
Breaking capacity 50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
20 kA at 600 V AC 50/60 Hz conforming to UL 508
65 kA at 480 V AC 50/60 Hz conforming to UL 508
85 kA at 240 V AC 50/60 Hz conforming to UL 508
[Ics] rated service breaking capacity Ics 10 kA 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Ics 100 kA 220/240 V AC 50/60 Hz conforming to IEC 60947-2
Ics 11 kA 525 V AC 50/60 Hz conforming to IEC 60947-2
Ics 50 kA 500 V AC 50/60 Hz conforming to IEC 60947-2
Ics 65 kA 440 V AC 50/60 Hz conforming to IEC 60947-2
Ics 70 kA 380/415 V AC 50/60 Hz conforming to IEC 60947-2
Suitability for isolation Yes conforming to EN 60947-2
Yes conforming to IEC 60947-2

Nov 20, 2018


1
Utilisation category Category A
Trip unit name Micrologic 1.3 M
Trip unit technology Electronic
Trip unit protection functions I
Trip unit rating 320 A ( 65 °C )
Protection type Short-circuit protection (magnetic)
Pollution degree 3 conforming to IEC 60664-1

Complementary
Control type Toggle
Mounting mode Fixed
Mounting support Backplate
Upside connection Front
Downside connection Front
Mechanical durability 15000 cycles
Electrical durability 12000 cycles 440 V In/2 conforming to IEC 60947-2
3000 cycles 690 V In conforming to IEC 60947-2
6000 cycles 440 V In conforming to IEC 60947-2
6000 cycles 690 V In/2 conforming to IEC 60947-2
Connection pitch 45 mm
Local signalling LED ready
Short-time pick-up adjustment type Isd Adjustable 9 settings
[Isd] short-time pick-up adjustment 1600 A
range 1920 A
2440 A
2560 A
2880 A
3200 A
3520 A
3840 A
4160 A
Short-time delay adjustment type Fixed
Instantaneous pick-up adjustment type Fixed
Ii
Instantaneous pick-up adjustment 4800 A
range
Height 255 mm
Width 140 mm
Depth 110 mm
Product weight 6.05 kg

Environment
Overvoltage category Class II
Electrical shock protection class Class II
Standards EN/IEC 60947
UL 508
Product certifications CCC
Marine
EAC
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to IEC 62262
Ambient air temperature for operation -35...70 °C
Ambient air temperature for storage -55...85 °C

Offer Sustainability
Sustainable offer status Green Premium product
RoHS (date code: YYWW) Compliant  - since  0819  -  Schneider Electric declaration of conformity

2
Schneider Electric declaration of conformity
REACh Reference not containing SVHC above the threshold
Reference not containing SVHC above the threshold
Product environmental profile Available
Product environmental
Product end of life instructions Available
End of life manual

Contractual warranty
Warranty period 18 months 18 months