Kingfisher PLUS+

Installation Manual
Document Information

Document Control
Copyright  CSE-Semaphore (Australia) Pty Ltd. ABN 35 006 805 910
Copyright
www.cse-semaphore.com/mykingfisher, info.kingfisher@cse-semaphore.com
CSE-Semaphore asserts ownership of the intellectual property contained herein and
Intellectual Property claims copyright and authorship. CSE-Semaphore has and retains all rights of
ownership and use of the material herein in its on-going business.
This document is provided to the intended recipient(s) under a non-exclusive licence.
This licence permits Fair Use of the document for operational requirements, without
payment of further royalty or licence fee. Fair Use includes making copies of the
document for operational, backup and archive purposes. Fair Use includes distributing
Licence
copies of the document to other entities for the purposes of their performing related
works for the intended recipient(s). Fair Use does not include creating, selling or
distributing copies of the document for other purposes. All copies must retain this
statement of Intellectual Property and Copyright.

Revision History
Rev.* Date Summary
1.7 29/1/2004 Added DO-5 relay board wiring diagram.
1.8 13/8/2004 Added CDMA and satellite phone cables. Updated DO-5 relay board wiring diagram (new
revision TEL REL 002). Removed AI-4 wiring diagram.
1.81 2/9/2004 Updated backplane terminators drawing (all terminators are now on for a single
backplane).
1.82 9/9/2004 Renamed chapter 6 from Wiring Modules to Wiring Diagrams. Revision date for 1.81 was
incorrect.
1.9 23/8/2005 Updated wiring drawing for ADP-16. Added RJC-ADP-17 cable.
2.0 4/5/2006 Updated RTUnet contact details. Added ADP-28 cable. Added battery warnings for PS-
11/21 wiring diagrams.
2.1 26/10/2006 Added ADP-08-M, ADP-29, RJC-ADP-30 and ADP-30 cables.
2.2 12/7/2007 Updated the RA Form. Added coaxial cable information. Added DO-5 wiring diagram.
Kingfisher Series II is now called Kingfisher PLUS+.
2.3 17/4/2008 Removed revision history entries prior to 2004. RJC-ADP-26 is now used for a Maxon 3G
modem (instead of a CDMA modem). Updated company name from RTUnet to CSE-
Semaphore. Added wiring examples for AI-1, AI-10, IO-3 and IO-4. Updated DO-5 to DO-
6. Standardised format of electrical units. Updated enclosure layout drawing for preventing
fire risk.
2.4 26/8/2008 Updated RA form to 21 November 2007. Updated GSM adaptor cable to RJC-ADP-22B.
Updated Overview chapter. Removed cables for Trio radios and devices that are no longer
available. Updated adaptor cable pictures.
2.5 10/9/2009 Updated AO-2 and PS-11 wiring diagrams. Updated contact details. Updated Backplane
Setup chapter for new backplane connectors (applies to BA-x PLUS backplanes). Added
Removable I/O Connector topic.
2.6 13/8/2010 Removed the resistance test for a new antenna installation. Added recommended wiring
gauges. Added 7 AH battery holding bracket that can be used in enclosures. Added topic
– 19” Rack Mounting.

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 2


Contents

1. RTU Layout........................................................................................................4

2. Installing Modules............................................................................................. 5

3. Removable I/O Connector ................................................................................5

4. Backplane Setup ............................................................................................... 6

5. Enclosure Layout.............................................................................................. 7
5.1 Battery and GPO Bracket ...................................................................................................7

6. 19” Rack Mounting ........................................................................................... 8


6.1 How To Mount a 12-Slot Backplane ...................................................................................8
6.2 How To Mount a Four Or Six Slot Backplane.....................................................................8

7. Installing Cables And Adaptors .......................................................................9

8. Wiring Diagrams ............................................................................................. 11


8.1 Analog Inputs....................................................................................................................11
8.2 AI-1 Wiring Diagram .........................................................................................................11
8.3 AI-10 Wiring Diagram .......................................................................................................12
8.4 AO-2 / AO-3 Wiring Diagram ............................................................................................13
8.5 DI-5 Wiring Diagram .........................................................................................................13
8.6 DI-10 Wiring Diagram .......................................................................................................14
8.7 DO-1 Wiring Diagram .......................................................................................................14
8.8 DO-2 Wiring Diagram .......................................................................................................15
8.9 DO-6 Wiring Diagram .......................................................................................................15
8.10 DO-6 Relay Board (TEL REL 002) Wiring Diagram .........................................................16
8.11 IO-2 Wiring Diagram .........................................................................................................17
8.12 IO-3 Wiring Diagram .........................................................................................................18
8.13 IO-4 Wiring Diagram .........................................................................................................19
8.14 PS-11 Wiring Diagram - AC Supply..................................................................................20
8.15 PS-11 Wiring Diagram - DC Supply .................................................................................20
8.16 PS-21 Wiring Diagram......................................................................................................21
8.17 PSU-3: Economy AC Input Power Supply (for PC-1).......................................................21

9. Solar Panel Installation ..................................................................................22

10. Level Probe Installation..................................................................................22

11. Antenna Installation........................................................................................23


11.1 Antenna Cable Selection And Installation ........................................................................24
11.2 How To Assemble Antenna Connectors...........................................................................24

12. Return Of Goods ............................................................................................. 25

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 3


1. RTU Layout
The exact layout should be defined in layout and wiring drawings supplied with the RTU. If these have
not been supplied, then the RTU layouts shown below can be used as a guide.

Every RTU has a backplane (eg BA-4, BA-6), a power supply (eg PSU-3 or PS-11) and a processor
module (eg PC-1 or CP-11). The two common types of RTUs are shown below.

PSU-3
BA-4 BA-6
PC-1 PS11 CP11

12V DC

MAINS MAINS
POWER POWER

An RTU can have additional communications ports (MC-11) and a wide variety of input/output
modules (eg. IO-4, AI-1, DI-5). Some of these are shown below.

PSU-3
BA-4 BA-6
PC-1 MC11 IO-4 PS11 CP-11
CP11 MC11 AI-1 DI-5

12V DC

MAINS MAINS
POWER POWER

If a communications module is used, standard practice is to install it to the right of the processor. IO
modules are usually installed in alphabetical order from left to right. Eg an AI-1 module would be
located to the left of a DI-5 module. The modules can be installed in any order if so desired (except a
PC-1 must be installed in the leftmost slot of a BA-4 backplane since it has two sockets).

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 4


2. Installing Modules

2 Press into socket 3 Fasten screw to lock module


onto backplane

Hook mounting tab onto


backplane slot

3. Removable I/O Connector


Each I/O module has a removable I/O connector. This allows the I/O module to be swapped without
having to detach the field wiring from the I/O connector. The I/O connector is secured to the module
using two fastening screws as shown below.

I/O Connector
Fastening
Screw

I/O Connector
Fastening
Screw

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 5


4. Backplane Setup
If a single backplane is being used then the switches on the backplane do not need to be changed.

When linking two backplanes, please set the backplane switches as shown below (for backplane
revisions 2.1, 2.2 and 3.2). A data cable is required to link the backplanes. If a backplane does not
have its own power supply, a power cable will also be required to connect it to a powered backplane.

The examples below show linking for BA-xx PLUS (revision 3.2) backplanes. When linking BA-xx
PLUS backplanes (green Phoenix data connectors) with the older BA-xx backplanes (black Harwin
data connectors), BAC-INT-0x data cables are used. These cables have a Phoenix connector on one
end and a Harwin connector on the other. All data cables are straight through and do not contain
crossovers. To link two older BA-xx backplanes, a BAC-0x data cable is used.

BAC-PLUS-0x DATA CABLE


Note: different rack numbers are required to BPC-0x POWER CABLE
avoid clashing of the slot addresses.
Both backplanes are PC-1 J13 J13
ON ON
powered from the
PC-1 in slot 13. J14 J14
The PC-1 is S LO T 13 16 SLOT 29 32
powered by a
PSU-3 connected to BA-4 BA-40
the BA-4 RACK 1 RACK 2

BAC-PLUS-0x DATA CABLE


Note:same rack numbers can be used since each backplane BPC-0x POWER CABLE
has different slot addresses (1 to 6 and 13 to 16).
J13 J13
Both backplanes PS-11 ON ON
P
are powered S
using a PS-11 in J14 J14
- S LO T 1 6 SLOT 13 16
any slot 1
(typically slot 1) 1 BA-6 BA-40
RACK 1 RACK 1
Same settings apply for BA-12

BAC-PLUS-0x DATA CABLE


Note: different rack numbers are required to avoid
clashing of the slot addresses.
J13 J13
ON ON

SLOT 1 12 SLOT 17 22

BA-12 BA-6
P
S
RACK 1 - RACK 2
Each backplane requires its own PS-11/21 power Same settings apply for BA-12
1
supply module (typically installed in the left slot). 1
Note: a single supply can be used to power both
backplanes using a BPC-0x power cable if the total
current load of the supply is not exceeded.

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 6


5. Enclosure Layout
CAUTION! A RADIO SHOULD ONLY BE POWERED WHEN IT HAS AN ANTENNA CONNECTED.
THIS WILL PREVENT DAMAGE TO THE RADIO IF IT TRANSMITS.

All components of a Kingfisher PLUS+ RTU shall be installed inside of an enclosure providing safety
and environmental protection. The enclosure shall be made from metal or other material with a
flammability rating of V-0 or better in accordance with the requirements of the IEC 60950-1:2001
standard for a fire enclosure. An enclosure is not required to prevent fire hazard if the RTU is installed
above concrete or other non-combustible surface. Examples of enclosure layouts are shown below.

VENT MUST BE ENCLOSURE – RITTAL AE1045 INSTALL BACKPLANE LOW ENOUGH TO


INSTALLED IF ALLOW FOR AIRFLOW THROUGH MODULES.
500 HIGH x 400 WIDE x 210 DEEP mm
ENCLOSURE HAS A
BATTERY. INSTALL A RADIO OR MODEM.
SECOND VENT IN GEARPLATE NOTE: RADIO CAN BE
LOWER RIGHT HAND MOUNTED ON REAR OF
CORNER IF BATTERY PC-1 MC11 IO-3 DOOR BY USING DIN
IS > 26 AH OR IF RAIL. ENSURE THAT THE
PSU-3 RADIO IS MOUNTED ON
ENVIRONMENTAL
CONDITIONS THE TOP LEFT HAND
REQUIRE GREATER CORNER OF THE DOOR
AIRFLOW. TO ALLOW THE RADIO
TO CLEAR THE RTU
MODULES WHEN THE
DOOR IS CLOSED.

IO WIRING TERMINALS
DOUBLE GPO. ONE SLOTTED DUCT 20 X 60 mm
OUTLET FOR RTU. ONE LIGHTNING ARRESTOR.
OUTLET FOR LAPTOP INSTALL HIGH ENOUGH TO
ALLOW EASY ACCESS FOR
ANTENNA LEAD
CONNECTION

EARTH STUD. ENSURE


GPO, BACKPLANE AND
LIGHTNING ARRESTOR
ARE CONNECTED TO
THIS POINT USING
BATTERY
APPROPRIATE EARTHING
(MINIMUM 7 AH) METHODS.
BATTERY CAN REST
ON BOTTOM OF
ENCLOSURE OR A
BATTERY BRACKET
CAN BE USED
LEAVE AT LEAST 30 mm
CLEARANCE TO ALLOW
ROOM FOR GLANDS AND
ENCLOSURE MUST NOT CABLES.
CONTAIN OPENINGS IN
THIS AREA TO AVOID
CABLE GLANDS MOUNTED
FIRE RISK TO EXTERNAL
THROUGH GLAND PLATE
5 DEG ENVIRONMENT 5 DEG

5.1 Battery and GPO Bracket


When using a 7 AH backup battery, a standard battery holder is available from your RTU supplier. The
bracket supports the battery and allows a General Power Outlet (GPO) to be mounted on the front
using M3 x 10 mm pan head screws. The battery holder also allows an ISB50LN lightning arrestor to
be mounted underneath.

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 7


6. 19” Rack Mounting

6.1 How To Mount a 12-Slot Backplane


A 12 slot backplane (BA-12) is mounted in a 19 inch rack using two MBR-3 mounting brackets. The
MBR-3 brackets replace the surface mount brackets supplied with BA-12 backplanes.

Installation Note: The holes in the MBR-3 brackets that are used to attach the brackets to the back of
the backplane are drilled oversize to accommodate slight variances in racking equipment. By
loosening these screws, pushing the brackets toward the centre of the backplane and then re-
tightening the screws, the unit will fit freely into any correctly sized 19-inch rack.

6.2 How To Mount a Four Or Six Slot Backplane


A four slot backplane (BA-4 or BA-40) or a six slot backplane (BA-6) is mounted in a 19 inch rack
using a TEL-RAK-002 mounting bracket. One BA-6 or two BA-4/BA-40 backplanes can be attached to
the TEL-RAK-002 using the surface mount brackets supplied with each backplane. The TEL-RAK-002
is supplied with eight M3 x 5 mm screws for attaching the backplane(s).

450 mm

222 mm

222 mm

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 8


7. Installing Cables And Adaptors
TOOLBOX OR SCADA CABLE RTU
ADP-05
RJ45 TO RJ45 PATCH CABLE RJ45

RS232

PSTN MODEM
Eg. Netcomm MyModem V.92
from www.netcomm.com.au ADP-07 RTU

RJ45 TO RJ45 PATCH CABLE RJ45


RS232

NULL MODEM CABLE


ADP-08 ADP-05
RJ45 TO RJ45 PATCH CABLE

Spread Spectrum Radio


XTend-PKG or XStream-PKG
from www.digi.com

ADP-08M
RTU
RJ45

RS232

RJ45 TO RJ45 PATCH CABLE

TRIO D OR E SERIES RADIO

RTU
RJ45
RJ45 TO RJ45 PATCH CABLE
RS232
ADP-16

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 9


GSM MODEM
Eg. Fastrack Supreme
from www.wavecom.com
RTU

RJ45
RS232

RJC-ADP-22B

Maxon 3G Modem Modmax


MM-6280IND from
www.maxon.com.au
RTU

RJ45
RS232

RJC-ADP-26

TRIO M SERIES RADIO (eg. MR450) with MODEM FITTED

RTU

RJ45
RJ45 TO RJ45 PATCH CABLE
RS232
ADP-29

TRIO M SERIES ANALOG RADIO (eg. MR450) with NO MODEM FITTED CP-xx
MC-xx

RJ45

LINE-2
LINE-2 POWER
WIRE.
RJC-ADP-30
CONNECT TO
RADIO POWER
+12 V

TRIO M SERIES ANALOG RADIO (eg. MR450) with NO MODEM FITTED


PC-1
MC-1

RJ45
RJ45 TO RJ45 PATCH CABLE
ADP-31
RADIO

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 10


8. Wiring Diagrams
To Wire Use Wire Type
2
IO Modules 0.75 to 2.08 mm OR 18 to 14 AWG (American Wire Gauge)
(Note: Fujicon IO terminal tension: 1 Nm)
2 2
Battery and 12 V power 2.5 to 4.0 mm OR 13 to 11 AWG. Use 4mm for > 2 m runs

8.1 Analog Inputs


A combination of loop powered (2-wire) and self powered (3 or 4-wire) analog input transmitters can
be used on the one module (AI-1, AI-10, IO-3 or IO-4).

By default, each analog input is designed to accept 4 to 20 mA. Removing a link on the back of the
module will allow 0 to 20mA operation for all channels of an AI-1, AO-2, IO-3 or IO-4. The current or
voltage range for all channels of an AI-10 module is software configurable.

8.2 AI-1 Wiring Diagram

1 CH 1
Wiring Examples
2 0V +24 V
Output + Analog 2-wire transmitter
3 +24 V Ou tput
- Input (powered by module)
4 CH 2 CH x
5 SHIELD
6 CH 3
7 0V CH x + Analog 3-wire transmitter
- Input (powered by module)
8 +24 V Ou tput 0V
9 CH 4 +24 V
10 SHIELD Output
11 CH 5 + Analog
0V CH x 4-wire transmitter
12 - Input
0V (powered by module)
13 +24 V Ou tput
PWR
14 CH 6 +24 V
15 SHIELD Output
16 CH 7
17 0V
18 +24 V Ou tput + Analog 2-wire transmitter
19 CH 8 CH x - Input (powered externally)
20 SHIELD
+ POWER
0V SUPPLY
-

CH x + Analog 3-wire transmitter


- Input (powered externally)
PWR + POWER
0V SUPPLY
-

CH x + 4-wire transmitter
Analog
0V - Input (powered externally)
PWR + POWER
SUPPLY
-

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 11


8.3 AI-10 Wiring Diagram
Wiring Examples
1 CH 1+
+24 V + Analog
2 CH 1- Output 2-wire transmitter *
- Input (powered by module)
3 CH 2+
CH x +
4 CH 2-
5 CH 3+ CH x -
LOOP
6 CH 3- 0V
7 CH 4+
8 CH 4- CH x + + Analog 3-wire transmitter *
9 +24 V Output CH x - - Input (powered by module)
10 0V 0V PWR
11 CH 5+ +24 V
12 CH 5- Output
13 CH 6+
14 CH 6- CH x + + Analog 4-wire transmitter
15 CH 7+ CH x - - Input (powered by module)
16 CH 7- 0V PWR
17 CH 8+ +24 V
18 CH 8- Output
19 +24 V Output
20 0V + Analog 2-wire transmitter
CH x + - Input (powered externally)
+ POWER
CH x - SUPPLY
-

CH x + + Analog 3-wire transmitter


- Input (powered externally)
PWR + POWER
CH x - SUPPLY
-

+
CH x + Analog 4-wire transmitter
CH x - - Input (powered externally)
PWR
+ POWER
SUPPLY
-

* When using the +24V output to power a transmitter, the negative input terminal of the analog input channel (2, 4,
6, 8, 12, 14, 16 or 18) must be wired to the OV terminal (10 or 20). This will complete the current loop due to
electrical isolation between the input channel and the module +24V supply.

Note: Any channels sharing the same power source (e.g. +24V from module or a field power supply) are no
longer isolated from one other.

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 12


8.4 AO-2 / AO-3 Wiring Diagram
1 CH 1+ Wiring Example
2 CH 1-
3 CH x + + Analog 4-20 or 0-20 mA
4 CH x - - Output Current Load
5 SHIELD SHIELD
6 CH 2+
7 CH 2-
8
9
10 SHIELD
11 CH 3+
12 CH 3-
13
14
15 SHIELD
16 CH 4+
17 CH 4-
18
19
20 SHIELD

8.5 DI-5 Wiring Diagram


Wiring Examples
1 CH 1
2 CH 2 FIELD CONTACT
3 CH 3 CH x
+12V
Powered by
4 CH 4
module
5 CH 5
6 CH 6 FIELD CONTACT
INTERNAL
7 CH 7
CH x + External power
CIRCUITRY 8 CH 8
POWER supply
9 +12V Ou tput SUPPLY
Note: polarity can
10 0V / Common 0V
be reversed.
11 CH 9
12 CH 10
13 CH 11
14 CH 12
15 CH 13
16 CH 14
17 CH 15
18 CH 16
19 +12V Ou tput
20 0V / Common

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 13


8.6 DI-10 Wiring Diagram
Wiring Examples
1 CH 1
2 CH 2 FIELD CONTACT
3 CH 3 CH x Powered by
4 CH 4 +12V module
5 CH 5
6 CH 6 FIELD CONTACT
7 CH 7
INTERNAL CH x +
CIRCUITRY 8 CH 8
AC or DC* External power
9 +12V Ou tput POWER supply
10 0V / Common SUPPLY
11 CH 9 0V /
12 CH 10 Common
* DC voltage applied to input
13 CH 11 channel must be more positive
14 CH 12 than the common
15 CH 13
16 CH 14 DC pow ered inputs and AC powered inputs can
17 CH 15 both be used on the one module.
18 CH 16 Care should be taken to ensure that the negative
19 +12V Ou tput rail of each external power supply is connected
20 0V / Common to the DI-10 0V / Common ter minal.

8.7 DO-1 Wiring Diagram


INTERNAL Wiring Example
CIRCUITRY
1 NO
NC CH 1 CH x LOAD External Power
2
Supply. Note:
3 NO POWER
CH 2 polarity can be
NC SUPPLY
4 reversed.
COMMON 1 COMMON +
7A 5
6 NO
NC CH 3
7
8 NO
NC CH 4
9

7A 10
COMMON 2
11 NO
NC CH 5
12
13 NO
NC CH 6
14
7A 15
COMMON 3
16
NO
NC CH 7
17
NO
18
NC CH 8
19
7A 20 COMMON 4

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 14


8.8 DO-2 Wiring Diagram

1 CH 1 Wiring Example
2 CH 2
CH x LOAD
3 CH 3 External Power
4 CH 4 POWER Supply. Note:
5 CH 5 COMMON SUPPLY polarity can be
+ reversed.
6 CH 6
7 CH 7
8 CH 8
7A 9 COMMON 1
10 LINK *
11 CH 9
12 CH 10
13 CH 11
14 CH 12
15 CH 13
16 CH 14
17 CH 15
18 CH 16
7A 19 COMMON 2
20 LINK *
INTERNAL
CIRCUITRY * Optional link for DC SUPPLY ONLY. Enables fuse fail LED ‘FU’ on module. CAUTION! When
links are installed, a maximum voltage of 30V AC or DC can be used to power the common.

8.9 DO-6 Wiring Diagram

1 CH 1 Wiring Examples
2 CH 2
CH 3 CH x +
3 LOAD
+
4 CH 4
POWER External DC
5 CH 5 SUPPLY Power Supply
6 CH 6 0V
7 CH 7
INTERNAL
CIRCUITRY 8 CH 8
9 0V + Load powered by
CH x LOAD DO-5 module
10 0V
11 CH 9 +12V Output
12 CH 10
13 CH 11
14 CH 12
15 CH 13 When output is energised, output channel is
16 CH 14 shorted to the 0V terminal.
17 CH 15
18 CH 16
19 +12V Output 12V Output is sourced from the backplane power rail.
20 +12V Output This output is not isolated. Care should be exercised
to avoid shorting or overloading this output.

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 15


8.10 DO-6 Relay Board (TEL REL 002) Wiring Diagram

CH 1

CH 2

CH 3

CH 4

CH 5

CH 6

CH 7

CH 8

CH 9

CH 10

CH 11

CH 12

CH 13

CH 14

CH 15

CH 16

Terminal Layout For Each DO-5 Channel


NO - Normally open contact
C - Common
NC - Normally closed contact

Each channel has 3 relay contacts (NO,C,NC) connected


to two 3-way terminal blocks
Wiring Example
NO LOAD
When the output
channel is set ON, POWER External Power Supply.
the load is energised SUPPLY
Note: polarity can be reversed.
C +

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 16


8.11 IO-2 Wiring Diagram

Wiring Examples
1 DI CH 1
FIELD CONTACT
2 DI CH 2
DI CH x + External power
3 DI CH 3 POWER supply.
4 DI CH 4 SUPPLY
Note: polarity can
5 DI CH 5 DI 0V
be reversed.
6 DI CH 6
7 DI CH 7
8 DI CH 8
INTERNAL
9 DI 0V / Common DO CH x LOAD External Power
CIRCUITRY 10 DI 0V / Common Supply
POWER
11 DO CH 1 SUPPLY Note: polarity can be
12 DO CH 2 DO + reversed.
13 DO CH 3 Common
14 DO CH 4
15 DO CH 5
16 DO CH 6 DC pow ered inputs and low voltage AC inputs can both be used
17 DO CH 7 on the one module.
18 DO CH 8
10A 19 DO Common
20 LINK *

* Optional link for DC SUPPLY ONLY. Enables fuse fail LED ‘FU’ on module.
CAUTION! When link is installed, a maximum voltage of 30V AC or DC can be used
to power the common.

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 17


8.12 IO-3 Wiring Diagram
There are three separate isolated groups, one for the analog input/output, one for the digital input and
one for the digital output. Each group may be powered from a separate source.

Wiring Examples

1 AI CH 1 AI CH x - 2-wire transmitter
Analog
2 AI CH 2 +24 V + Input (powered by module)
Output
3 AI CH 3
4 AI CH 4
AI CH x + Analog 3-wire transmitter
5 0V - Input
0V (powered by module)
6 +24 V Ou tput
+24 V
7 AO +
Output
8 AO -
9 SHIELD AI CH x + Analog 4-wire transmitter
DI CH 1 - Input (powered by module)
10 0V
11 DI CH 2 +24 V PWR
12 DI CH 3 Output
INTERNAL 13 DI CH 4
CIRCUITRY DI Common
14
+ Analog 2-wire transmitter
15 DO CH 1 -
AI CH x Input (powered externally)
16 DO CH 2
17 DO CH 3 + POWER
0V SUPPLY
18 DO CH 4 -
7A 19 DO Common
20 LINK *
AI CH x + Analog 3-wire transmitter
- Input (powered externally)
* Optional link for DC SUPPLY PWR +
ONLY. Enables fuse fail LED POWER
‘FU’ on module. CAUTION! 0V SUPPLY
-
When link is installed, a
maximum voltage of 30 V AC
or DC can be used to power
AI CH x + 4-wire transmitter
the common. Analog
0V - Input (powered externally)
PWR + POWER
SUPPLY
-
+
AO + Analog Current Load
- Output
AO -

FIELD CONTACT
DI CH x Powered by module
+24 V
Output DC pow ered inputs
and low voltage AC
DI Com. inputs can both be
0V
Link
used on the one
module.
FIELD CONTACT
DI CH x +
POWER
External power
SUPPLY supply. Note: polarity
DI can be reversed.
Common

DO CH x LOAD
External Power
POWER
SUPPLY Supply. Note: polarity
DO + can be reversed.
Common

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 18


8.13 IO-4 Wiring Diagram
There are three separate isolated groups, one for the analog input, one for the digital input and one for
the digital output. Each group may be powered from a separate source. Analog input channel 1 can be
factory modified to support a strain gauge input.

Wiring Examples

1 +E (optional) +E (5 V)
2 -E (optional) -E (0 V) Strain gauge input
3 AI CH 1 or -S -S (special order only)
0-50 mV
4 +S (optional) +S
5 AI CH 2
6 0V AI CH x - 2-wire transmitter
Analog
7 +24 V Ou tput +24 V + Input (powered by module)
8 DI CH 1 Output
9 DI CH 2
AI CH x + Analog 3-wire transmitter
10 DI CH 3 - Input
0V (powered by module)
11 DI CH 4
+24 V
12 DI CH 5 Output
13 DI CH 6
14 DI CH 7 AI CH x + Analog 4-wire transmitter
INTERNAL 15 DI CH 8 0V - Input (powered by module)
CIRCUITRY 16 DI Common +24 V PWR
17 DO CH 1 Output
18 DO CH 2
7A 19 DO Common + Analog 2-wire transmitter
20 LINK * AI CH x - Input (powered externally)
+ POWER
* Optional link for DC SUPPLY 0V SUPPLY
ONLY. Enables fuse fail LED -
‘FU’ on module. CAUTION!
When link is installed, a AI CH x + Analog 3-wire transmitter
maximum voltage of 30 V AC or - Input (powered externally)
DC can be used to power the
PWR +
common. POWER
0V SUPPLY
-

AI CH x + 4-wire transmitter
Analog
0V - Input (powered externally)
PWR
+ POWER
SUPPLY
-

FIELD CONTACT
DI CH x Powered by module
+24 V
Output
DC pow ered inputs
DI Com. and low voltage AC
Link inputs can both be
0V
used on the one
FIELD CONTACT module.
DI CH x +
POWER
External power
SUPPLY supply. Note: polarity
DI can be reversed.
Common

DO CH x LOAD
External Power
POWER
SUPPLY Supply. Note: polarity
DO + can be reversed.
Common

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 19


8.14 PS-11 Wiring Diagram - AC Supply
PS-11

OFF
VA+ + 24 VDC AUXILIARY OUTPUT (OPTIONAL)
VA- -
R+ + 13.8 VDC OUTPUT (FOR RADIO OR OTHER DEVICE)
R- -
GREY WITH BLACK STRIPE #
TS TEMPERATURE SENSOR
B+
B- - +
CAUTION! Connecting the
BACKUP battery in reverse may cause
BATTERY damage to the power supply.

A ACTIVE (+)
N NEUTRAL (-)
E EARTH
100-240 VAC
96-340 VDC
#
TAPE OR CABLE TIE TEMPERATURE SENSOR TO NEGATIVE BATTERY TERMINAL (OR
AS CLOSE AS POSSIBLE). CONNECT BLACK STRIPED WIRE OF SENSOR TO R- OR B-

8.15 PS-11 Wiring Diagram - DC Supply


A low voltage DC supply can be fitted to the battery input terminals or a higher voltage DC supply can
be fitted to the AC input circuit.

PS-11

OFF
VA+
+
24 VDC AUXILIARY OUTPUT (OP TIONAL)
VA- -
R+ + 13.8 VDC OUTPUT (FOR RADIO OR OTHER DEVICE)
R- -
TS
B+ + 12 VDC SUPPLY (NOMINAL) CAUTION! Connecting the
(MUST BE ISOLA TED FROM FIELD SUPPLY )
B- - DC Supply in reverse may
cause damage to the PS-11.

+ 96 TO 340 VDC SUPPLY


A
- (ALTERNA TIVE TO USING BATTERY TERMINALS)
N
E

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 20


8.16 PS-21 Wiring Diagram
PS-21

OFF
VA+ + 24 VDC AUXILIARY OUTPUT (OPTIONAL)
VA- -
R+ + 13.8 VDC OUTPUT (FOR RADIO OR OTHER DEVICE)
R- -
GREY WITH BLACK STRIPE #
TS TEMPERATURE SENSOR
B+
B- - +
CAUTION! Connecting the
BACKUP battery in reverse may cause
BATTERY damage to the power supply.
E EARTH
- - SUPPLY
+ + SUPPLY 20 TO 60 VDC INPUT SUPPLY *

*A NEGATIVE DC INPUT SUPPLY CAN BE USED. CONNECT THE MORE POSITIVE WIRE
(eg 0 V) TO +SUPPLY AND CONNECT THE MORE NEGATIVE WIRE (eg -48 V) TO -SUPPLY.
#
TAPE OR CABLE TIE TEMPERATURE SENSOR TO NEGATIVE BATTERY TERMINAL (OR
37.5
AS CLOSE AS POSSIBLE). CONNECT BLACK STRIPED WIRE OF SENSOR TO R- OR B-

8.17 PSU-3: Economy AC Input Power Supply (for PC-1)


+V and –V are wired to pins 7 and 8 (12V Supply Input) of the orange BL9 connector on the BA-4
backplane.

1 2 3 4 5
-V
+V
A
N
E

Voltage
Adjust
(13.8V)
BA-4

+12V Supply Input


0V Supply Input

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 21


9. Solar Panel Installation

LATTITUDE TILT ANGLE ‘A’


OF SITE
L
NE 0-4 Deg 10 Deg
Ensure panel PA 5-20 Deg Add 5 Deg to local lattitude
R
will not be
OLA 21-45 Deg Add 10 Deg to local lattitude
shaded by S 45-65 Deg Add 15 Deg to local lattitude
trees etc 65-75 Deg 80 Deg

Eg Sydney, Australia has a lattitude of 33 Deg.


A Therefore tilt angle = 43 Deg.

Set to face due South when in northern


hemisphere and set to face due North when in
southern hemisphere

10. Level Probe Installation


Hang level probe near
access hatch

Connect level
RTU probe to
analog input

Hang level probe (Eg. Platypus from www.ecefast.com.au)


100mm above floor of tank (above sludge)

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 22


11. Antenna Installation
N TYPE MALE *
ANTENNA N TYPE FEMALE *
MOUNTING
CLAMP

AIM ANTENNA AT
REPEATER OR AT
B MASTER RTU.
SHOULD HAVE
LINE OF SITE. USE
DRAIN HOLE TO COMPASS TO AIM
ANTENNA CONNECTION BOTTOM WHEN WHERE
TO BE SEALED WITH MOUNTED NECESSARY
SELF AMALGAMATING VERTICALLY
TAPE

CABLE TO TEST USING A MULTIMETER


MAINTENANCE (WITH CONNECTORS INSTALLED):
LOOP
1. TEST FOR OPEN CIRCUIT BETWEEN THE
CENTRE PIN AND THE CASE OF CONNECTOR A
CABLE TIE WITH THE ANTENNA DISCONNECTED:
B A OPEN
CIRCUIT?

NO ANTENNA
FASCIA MOUNT
HOCKEY STICK
ANTENNA MAST 2. TEST FOR SHORT CIRCUIT BETWEEN THE
CENTRE PIN AND THE CASE OF CONNECTOR A
WITH A SHORT CIRCUIT AT CONNECTOR B (CAN
USE AN ALIGATOR CLIP FOR THE SHORT)
COACH SCREWS B A SHORT
CIRCUIT?

ANTENNA CABLE.
SHORT CIRCUIT

NOTE: A THOROUGH ANTENNA TEST REQUIRES A


WATTMETER. WHEN RADIO IS TRANSMITTING,
CHECK:
REVERSE POWER = 0W
FORWARD POWER > 0W

USE N TYPE MALE WHEN


CONNECTING TO LIGHTNING
ARRESTOR OR USE BNC
MALE WHEN CONNECTING
STRAIGHT TO RADIO* (A
A LIGHTNING ARRESTOR IS
HIGHLY RECOMMENDED)

* Wiring of antenna connectors is detailed in the next section.

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 23


11.1 Antenna Cable Selection And Installation
Recommendations:
 Only use RG58 within an enclosure or within a building and if the cable run is less than 5 metres.
The cable is too fragile and the cable loss is too high for outside longer cable runs.
 Typically use RG213 up to 10 metres. This suits 6 metre water pipes that are commonly used for
antenna masts.
 After 10 metres it becomes a question of how much signal loss can be tolerated. LDF4 or LDF5
have lower signal loss per metre as listed below.
 Minimise the number of connections in the cable run – connections have a great deal of loss.

Loss per m of coax (@450MHZ) Loss per m of coax (@900MHZ):


RG58 0.44 dB RG58 0.60 dB (Do not use!)
RG213 0.16 dB RG213 0.24 dB
LDF4 0.05 dB LDF4 0.07 dB
LDF5 0.03 dB LDF5 0.04 dB

11.2 How To Assemble Antenna Connectors


The following instructions apply to all three connectors:

1. Place clamp nut and plain gasket over cable.


2. Trim outer sheath from cable to dimension shown.
3. Fold back braid and insert ferrule to trap braid between outer sheath and ferrule.
4. Trim off surplus braid.
5. Trim dielectric to dimension shown, and check that exposed centre conductor length is as
specified.
6. Tin centre conductor.
7. Slide rear insulator over dielectric to butt against ferrule.
8. Mount contact (male for plugs, female for jacks) over centre conductor with shoulder pressed
against rear insulator.
9. Hold cable and contact firmly together, and solder.
10. Slide plain gasket and clamp nut up to ferrule, trapping braid.
11. Fit front insulator over contact to butt against rear insulator.
12. Press sub-assembly into body as far as possible and engage clamp nut.
13. Holding body and cable rigid, tighten clamp nut to compress plain gasket and retain cable.

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 24


RG213 To BNC

RG213 To N-Type

RG58 To N-Type

12. Return Of Goods


If you would like to return RTU modules or equipment for testing or repair, please carry out the
following steps:

 Request a Return Authorisation (RA) number from your Kingfisher representative


 Complete all details on a RA form (please use the supplied form as a master copy or download
one from the Semaphore web site)
 Return RA form with goods

Kingfisher PLUS+ Installation Manual 2.6 www.cse-semaphore.com/mykingfisher Page 25


RETURN AUTHORISATION

RETURN AUTHORISATION NUMBER RETURNS PROCEDURE CSE-Semaphore Australia Pty Ltd


Unit 8, 3-5 Gilda Court
1. Request an RA No. from CSE-Semaphore Australia Pty Ltd MULGRAVE, VICTORIA 3170, AUSTRALIA
2. Complete all details on form then fax copy to CSE Semaphore PH: (61) 3 8544 8544
FAX: (61) 3 8544 8555
3. Return form with goods to address shown on right ABN: 006 805 910

PLEASE NOTE: Goods can only be repaired when accompanied by an RA Form with all details completed

CUSTOMER DATE: / / PHONE No: ( )


DELIVERY ADDRESS FAX No: ( )
ORDER NO:
TECHNICAL CONTACT:
PREFFERED COURIER:
Please note, customer pays freight both ways
PART NO SERIAL NO PROBLEM - Please provide as much detail as possible INTERNAL USE ONLY

FACTORY WARRANTY
Goods are under warranty for twelve months only from date of shipment, unless otherwise arranged by contract. Please note that goods are not co vered under warranty when subjected to
improper use. If goods are under warranty, please complete the following otherwise goods will be charged for.
DATE PURCHASED YOUR ORDER NO. INTERNAL USE ONLY

21 November 2007: Installationmanual.Doc