Modbus Server
Interface
Revision 6
7 July 2013
Data Access
Coalscan data is made available as register data which can be interpreted as 16 bit unsigned values or
32 bit floating point data. Floating point numbers use two registers and all values are stored in “Big
Endian” format (This is a ModBus requirement, other PLC protocols may be different).
Data is made available in blocks and these blocks can be read in part or in full. Multiple blocks can
not be read using a single read command. Some blocks are broken in sub-blocks of integer and
floating point values. The sub-blocks must be read individually. Empty rows separate blocks
which cannot be read together.
Note : Ranges given in table below are typical and will vary between material type and location
Note : Results available will vary depending on application
Write Command
TW Accumulator Reset (send Unsigned 45005
a non zero) Integer
0
Ambienet temperature Float C -20 to 50 43125
0
Detector temperature Float C 0 to 50 43121
0
Electronics Cabinet temperature Float C 0 to 50 43123
NOTES:
- Addresses 45202, 45203, 45204 and 45205 can be read together even though they are listed on
four separate pages (p4 to p7).