 DETAILS
CARBON FILTER








       












ODOUR CONTROL UNIT FOR ECOLOGY UNIT
MODEL NO: ECO-01
Air Flow: 500 CFM
SPECIFICATIONS:
Material: Double Skin insulated material
750 Pressure Drop: 150 Pa
Both sides flanges to connect between the ducts
Size of Housing Box: 750W x 750H x 600L
Weight : 140 Kg
750

FILTER DIMENSIONS:
Stage 1 - PLEATED FILTER (24"x24"x2") - 1 Nos
Stage 2 - CARBON FILTER (24"x24"x12") - 1 Nos
SECTION VIEW
Stage 1 (Pre Filter)
Stage 2 (Carbon Filter)
600 PROJECT NAME:

AIR OUTLET
COCO PARIS - TDM
AIR INLET

AIR OUTLET
AIR INLET
DRAWING TITLE:
ODOUR CONTROL UNIT

750

750
FOR ECOLOGY UNIT
DRAWN: CHECKED: APPROVED: DATE:
KR NKV
SCALE: PROJECT NO: DRAWING NO: REVISION
NTS
AVANTE UAE
TOP VIEW FRONT VIEW Ventilation Specialist
Dubai, UAE


 


SECTION -4


FILTER DETAILS







 
  















MetaNet®
Lightweight metal filters for heavy duty applications,
HVAC systems and kitchen hoods

• Reduces maintenance costs

• High dust holding capacity and long


service life

• Lightweight and easy to install

• Washable

• Average arrestance: 75 - 85%


according
to EN779

MetaNet® are washable metal air filters for In addition, MetaNet® air filters can be and aluminium sheet execution.
use in heavy duty industrial applications used as prefilters to more expensive higher Sturdy, Rigid Construction
and in commercial and industrial heating, effi-ciency filters. The filters are available To ensure complete filter integrity in
ventilation and air conditioning systems. in the classification range G2, but when difficult operating conditions, the filter frame
Owing to their excellent dust holding coated with AAF’s special dirt trap adhesive, is made of sturdy galvanized steel. The
capacity and ability to perform in high Viscosine, the filters qualify for G3 classifi- multi-layered media is held in place by metal
moisture conditions they are particularly cation according to the EN779 standard. grids on both the air inlet and air outlet
suitable for use as grease filters in kitchen sides. This construction
hoods. Multiple Layered Media Holds increases filter rigidity and ensures filter
Their ability to reduce grease deposits on performance in heavy dust loading
fixtures and duct work has many cost saving More Dust applications. The frame is also available in a
benefits: MetaNet® filter media consists of multiple stainless steel and aluminium execution.
layers of pleated galvanized wire formed into
• reduces frequency of duct cleaning a compact maze of dirt catching surfaces.
This multiple layer design creates an Easy to clean and install
maintenance MetaNet® filters are easy to install.
• reduces the risk of fire effective dust holding barrier for dust laden
particles while allowing clean air particles to The filters can be washed in a solution of
prolongs the life span of fans and motors detergent and warm water or cleaned with
• promotes health and safety in kitchens move through the media unhindered. The
media is also available in a stainless steel compressed air.

Better Air is Our Business ®


MetaNet®

Technical specification
Filter Type Code Filter Type Code Filter Type Code
Galvanized steel 1111 Stainless steel 2626 Aluminium 3737
Code description: Code description: Code description:
1. U-profile; galvanized steel, 2. U-profile; stainless steel, 3. U-profile; aluminium,
1 mm thick. 1 mm thick. 1 mm thick.
1. Support grid air entering side; 6. Support grid air entering side; 7. Support grid air entering side;
galvanized steel, mesh stainless steel, expanded aluminium, expanded
1. Media; multiple layers of 2. Media; multiple layers of 3. Media; multiple layers of
knitted galvanized steel knitted stainless steel knitted aluminium steel
1. Support grid air leaving side; 6. Support grid air leaving side; 7. Support grid air leaving side;
galvanized steel, mesh stainless steel, expanded aluminium, expanded
Temperature limit: 420˚C Temperature limit: 500˚C Temperature limit: 300˚C

Technical Data
Nominal Size Actual Size Rated air velocity Tolerance on:
inches mm m3/h at 2.5 m/s - Width and height : +0 mm;
-1 mm.
20x10x2 495x245x48 1170
16x20x2 395x495x48 1870 - Thickness : ± 0.5 mm.
20x20x2 495x495x48 2380
16x25x2 395x620x48 2380
20x25x2 495x620x48 2975
24x24x2 595x595x48 3400
Note: Also available in 20 mm depth

Airflow Resistance
Initial Resistance (Pa) (

30

25

20
48
595mmx depth
595 mm
15

10

5
0
0 0.75 1.5 2.25 3.0
Face velocity (m/s)
Recommended final resistance: 130 Pa.

AAF-International B.V. International AAF Offices: Suzhou, Shenzhen (PRC), Singapore,


P.O. Box 7928 Amsterdam (NL), Athens (GR), Brussels (B), Taiwan, Vienna (A)
1008 AC Amsterdam Cramlington (GB), Dortmund (D), Dubai
The Netherlands (UAE), Helsinki (Fin), Istanbul (TR), Lisbon AAF Agents:
Tel.: + 31 20 549 44 11 (P), Louisville, Ky (USA), Madrid (E), Mexico Johannesburg (RSA)
Fax: + 31 20 644 43 98 (Mex), Mozzate-Co (I), Paris (F), Bangalore
www.aafeurope.com (IND), Riyadh (KSA), Shah Alam (Mal),

AAF has a policy of continuous product research and improvement and reserves the right to change design
and specifications without notice.
RA-3-129-IN-0307 © 2007 AAF International
THE WORLD LEADER IN CLEAN AIR SOLUTIONS

PREpleat LPD HC
(Low Pressure Drop, High Capacity)
EXTENDED SURFACE PLEATED PANEL FILTERS

• Lowest initial resistance MERV 8 (PYÄS[LYZHYLKLZPNULKMVYK\Z[OVSKPUN


WSLH[LKÄS[LYPU[OLPUK\Z[Y` WYLZZ\YLKYVWHUK4,9=YH[PUN((-
-SHUKLYZ»79,WSLH[37+/*ÄS[LYPZ[OL
• /PNO+\Z[/VSKPUN*HWHJP[`+/* lowest initial resistance MERV 8 pleated
MVYLULYN`LѝJPLU[WLYMVYTHUJL ÄS[LYPU[OLPUK\Z[Y`*VTIPULK^P[OP[Z
• ,JVSVNPJHSS`MYPLUKS`MYHTL OPNO+/*[OL79,WSLH[37+/*ÄS[LY
JVTWVULU[ZTHKLMYVT WYV]PKLZHUL_[LUKLKSPMLJ`JSLHUK
YLJ`JSHISLTH[LYPHSZ LULYN`LѝJPLU[WLYMVYTHUJL

• ,_WHUKLKTL[HSNYPKTHPU[HPUZ
Superior Design and Construction
WSLH[ZOHWLK\YPUNVWLYH[PVUMVY
M\SSTLKPH\[PSPaH[PVUHUKOPNO+/* Media: Z`U[OL[PJUVU^V]LUWYVWYPL[HY`TLKPH[OH[JHUILYLJ`JSLK
,UNPULLYLK^P[OHNYHKPLU[KLUZP[`JVTWVZP[PVU[OH[HJOPL]LZH4,9=YH[PUN
• +PHNVUHSZ\WWVY[TLTILYZHUK \ZPUN[OLTLJOHUPJHSTL[OVKVMWHY[PJSLJHW[\YL4LKPHKVLZUV[YLS`VUHU
^PYLIHJRLKTLKPHJVU[YPI\[L[V LSLJ[YVZ[H[PJJOHYNL[VJHW[\YLWHY[PJ\SH[LZPUJLLSLJ[YVZ[H[PJJOHYNLKPZZPWH[LZ
V]LYHSSZ[YLUN[OVMJVUZ[Y\J[PVU V]LY[PTL

• -PS[LYTLKPHWHJRPZIVUKLK[V[OL Media Support:,_WHUKLKTL[HSPZJVU[PU\V\ZS`SHTPUH[LKVU[OLHPYSLH]PUN


MYHTLH[HSSWVPU[ZVMJVU[HJ[[V ZPKL[VWYV]PKLWSLH[Z[HIPSP[`K\YPUNVWLYH[PVU7SLH[ZOHWLPZTHPU[HPULK
LSPTPUH[LHPYI`WHZZ HSSV^PUNM\SSTLKPH\[PSPaH[PVU^OPJOTH_PTPaLZ+/*
Pleat Design:=7SLH[KLZPNUHPKZPUWYLZZ\YLKYVW^OPSLYLK\JPUNLULYN`
• MERV 8
JVZ[+LZPNUHSSV^ZMVYTH_PT\THPYÅV^HUK+/*K\YPUN[OLSPMLVM[OLÄS[LY
Frame:/LH]`K\[`[^VWPLJLTVPZ[\YLYLZPZ[HU[MYHTL^P[OKPHNVUHS
Z\WWVY[TLTILYZ-YHTLPZIVUKLK[V[OLTLKPHH[HSSWVPU[ZVMJVU[HJ[MVY
\UZ\YWHZZLKMYHTLZ[YLUN[O0U[LYSVJRPUNJVYULYZHUKWVZP[P]LTLKPH[VMYHTL
ZLHSYLK\JL[OLWVZZPIPSP[`VMHPYI`WHZZ
Operating Temperature Limits:4H_PT\TVWLYH[PUN[LTWLYH[\YLPZ
‡-‡*

Applications
;OL79,WSLH[37+/*OPNOJHWHJP[`WSLH[LKWHULSÄS[LYZHYLL_JLSSLU[
WYLÄS[LYZHUKHYLILZ[Z\P[LKMVYOLH]`K\[`JVTTLYJPHSPUK\Z[YPHS
WOHYTHJL\[PJHSHWWSPJH[PVUZHZ^LSSHZV[OLYPUK\Z[YPHSHWWSPJH[PVUZ^OLYLOPNO
K\Z[OVSKPUNPZYLX\PYLK79,WSLH[37+/*ÄS[LYZJHUILPUZ[HSSLKPUIV[OMYVU[
HJJLZZOVSKPUNMYHTLZHUKZPKLHJJLZZOV\ZPUNZ
®

PREpleat LPD HC Filters


Performance Data

Pleats Rated Initial Resistance Recommended


Per (in. w.g.) Final Resistance ASHRAE 52.2 Continuous Operating
Filter Linear Foot 300 FPM 500 FPM (in. w.g.) MERV Temperature Limits
ґ79,WSLH[37+/* 15  –  8 ‡-‡*
ґ79,WSLH[37+/* 15    8 ‡-‡*
ґ79,WSLH[37+/*     8 ‡-‡*

All performance data based on ASHRAE Standard 52.2. Performance tolerance conforms to Section 6.4 of ANSI/AHRI Standard 850-2013.
<UKLY^YP[LYZ3HIVYH[VYPLZ*SHZZPÄJH[PVU¶79,WSLH[ÄS[LYZHYL<3*SHZZPÄLK;LZ[PUN^HZWLYMVYTLKHJJVYKPUN[V<3:[HUKHYK 

*VTWVZP[L4PUPT\T,ɉJPLUJ`*\Y]L Product Information – Standard Sizes


,ѝJPLUJ`]Z7HY[PJSL:PaL Nominal Sizes Actual Sizes 9H[LK(PYÅV^ Pleats Gross
 (Inches) (Inches) (SCFM) Per Media Area
 (W x H x D) (W x H x D) 300 FPM 500 FPM 625 FPM Filter (sq. ft.)

 12 x 24 x 1 113⁄ 8 x 233⁄ 8 x ¾ 600 1000 – 14 3.7


14 x 20 x 1 13½ x 19 ½ x ¾ 600 950 – 17 3.7


,ѝJPLUJ` 

14 x 25 x 1 13½ x 24½ x ¾ 750 1200 – 17 4.6


 16 x 20 x 1 15½ x 19 ½ x ¾ 650 1100 – 19 4.1
 16 x 25 x 1 15½ x 24½ x ¾ 850 1400 – 19 5.2
 18 x 24 x 1 17 ½ x 23½ x ¾ 900 1500 – 22 5.7
18 x 25 x 1 17½ x 24½ x ¾ 950 1550 – 22 5.9

20 x 20 x 1 19 ½ x 19 ½ x ¾ 850 1400 – 24 5.1
 20 x 24 x 1 19 ½ x 23½ x ¾ 1000 1650 – 24 6.2
 20 x 25 x 1 19 ½ x 24½ x ¾ 1050 1750 – 24 6.4
 24 x 24 x 1 233⁄ 8 x 233⁄ 8 x ¾ 1200 2000 – 29 7.4
                25 x 25 x 1 24½ x 24½ x ¾ 1300 2150 – 31 8.3
7HY[PJSL:PaLэT 12 x 24 x 2 113⁄ 8 x 233⁄ 8 x 1¾ 600 1000 1250 14 8.7
14 x 20 x 2 13½ x 19 ½ x 1¾ 600 950 1150 17 8.6
14 x 25 x 2 13½ x 24½ x 1¾ 750 1200 1500 17 10.8
Initial Resistance vs. Filter Face Velocity 16 x 20 x 2 15½ x 19½ x 1¾ 650 1100 1400 19 9.6
16 x 25 x 2 15½ x 24½ x 1¾ 850 1400 1750 19 12.0
18 x 24 x 2 17½ x 23½ x 1¾ 900 1500 1900 22 13.3

18 x 25 x 2 17½ x 24½ x 1¾ 950 1550 1950 22 13.8
20 x 20 x 2 850 1400 1750 24 12.0
0UP[PHS9LZPZ[HUJLPU^N

19½ x 19½ x 1¾
 20 x 24 x 2 19½ x 23½ x 1¾ 1000 1650 2100 24 14.4
20 x 25 x 2 19½ x 24½ x 1¾ 1050 1750 2150 24 15.0
 24 x 24 x 2 233⁄ 8 x 233⁄ 8 x 1¾ 1200 2000 2500 29 17.3
.25 12 x 24 x 4 113⁄ 8 x 233⁄ 8 x 3¾ 600 1000 1250 11 16.5
 ̯ ̯ .19 16 x 20 x 4 15½ x 19½ x 3¾ 650 1000 1400 16 18.0
16 x 25 x 4 15½ x 24½ x 3¾ 850 1400 1750 16 22.6
.17 900 1500 1875
18 x 24 x 4 17½ x 23½ x 3¾ 18 24.2
 20 x 20 x 4 19½ x 19½ x 3¾ 850 1400 1750 19 22.3
̯ 20 x 24 x 4 19½ x 23½ x 3¾ 1000 1650 2100 19 24.0
 20 x 25 x 4 19½ x 24½ x 3¾ 1050 1750 2150 19 27.7
   
   24 x 24 x 4 233⁄ 8 x 233⁄ 8 x 3¾ 1200 2000 2500 23 28.8
-PS[LY-HJL=LSVJP[`-74
,ULYN`ZH]PUNZTH`ILYLHSPaLKI`VWLYH[PUN[OL79,WSLH[37+/*ÄS[LYZ[V
HSV^LYÄUHSYLZPZ[HUJL*VU[HJ[`V\YSVJHS((--SHUKLYZYLWYLZLU[H[P]LMVY
H;V[HS*VZ[VM6^ULYZOPWHUHS`ZPZMVY`V\YZWLJPÄJHWWSPJH[PVU
PREpleat ®PZHYLNPZ[LYLK[YHKLTHYRVM-SHUKLYZ*VYWVYH[PVUPU[OL<:

AAF Flanders has a policy of continuous product


research and improvement and reserves the right to
change design and specifications without notice.

©2017 AAF International and its affiliated companies.


9920 Corporate Campus Drive, Suite 2200, Louisville, KY 40223-5690
888.223.2003 Fax 888.223.6500 | aafintl.com ISO Certified Firm AFP-1-379 01/17
DriPak® GF
Glass Fibre Pocket Filters for HVAC Applications

• Filter classes F5-F9 meet the clean air


requirements of numerous industrial
and commercial applications

• Low resistance to airflow

• High dust holding capacity and long


service life

• Outstanding performance in difficult


operation conditions

Unique Design, Unparalleled High Quality Glass Fibre Media Efficiency Ranges
Performance DriPak microfine glass fibre media has a The DriPak range of glass fibre filters is
DriPak glass fibre media consists of an proven reputation for high quality air filtration available in five efficiency ranges:
unique blend of coarse and fine glass fibres, performance. EN 779 Media Colour
specially designed and interwoven to provide
F9 White
a low initial resistance and high air cleaning The media is strong and can withstand
performance. turbulent airflow and repeated fan shut F8 Yellow
down. F7 Pink
The coarse fibres arrest the larger, heavier F6 Amber
particles in the airstream while the fine fibres DriPak filters display exellent dust holding F5 Green
remove the smaller particulate matter and capacity and have a long service life.
give the filter its high efficiency classification. Today, these unique products are being Final Resistance
used to satisfy the clean air requirements DriPak filters are tested in accordance
The media is covered by a thin layer of of hospitals, office blocks, manufacturing with EN779:2002. The recommended final
spunbond scrim which serves to increase plants, and public buildings all around the resistance if 450 Pa is for classification
filter strength and efficiency. world. purpose. Temperature limit, continuous 70ºC.
DriPak® GF

DriPak F8/F9
225
Rated Face Actual Number Gross Media Rated Airflow Rated
Capacity
A
200
C
Velocity1 Size4/5) of Area Initial2/3)
Initial Resistance (Pa)

B
175 (m/s) (WxHxD) (mm) pockets (m2) (m3/h) Resistance (Pa)
150
125 Filter classification2) - F 9
100
2,5 592x592x700 10 9.4 3400 130
75
50
287x592x700 5 4.7 1700 130
25 490x592x700 8 7.5 2850 130
0
0.5 1.0 1.5 2.0 2.5 3.0 3.5
Filter classification2) - F 8
A= 8 pockets, 635 mm long, F8
B= 9 pockets, 700 mm long, F8 Face Velocity (m/s)
592x592x700 9 8.1 4250 195
C=10 pockets, 700 mm long, F9 3.2 287x592x700 4 3.7 2125 195
490x592x700 7 6.3 3550 195
592x592x635 8 6.7 3400 165
DriPak F7
2.5 287x592x635 4 3.3 1700 165
225
490x592x635 6 5.0 2850 165
200
592x592x508 6 4.1 1700 114
Initial Resistance (Pa)

175
150
A 1.25 287x592x508 3 2.0 850 114
125
B
490x592x508 5 3.4 1400 114
100 Filter classification2) - F 7
75
50 592x592x700 9 8.1 4250 140
25 3.2 287x592x700 4 3.7 2125 140
0 490x592x700 7 6.3 3550 140
0.5 1.0 1.5 2.0 2.5 3.0 3.5
592x592x635 8 6.7 3400 115
A= 8 pockets, 635 mm long
B= 9 pockets, 700 mm long Face Velocity (m/s) 2.5 287x592x635 4 3.3 1700 115
490x592x635 6 5.0 2850 115
592x592x508 6 4.1 1700 80
DriPak F6
1.25 287x592x508 3 2.0 850 80
490x592x508 5 3.4 1400 80
120
Initial Resistance (Pa)

Filter classification2) - F 6
A
90 3.2 592x592x700 9 8.1 4250 75
B
287x592x700 4 3.7 2125 75
60
490x592x700 7 6.3 3550 75
30
2.5 592x592x635 8 6.7 3400 60
287x592x635 4 3.3 1700 60
0 490x592x635 6 5.0 2850 60
0.5 1.0 1.5 2.0 2.5 3.0 3.5
A= 8 pockets, 635 mm long
Filter classification2) - F 5
Face Velocity (m/s)
B= 9 pockets, 700 mm long 592x592x635 6 5.0 3400 50
2.5
287x592x635 3 2.5 1700 50
DriPak F5 490x592x635 5 4.3 2850 50
592x592x508 6 4.1 3400 55
2.5
120 287x592x508 3 2.0 1700 55
Initial Resistance (Pa)

490x592x508 5 3.4 2850 55


A
90
592x592x305 6 2.4 3400 65
2.5
B 287x592x305 3 1.2 1700 65
60
490x592x305 5 2.0 2850 65
30 Notes:
1) Filters can be operated at 67% to 133% of rated face velocity.
0 2) All performance data based on EN 779:2002.
0.5 1.0 1.5 2.0 2.5 3.0 3.5 3) The final resistance of 450 Pa is for classification purpose.
A= 6 pockets, 305 mm long 4) The DriPak filter sizes fit into frame sizes 610 x 610, 305 x 610 and 508 x 610 mm.
Face Velocity (m/s)
B= 6 pockets, 635 mm long 5) Filters are also available with 25 and 20 mm metal header.
6) Other sizes upon application.

AAF is participating in the Eurovent Certification Programme for Air Filters. The “Fine Filter range” acc. to EN 779 is certified under
the number (07.01.333) and presented in the Directory of Certified Aif Filters on Eurovent website: www.eurovent-certification.com
AAF-International B.V. International AAF Offices: Suzhou, Shenzhen (PRC), Singapore,
P.O. Box 7928 Amsterdam (NL), Athens (GR), Brussels (B), Taiwan, Vienna (A)
1008 AC Amsterdam Cramlington (GB), Dortmund (D), Dubai
The Netherlands (UAE), Helsinki (Fin), Istanbul (TR), Lisbon AAF Agents:
Tel.: + 31 20 549 44 11 (P), Louisville, Ky (USA), Madrid (E), Mexico Johannesburg (RSA)
Fax: + 31 20 644 43 98 (Mex), Mozzate-Co (I), Paris (F), Bangalore
www.aafeurope.com (IND), Riyadh (KSA), Shah Alam (Mal),

AAF has a policy of continuous product research and improvement and reserves the right to change design
and specifications without notice.
RA-5-543-IN-0609 © 2009 AAF International
VariSorbTM XL Chemical Filter
Pleated Compact Filter

• Standard Dimensions

• Sturdy Construction

• Corrosion-free,
non-metal construction

• Fully incinerable

• Free of halogens

• For Fresh Air AHU and


Recirculation Units

Construction layers. The pleat packs are arranged in a V- impregnated SAAFCarb media, SAAFOxidant
VariSorb XL delivery system consist of filter shape to utilize maximum amounts of media for and SAAF Blend. For details consults our
elements in high impact polystyrene (HIPS) cell the given face area. Each VariSorb is plastic Chemical Media brochure.
sides for assembly in front or rear access bagged and carton packed.
standardized universal holding frames or side- Application Guide
access track systems to fit standard dimension Spontaneity and Yield Always use adequate prefiltration to avoid dust
filter sections in air handling units. Unlike traditional granular bed chemical filters, settling on the chemical media. This ensures
VariSorb XL comes factory-ready for installation. the granular microstructure ensures a much optimized lifetime of the chemical filter system
No special tools are needed to install or replace higher effective active area per kg of media, without increase of pressure drop. Prefiltration
the filter element. The individual VariSorb XL resulting in a high spontaneity of reaction. should be a compact, pleated or mini-pleated
seals and holds in the frame with the latching Combined with the dense packing of the filter cell.
system or in the track with its header and the microstructure, this creates a tortuous path for
Prefiltration to
track-specific gasket system. Side seals gaskets the contaminant, resulting in a high yield for the F7
EN779:2002
are supplied upon request. filter. The construction greatly reduces pressure Relative Humidity < 95%
drop, eliminates by-pass and abrasion. The
Temperature < 55 °C
Filter Elements entire VariSorb can easily be disposed-off and
VariSorb XL filters are designed for effective is fully incinerable. Always follow the local, state Service
gas-phase removal of medium and low or federal regulations for disposal. AAF International will be pleased to offer you a
concentrations of gas-phase contamination in maintenance contract for your chemical filter
fresh air and recirculation air handling systems. Choice of Media system. This includes removal of the used
HIPS cell sides are fitted with pleated packs, VariSorb can be supplied with a wide range elements, cleaning of the installation and
comprising micro granulate media embedded of gas specific media or custom blends. installation of new elements. Disposal in
between two non-woven synthetic support These include standard SAAFCarb media, accordance with regulations is part of our scope.

Better Air is Our Business ®


VariSorb™ XL Chemical Filter

Specifications

Maximum operating temperature < 55°C


Maximum relative humidity < 95 % r.H.
Media Mini-granulate, embedded in fibermat
Cell Sides High Impact Polystyrene (HIPS)
Disposal Incineration

Technical Data
1)
Type Dimensions Airflow Initial Resistance
mm (m3/h) at Nominal
(HxWxD) Nominal Maximum Airflow (Pa)
VSXL- 24.24.12 592 x 592 x 292 1700 3400 45
VSXL- 12.24.12 287 x 592 x 292 850 1700 45
Notes
1)
Width and height are interchangeable; pleats can be either vertical or horizontal without affecting performance.

Media Initial Resistance vs. Face Velocity


100
90
80
Type Application Contaminants 70
60
50
SAAFCarb Airports, Pharma & Food Hydrocarbons 50
40

SAAFCarb MA Industry Mineral acids


30
20
10

SAAFCarb MB Industry Ammonia, amines 0


0 0,5 1 1,5 2 2,5 3

Face Velocity (m/s)


SAAFCarb MS Industry & Waste water H2S, SO2

Legend
Type VSXL SAAF VariSorb XL
Nominal size code (inch) 242412 Nominal sizes are 12,20,24
Always 12” deep
Header - 25 mm header
A 20 mm header

Media - SAAFCarb
MA SAAFCarb MA
MB SAAFCarb MB
MS SAAFCarb MS

EXAMPLE: SAAF VariSorb with SAAFCarb MA size 24x24x12 VSXL-242412- MA

AAF-International B.V. International AAF Offices: AAF Agents:


P.O. Box 7928 Amsterdam (NL), Athens (GR), Brussels (B), Cramlington Johannesburg (RSA)
1008 AC Amsterdam (GB), Dortmund (D), Dubai (UAE), Helsinki (Fin), Istanbul
The Netherlands (TR), Lisbon (P), Louisville, Ky (USA), Madrid (E), Mexico
Tel.: + 31 20 549 44 11 (Mex), Mozzate-Co (I), Paris (F), Bangalore (IND), Riyadh
Fax: + 31 20 644 43 98 (KSA), Shah Alam (Mal), Suzhou, Shenzhen (PRC),
www.aafeurope.com Singapore, Taiwan, Vienna (A)

AAF has a policy of continuous product research and improvement and reserves the right to change design
and specifications without notice.
GPF 2 005 IN 0107 © 2007 AAF International


 


 -6
SECTION


FAN SELECTION







  

CMB/CMT
CMT/4-280/115-LG270-2.2KW-3-230/400V-50HZ
Single inlet centrifugal fan direct driven , forward curved for continous extraction of airstreams temperature up to 150ºC. Manufactured from galvanised sheet steel
painted with epoxy polyester. Three phase motor. Brand S&P model CMT/4-280/115-LG270-2.2kW-3-230/400V-50Hz for an airflow 504 cfm and static pressure
610 Pa.

Project: Nirmal AVAnte (rev. 1 (4)) - Reference: Coco Paris

Theoretical Working Point Performance Chart


Airflow 500 cfm 800
Static Pressure 600 Pa
Temperature 20 °C
700
Altitude 0m
Density 1,2 kg/m³
Frequency 50 Hz 600
Voltage 3-230/400V-50Hz

Working Point 500

Static Pressure (Pa)


Airflow 504 cfm
Static Pressure 610 Pa
Dynamic pressure 11,2 Pa 400
Total Pressure 622 Pa
Output power 1,86 kW
300
Outlet speed 4,3 m/s
Fan speed 1430 rpm
400V
Specific Fan Power 7,79 W/l/s 200
Specific Fan Power reg 7,69 W/l/s

Construction 100
Fan size 280/115
Weight 43,00 kg
0
Motor Characteristics 0 500 1000 1500 2000 2500 3000 3500
Number of poles 4
Q- Airflow (cfm)
Motor Power 2,2 kW
Voltage 3-230/400V-50Hz
Maximum absorbed current 8,1 A / 4,6 A
IP Rating IP55 Sound Performance
Motor insulation class F
63 125 250 500 1k 2k 4k 8k Overall
Drawing
Inlet (LwA) 59 72 78 79 84 85 81 78 90

Inlet LpA @ 3m 38 51 57 58 63 64 60 57 69

Outlet (LwA) 59 72 78 79 84 85 81 78 90

Outlet LpA @ 3m 38 51 57 58 63 64 60 57 69

A B C D E F G H I K L M N P Q R S T U V

471 553 300 184 184 300 220 170 243 293 320 216 340 363 10 245 275 240 95 66

S&P Sistemas de Ventilación, S.L.U / 08150 Parets del Vallès, Barcelona, ??España / Teléfono 93.571.93.00 Fax 93.571.93.01 /e-mail: consultas@solerpalau.com 3/6
11/22/2018, 8:57:27 AM
CMB/CMT
CMT/4-280/115-LG270-2.2KW-3-230/400V-50HZ
Project: Nirmal AVAnte (rev. 1 (4)) - Reference: Coco Paris

Drawing

A B C D E F G H I K L M N P Q R S T U V

471 553 300 184 184 300 220 170 243 293 320 216 340 363 10 245 275 240 95 66

S&P Sistemas de Ventilación, S.L.U / 08150 Parets del Vallès, Barcelona, ??España / Teléfono 93.571.93.00 Fax 93.571.93.01 /e-mail: consultas@solerpalau.com 4/6
11/22/2018, 8:57:27 AM