Beruflich Dokumente
Kultur Dokumente
DOC-DSS-000004-01
21/074/11
GANTRY FEATURES
General
The gantry is a self contained unit that houses all the
devices and systems to provide loading of product from a Full compliance and inspection to Australian Standards.
tank to truck (less pumps). Lifting lugs are provided for Structure design has been fully developed for use in
crane use. Tropical/Hurricane prone regions. AS Zone 4 cyclone
rating.
Truck Connection
Single 4” female API coupling per loading arm for Pipework
connection to the truck. All pipework constructed to International Standards ASME /
ANSI.
Additives
Additive controllers are connected to the Load Controller via
serial communications. The maximum number of additive GANTRY ENVIRONMENT
per loading controller (AccuLoad III) is twenty four.
Gantries can be located in a Zone 1 Class 1 hazardous area
3 Additive Injection Points standard per arm, optional up to location requiring Exd, Exi or EXMe rated products. All
maximum per controller (24) shared amongst arms. products used shall have SAA approval. Copies of
certificates shall be provided as part of the project
Vapour Removal documentation.
Vapour removal components complete with frame arrestor
and intrinsically safe interlock sensors. Design Temperature
Minimum Design Temperature = -10 Deg C
Safety
Maximum Design Temperature = +50 Deg C
Emergency Stop button located either end of module.
Deadman system available as option. Ingress Protection
Earth / Overfill IP65
Industry standard 10 pin overfill protection system with
Zone
integrated earth check.
Zone 1
Structural Class 1
All framework is Hot Dip Galvanised for maximum
environmental protection.
Page 1 of 5
“Mutual Success Through Teamwork With Customers”
Specifications stated are subject to change without notice. Diamond Key International Pty Limited accepts no liability of any kind for errors or omissions
Bottom Loading Modules
DOC-DSS-000004-01
21/07/11
PRODUCTS ON MODULE
Main products used on the gantry are:
Denotes:
Y = Available
N = not available
1 = based on product
2 = have Viton Seals
3 = Exe Housing for interfacing gantry instrumentation to field connections
4 = Exd Housing for IS barrier devices and fibre optic Connections
5 = Meter used determined by product being loaded and flow rates
6 = If gantry used with Omega TAS system
Page 2 of 5
“Mutual Success Through Teamwork With Customers”
Bottom Loading Modules
DOC-DSS-000004-01
21/07/11
Page 3 of 5
“Mutual Success Through Teamwork With Customers”
Bottom Loading Modules
DOC-DSS-000004-01
15/01/09
Page 4 of 5
“Mutual Success Through Teamwork With Customers”
Bottom Loading Modules
DOC-DSS-000004-01
21/07/11
Cabling
PHYSICAL CHARACTERISTICS All cabling is steel wire armoured to ensure maximum
mechanical protection, with intrinsically safe cables being
Weight (2 Arm RA Gantry)(kg) identified.
Dry: 2,500 All gantry wiring is terminated to the Exe field termination
box. Any cable that is glanded into an Ex‟d enclosure will
Wet: 2,800 (dependent on specific gravity of liquid type)
use Barrier Glands. All other field wiring may be
conveniently terminated to this point.
Weight (6 Arm Slimline Gantry)(kg)
Dry: 4,500 Fibre Cable & Connections
Wet: 5,500 (dependent on specific gravity of liquid type) If the gantry is used in conjunction with Omega TAS fibre
cables need to be laid between the gantry and the Control
Steel Work Construction - AS 4100 Room.
Fibre cable shall be:
Galvanising - AS1650
Optical wavelength: 850nm nominal
Pipework - ASME IX 2001 Connectors: ST connectors
Type: 2 off twin cores as a minimum
Painting
Recommended: DKI recommends additional
All pipe work is prepared for painting by shot blasting and/or cores are included for spares.
sandblasting to AS1627.4 class 2.5 and is primed with
appropriate primer for top coat. Product Input Pressures
Top coat: Two Pack re-coatable polyurethane enamel Main Base Products
Colour: RAL 7031 Blue Grey Typical: 500 – 600 kPa static
The three coat process is fully maintained to AS/NZS ISO Minimum: 250 kPa @ 2400 LPM
9001-2008.
Other by special request.
Additive Products
Painting – Supplied Products Typical: 1100 kPa static
To suppliers standard paint codes and colours unless other Note: Differential pressure of additives to main
by special request product must be greater than 310 kPa at all
times.
Compressed Air Requirement
At least 550Kpa. The air connection ½” NPT
Process Connection
All main piping connections are flanged 4” ANSI 150.
Electrical
240v AC, 50Hz single phase electrical power rated at 500
Watts
Power connections to the AccuLoad Controller shall be via a
Uninterruptible Power Supply with suitable capacity to
provide power to the AccuLoad unit for 30 minutes after a
supply failure and an alarm system for notifying of a low
battery.
Reference is made of Australian National Standards
Commission Certificate Number S413 – section 1.5
Diamond Key International Pty Limited A.C.N. 082 814 168 A.B.N. 86 082 814 168 www.diamondkey.com
Head Office: Postal Address: E-mail: Telephone: + 61 3 9730 8888
110 Henderson Rd P.O. Box 2813 sales@diamondkey.com Facsimile: + 61 3 9764 9931
Rowville, Victoria 3178 Rowville, Victoria 3178 support@diamondkey.com Support: (Int) + 61 3 9730 8801
Australia Australia (Aus) 1 800 33 33 1