IS 3034 : 1993

8.5 Turbo-Generators and Supporting 8.5.6 The internal hydrant (landing valves)
Structures shall be provided for protection of the turbo-
8.5.1 The fixed water spray type protection generator building including turbine operating
system shall be used for controlling a fire floors and basement areas.
involving large quantities of lubricating oil on 8.5.7 The hydrant system shall have sufficient
turbine generators. This shall consist of two pressure to allow the generation of low
systems of water protection, one for areas below expansion foam from hand branches for
the operating floor of the turbo generator and fighting static/running oil fires.
designed to extinguish pool fires and also
providing protection against heat generated by 8.6 Turbine Driven Feed Pumps
three-dimensional or spray fires. The other is a 8.6.1 The fixed high velocity water spray
water spray system for oil fires at or around the system shall cover completely all the systems,
bearing housings. Fixed CO2 or dry chemical
oil pipe to the pumps, coolers and other similar
extinguishing systems have been found to be
inadequate for basic protection of turbo- associated equipment including adjacent floor
generator because of the likelyhood of areas, as for the main turbine. The fire
re-ignition and, further, these extinguishing detection system as well as the water spray
media may not be sufficient to cope with a long system shall be of the same type as for the
duration fire. However, in some cases fixed dry turbo-generator.
chemical or CO2 systems backed by water spray 8.6.2 To enable fire fighting to be successfully
systems should be provided. carried out facilities shall be provided for easy
8.5.2 Fixed high velocity water spray systems, smoke disposal, by provision of sufficient cont-
designed to discharge a flow of 10 lpm/m2 shall rollable top and bottom ventillation.
cover completely all oil systems, oil piping,
pumps, coolers and all similar associated equip- 8.6.3 In the event of a fire involving or close to a
ments including adjacent floor areas. The water turbo-generator or its auxiliaries, it may be safer
spray systems shall be divided into convenient to shut down the unit so as to limit the. damage
zone, and each zone shall have sufficient number only to that directly resulting from the fire.
of projectors to cover the risk adequately. The 8.7 Hydrogen Equipment
number and groups of projection zones are
related to, the size of turbo-generator unit and 8.7.1 Any hydrogen equipment that is sited in
its lubricating plant and auxiliaries. Typical the turbo generator shall be positioned in such
zone arrangements shall cover the following a way that the area and the equipment are well
areas of seal oil systems, coolers and pipe work, ventilated and directed into the open air.
governor gear, excitor, main lubricating tank 8.7.2 Spark free tools shall be used in an area
and pumps, lubricating oil pipe work, turbo where gas may be present.
generator and boiler feed pump, exposed steel
equipment, foundation support legs, rate of rise 8.8 Transformers
fire detectors in accordance with IS 2175 : 1988 8.8.1 No fixed fire protection equipment (such
shall be provided. The heat detectors shall be as high velocity spray) is required on transfor-
provided at strategic points and arranged to give
mers below 10 MVA or in the case of oil filled
early warning of any unusual high temperature
conditions in the area. transformers with oil capacity of 2 000 litres
and below. For all other transformers high
8.5.3 Automatic control of the extinguishing velocity water spray system shall be provided.
systems in this area is more effective than This system shall be separately mounted and
manual control. However, manual over-ride designed to take into account the possibility of
shall also be provided. Zone control deluge
a transformer explosion. The water spray
operating valve shall be carefully sited so as to
be operable without fire or smoke hazard to the deluge valve house shall be located outside the
operator during a fire. This may be achieved by transformer fire zones and protected from
careful location of the valve assemblies away radient heat and other fire effects. The
from protection zones, or by enclosures of the actuation of this system shall be automatic but
valves in protective cubicles, at the same time manual operating valves shall also be provided.
affording the operator a good view of the 8.8.2 The high velocity spray system for the
protected zones. Access routes to control valves transformers should be well designed to have
shall not involve exposure hazards to the adequate coverage of the entire transformer
operating persons. unit including the conservation tanks, the
8.5.4 The water spray systems shall bushings and the bottom area. The positioning
incorporate isolation facilities so as to enable of the nozzles should be such to protect all
periodic testing, maintenance etc. surfaces of the transformer and to give
8.5.5 Normally all cut off valves shall be locked discharge rate for the system not less than
open. 10 lpm/m2 of the area to be protected. The