Sie sind auf Seite 1von 7

Type test verification - 24kV ABB Power Distribution

SafePlus (CSG) November 2, 2001

Type Test Verification.

Product: Compact Switchgear type SafePlus


Manufacture: ABB Kraft, Skien, Norway
Ratings: 24 kV, 630 A, 21 kA 3 s

Doc. version: Last update, 10 May 2000

This verification document is a statement of type tests which have been performed on the compact switchgear type SafePlus under the
surveillance of SATS/STL. All tests have been carried out according to relevant IEC Publications and other significant specifications.
Switch unit, C - module:
Type of test Specific. Test result Report no.
1.0 Mech.Endurance IEC 60265
1.1 Switch manual 1000CO 99-B16
1.2 Earthing Switch 1000CO 99-B16

2.0 Dielectric tests IEC 60298/60265


2.1 Lightning Impulse 125/145 kV 99-B19
2.2 Power frequncy 1 min. 50/60 kV 99-B19
2.3 P.D. measurement 26.4 kV/5 pC 99-B19

3.0 Short-Circuit tests IEC 60298/60265


3.1 Main circuit and Switch 40 kApeak 99-B14
16 kArms 3 s
52.5 kApeak 00-B02
21 kArms 3 s
3.2 Earthing Switch 40 kApeak 99-B14
16 kA 3 s
52.5 kApeak 00-B02
21 kArms 3 s

4.0 Make-Break tests


4.1 TD1 active load IEC 60265 E3 100CO 630 A 99-B07
4.2 TD2a closed loop IEC 60265 E3 630 A 99-B07
4.3 TD4a, 4c,4d capacitive IEC 60265 E3 135 A 99-B07
4.4 TD6a earth fault IEC 60265 E3 150 A 99-B07
4.5 TD6b e.f. cable charg. IEC 60265 E3 87 A 99-B07

5.0 Making tests


5.1 TD5 Switch IEC 60265 E3 5C 99-A07
40kApeak
5C BY E-
52.5 kApeak 2224Ea
5.2 TD5 Earthing Switch IEC 60265 E3 5C 99-A07
40 kApeak
5C BY E-2224E
52.5 kApeak

6.0 Temperature Rise tests


6.1 Main circuit/Switch IEC 60298/60265 630 A 99-B01

7.0 Mech. operating tests

7.1 Gas leakage test IEC 60298 0,25%p.a 99-B16


7.2 Interlocks IEC 60298 50CO 99-B22
7.3 Submersion test UNESA 24 hrs. 24 kV 99053024A

8.0 Arc fault tests IEC 60298


8.1 without arc surpressor 16 kA 1 s NEFI 1401
8.2 with arc surpressor 20 kA 1s NEFI 1364
8.3 Cable Compartment 16 kA 1 s NEFI 1399
Switch-Fuse unit, F - module:
Type of test Specific. Test result Report no.
1.0 Mech.Endurance IEC 60265
1.1 Switch Fuse manual 1000CO 99-B17
1.2 Earthing switch 1000CO 99-B17

2.0 Dielectric tests IEC 60298/60265


2.1 Lightning Impulse 125/145 kV 99-B20
2.2 Power frequncy 1 min. 50/60 kV 99-B20
2.3 P.D. measurement 26.4 kV/5 pC 99-B20

3.0 Short-Circuit tests IEC 60298/60265


3.1 Downstream Earthing Switch 12.5 kApeak 99-B15
5 kArms 1s

4.0 Make-Break tests


4.1 TD2 max. I2t IEC 60420 CEF63 99-B09
4.2 TD3 long prearcing IEC 60420 CEF63 99-B09
4.3 TD4 transfer current IEC 60420 650 A 99-B09

5.0 Making tests


5.1 TD1 Switch Fuse Combination IEC 60420 16 kA 99-A05
prosp.current
CEF63
5.2 TD5 S.F downstream Earthing Switch IEC 60265 E3 5C 12.5 kApeak 99-B15

6.0 Temperature Rise tests


6.1 Switch Fuse Combination IEC 60420 CEF63 99-B12
50 A

7.0 Mech. operating tests

7.1 Gas leakage test IEC 60298 0,25%p.a 99-B17


7.2 Interlocks IEC 60298 50CO 99-B22

7.3 Submersion test UNESA 24 hrs. 24kV 99053024A

8.0 Arc fault tests IEC 60298


8.1 without arc surpressor 16kA 1 sec NEFI 1401
8.2 with arc surpressor 20kA 1sec NEFI 1364

Vacuum Circuit-Breaker unit, V - module:


Type of test Specific. Test result Report no.
1.0 Mech.Endurance
1.1 Vacuum CB manual IEC 60056 2000CO 000001
1.2 Earthing Switch manual IEC 60129 1000CO 99-B16
1.3 Disconnector manual 1000CO 99-B16
2.0 Dielectric tests IEC 60298/60056
2.1 Lightning Impulse 125/145 kV 980029
2.2 Power frequncy 1 min.
2.3 P.D. measurement
3.0 Short-Circuit tests IEC 60298/60265
3.1 Main circuit and vacuum CB 52,5 kApeak NEFI 1355
21 kA 1sec.
3.2 Earthing Switch 40 kA peak 99-B14
16 kA 3sec

4.0 Make-Break tests


4.1 TD1 10% Isc IEC 60056 1.7 kA KEMA 489-
99
4.2 TD2 30% Isc IEC 60056 4.5 kA KEMA
489-99
4.3 TD3 60% Isc IEC 60056 9.8 kA KEMA
489-99
4.4 TD4 100% Isc IEC 60056 16.1 kA KEMA
489-99

5.0 Making tests


5.1 TD5 downstream Earthing Switch IEC 60265 E3 5C 99-A07
40 kApeak

6.0 Temperature Rise tests IEC 60056


6.1 Vacuum CB 630 A 99-B21

Switch sectionalizer, SL - module:


Type of test Specific. Test result Report no.
1.0 Mech.Endurance IEC 60265
1.1 Switch manual 1000CO 99-B16
1.2 Earthing Switch 1000CO 99-B16

2.0 Dielectric tests IEC 60298/60265


2.1 Lightning Impuls 125/145 kV 000004
2.2 Power frequncy 1 min.
2.3 P.D. measurement

3.0 Short-Circuit tests IEC 60298/60265


3.1 Main circuit and Switch 52,5 kApeak
21 kA 3 s
3.1 Earthing Switch 52.5 kApeak
21kA 3 s

4.0 Make-Break tests


4.1 TD1 active load IEC 60265 E3 100CO 630 A 99-B07
4.2 TD2a closed loop IEC 60265 E3 630 A 99-B07
4.3 TD4a, 4c,4d capacitive IEC 60265 E3 135 A 99-B07
4.4 TD6a earth fault IEC 60265 E3 150 A 99-B07
4.5 TD6b e.f. cable charg. IEC 60265 E3 87 A 99-B07

5.0 Making tests


5.1 TD5 Switch IEC 60265 E3 5C 99-A07
40 kApeak
5C BY E-2224E
52.5 kApeak
5.2 TD5 Earthing Switch IEC 60265 E3 5C 99-A07
40 kApeak
5C BY E-224Ea
52.5 kApeak

6.0 Temperature Rise tests


6.1 Main circuit/Switch IEC 60298/60265 630 A

7.0 Mech. operating tests

7.1 Gas leakage test IEC 60298 0,25%p.a 99-B16


7.2 Interlocks IEC 60298 50CO 99-B22

Circuit-Breaker sectionalizer, SV - module:


Type of test Specific. Test result Report no.
1.0 Mech.Endurance
1.1 Vacuum CB manual IEC 60056 2000CO 000001
1.2 Earthing Switch IEC 60129 1000CO 99-B16
1.3 Disconnector manual 1000CO 99-B16
2.0 Dielectric tests IEC 60298/60056
2.1 Lightning Impuls 125/145 kV 000005
2.2 Power frequncy 1 min.
2.3 P.D. measurement

3.0 Short-Circuit tests IEC 60298/60056


3.1 Main circuit and vacuum CB 52.5 kA
21 kA 3 s
3.2 Earthing Switch 52.5kA
21 kA 3 s

4.0 Make-Break tests IEC 60056


4.1 TD1, 10% Isc 1.7kA KEMA
489-99
4.2 TD2, 30% Isc 4.5kA KEMA
489-99
4.3 TD3, 60% Isc 9.8kA KEMA
489-99
4.4 TD4, 100% Isc 16.1kA KEMA
489-99

5.0 Making tests


5.1 TD5 downstream Earthing Switch IEC 60265 E3 5C 40kApeak 99-A07

6.0 Temperature Rise tests


6.1 Vacuum CB IEC 60056 630 A 99-B21

Metering unit, MA - module:


Type of test Specific. Test result Report no.
1.0 Dielectric tests IEC 298
1.1 Lightning Impuls 125 kV 000054
1.2 Power frequncy 1 min.
1.3 P.D. measurement

2.0 Short-Circuit tests IEC298


2.1 Main circuit 52.5 kA peak NEFI 1413
21 kArms 3 s

3.0 Arc fault tests IEC298


3.1 without arc surpressor 16 kArms 1 s NEFI 1411