Beruflich Dokumente
Kultur Dokumente
Introduction
2
Features
3
Construction Standard Equipment
4
Catalog Numbering Current Transformer Selection
System
Series
IK5 Design with active elements in the dome, porcelain insulator,
0.3% accuracy class,with short-time mechanical and thermal
Catalog numbers are composed ratings as listed on page 4.
of two parts as shown in the IM Same design as IK5 with increased mechanical and short-
example on the right. time thermal current ratings.
IH Denotes Hi-ACC TM High Accuracy 0.15% metering type.
• The TYPE contains the trans- Other features same as IK5 design.
former SERIES designation and BIL (kV) Basic Lightning Impulse Insulation Level.
Primary Amperes Indicates highest nominal primary amperage.
the BIL (kV) rating. In this ex- (Suffix No 1) For example:
ample, IK5-650. 50 A = 500
• The SUFFIX is listed in two parts 200 A = 201
2000 A = 202
PRIMARY AMPERES and RATIO
Ratio Arrangements S- Dual ratio by secondary tap
ARRANGEMENTS. In this (Suffix No 2) Blank- Single ratio
example, 202S. P- Dual ratio by series-parallel
of primary
M- Multi-ratio by secondary tap
IK5-650-202 S
5
Accuracy Selection
Electrical Characteristics
BIL Applied Creepage Strike Thermal Mechanical Short-Time
Series (kV) Withstand Distance Distance Ratio Rating Current Thermal Current
Factor Rating Rating
(kV) in/mm in/mm at 30° C kA RMS Max. (1 sec.) kA RMS
25/50:5 2.0/1.5 4 3
50/100:5 2.0/1.5 8 6
150 50 34/864 13/330 75/150:5 2.0/1.5 12 10
200 70 34/864 13/330 100/200:5 2.0/1.5 15 13
250 95 52/1321 24/610 150/3005 2.0/1.5 24 20
350 140 52/1321 24/610 200/400:5 2.0/1.5 30 26
IK5 550 230 92/2337 40/1016 300/600:5 2.0/1.5 60 39
650 275 112/2845 48/1219 400/800:5 2.0/1.5 60 52
750 325 169/4293 65/1651 500/1000:5 2.0/1.5 60 60
900 395 169/4293 65/1651 600/1200:5 2.0/1.5 120 90
1050 460 214/5436 84/2134 750/1500:5 2.0/1.5 120 90
800/1600:5 2.0/1.5 120 90
1000/2000:5 2.0/1.5 120 90
1500/3000:5 2.0/1.0 120 90
25/50:5 2.0/2.0 21 21
350 140 52/1321 24/610 50/100:5 2.0/2.0 31 31
550 230 101/2565 42/1067 75/150:5 2.0/2.0 49 49
IM 650 275 131/3327 54/1372 100/200:5 2.0/2.0 63 63
750 325 169/4293 65/1651 150/300:5 2.0/2.0 63 63
900 395 169/4293 65/1651 200/400:5 2.0/2.0 63 63
1050 460 214/5436 84/2134 300/600:5 2.0/2.0 63 63
100:5 2.0 8 6
150:5 2.0 12 10
150 50 34/864 13/330 200:5 2.0 15 10
200 70 34/864 13/330 300:5 2.0 24 20
250 95 52/1321 24/610 400:5 2.0 30 25
350 140 52/1321 24/610 600:5 2.0 30 25
IH 550 230 101/2565 42/1067 800:5 2.0 60 50
650 275 131/3327 54/1372 1000:5 2.0 60 50
750 325 169/4293 65/1651 1200:5 2.0 60 50
900 395 169/4293 65/1651 1500:5 2.0 120 90
1050 460 214/5436 84/2134 1600:5 1.875 120 90
2000:5 1.5 120 90
3000:5 1.0 120 90
For units rated C400 or C800 relay class rating consult factory
Note: Consult factory for ratios not listed.
6
Dimensional Table
7
Trench Facilities
www.trenchgroup.com
E 217.31
Subject to change without notice (05.2006)
Printed in Canada.