Sie sind auf Seite 1von 4

STAYING ON TOP OF

ROOFTOP UNITS
Understanding RTUs, their operation,
preventive maintenance and current
technology can help keep your customers’
systems online and optimally operating.

BY N. ROBERT BURGESS, JR., CEM, CEA, LEED AP


Images courtesy of author.

[Editor’s Note: This feature has been left in first person to main-
tain the author’s personal experience.]

I
started to work on rooftop units (RTUs) more than 30 years
ago. As a young apprentice, I quickly learned several things
about working on these systems, including what a rooftop
unit is, how these systems operate, preventive maintenance
and current technology. This article will focus on exactly
these points. Knowing if the issue is on the cooling side or the heating
side (shown here) of an RTU helps eliminate many compo-
nents that are in need of troubleshooting.

require a crane. In this case, you would also need to have


a rooftop company ready to make any repairs and you want
to ensure that you do not void the rooftop warranty.
In reference to RTUs, I have also heard the terms “air-
handler unit” or “packaged unit” being used. On several
occasions, I have heard people call a split system an RTU
simply because the condensing coil was located on the roof.
This is not accurate. Know too that a packaged unit can
also be found inside a mechanical room, so it will not have
weather-related exposure issues. In these cases, the metal casing
does not need to be as resistant as a rooftop unit that may be
made of mill-galvanized steel, which tends to be more resistant
to corrosion.
The simplest definition of an RTU is a packaged unit that The rooftop unit can have various fans and controls on
rests on a curb adaptor and sits on the roof and supplies it. It can also use gas, oil, propane or electric for heating.
one or all the heating, ventilation and/or air-conditioning of The air-conditioning can be supplied with a direct-expansion
a building. (DX) system or a chilled-water coil (a chiller supplies chilled
water to this type of design). The duct work for supply air and
What is a rooftop unit? return air can have various options underneath: sideways or out
AHRI’s 2012 market share information indicated that approxi- the end. As far as fan design goes, most units come with two
mately 301,000 of these units were shipped within the United designs: constant volume, where the fan runs at full speed; and
States. That is a lot of rooftop units in the field that may variable air volume, which works with a VAV system. The VAV
be in need of servicing. The simplest definition of an RTU system changes fan speed and usually works off of static pressure.
is: a packaged unit that rests on a curb adaptor and sits on This type is very energy efficient and can supply better comfort
the roof and supplies one or all the heating, ventilating control, which are two items owners like to hear.
and/or air-conditioning of a building. The basic heating and cooling design is fundamentally the
It is very important to verify that the manufacturer has same as any other unit in the field. The rooftop unit might
sent the correct curb adapter for the new RTU. I have been have a return fan depending on the application. One fan that
sent the wrong one in the past and it has stopped the job. service technicians may be unfamiliar with is an exhaust fan.
It is important to remember that a replacement job may In some applications, the rooftop unit will be bringing in

10 RSES Journal MAY 2014 w w w. r s e s j o u r n a l . co m


outside air for ventilation or free cooling along with return In order to eliminate many components during the trou-
air. Exhaust fans are often used to prevent air pressure from bleshooting process, it is always best to know if the issue is
building up in the tenant space, such as a hallway, and over- on the heating or air-conditioning side. Is the blower fan
pressurizing it. This could cause dangerous conditions and running? Remember, in some cases, local code or ASHRAE
contribute to elevator or entrance doors not working correctly. 62 is requiring that the fan run constantly to pressurize the
In many cases, the rooftop unit has a sensor that measures hallway and to prevent odors and provide air for exhaust in
the difference between outside air and building pressures. a residential dwelling. In some commercial buildings the fan
When this pressure is exceeded, the exhaust fan comes on runs around the clock to ensure better air circulation. If it
to lower this pressure. These other features will be discussed is in the air-conditioning mode, are the compressors trying
more in the current technology section. to run? Or is the rooftop unit using a chilled-water coil. A
review of the central plant might be needed to check pumps,
Operation chillers, etc. A lot can be learned by listening, seeing and
Every service technician must understand the fundamentals touching, even before gauges are used. Also be sure to talk to
of the field. Once the technician understands how air-condi- the customer. They are always able to provide vital informa-
tioning and heating systems work, no matter what the system, tion about what is happening.
these fundamentals come into play. Knowing the sequence Spending a few minutes on the heating side, first determine
of operation allows anyone to be able to walk through the what type of heat the rooftop is using. If it is electrical, check to
door and watch what the system is doing and compare that to see if the heating element is being held out by a safety switch,
what it should be doing. Certainly, there will be exceptions, but such as a high- temperature cutout or air-flow switch. Are the
understanding these basics helps with troubleshooting a system. fuses blown? Many units will either use sequencers or contactors
Using an A/C gas-fired rooftop unit as an example, the first to bring on the electric heat, check to see if these are working
question to ask is if the unit is being directed to run, either from properly. Proficiency in using electrical meter and reading a sche-
a thermostat on the wall, a thermistor sending a temperature matic are keys to troubleshooting these problems. Remember,
back to the electronic board in the rooftop unit, or energy- safety first. Lock out and tag out when necessary.
management systems? Although it seems like a silly question, I In most cases on gas-heat units, the draft fan needs to run
once had a rooftop unit that would not run. When I checked to pre-purge and exhaust fumes. When walking to the unit,
the EMS, the building engineer had put it on a holiday schedule the technician should hear the fan running or feel exhaust
the Monday before and had not switched it back. A simple fix. air blowing out of the unit. If this is not happening, the air

Circle Reader Service No. 47


w w w. r s e s j o u r n a l . co m MAY 2014 RSES Journal 11
Rooftop  Maintenance  Schedule

Rooftop Maintenance Schedule

Burgess Green Facilities Service


Customer  Name  and  Location:
Date:
Performed  By:

Checklist Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec
Clean  Return  Air  Grilles
Replace  Return  Air  Filters
Replace  Unit  Disposable  Filters
Clean  Unit  Outside  Air  Filters  (Metal)
Check  Condensate  Drain
Inspect  Evaporator  Coil
Inspect  Condensor  Coil
Check  For  Noise  or  Vibration
Check  Supply  Air  Flow  cfm/Velcoity
Air  Side
CHECK  FAN  BELT  TENSION/  REPLACE  IF  NEEDED
EVAPORATOR  FAN  WHEEL  FOR  DIRT/CLEAN  IF  NEEDED
INSPECT  MOTORS,  STARTERS/CHECK  ELECTRICAL  CONNECTIONS
LUBRICATE  ALL  BEARINGS  IF  NEEDED
CHECK  ECONOMIZER  (DAMPER)  OPERATION
                                 OUTSIDE  AIR  DAMPER  CLOSES  W/UNIT
                                 DAMPER  OPEN  W/UNIT  ON
Gas  Heat
CHECK  CONDITION  OF  HEAT  EXCHANGERS  &  COMBUSTION  AIR  BLOWER
CHECK  FOR  PROPER  PILOT  IGNITION
CHECK  FOR  PROPER  BURNER  FLAME  APPEARANCE
CHECK  HEAT  EXCHANGE  LIMIT  SWITCH
CHECK  UNIT  HEATING  CONTROL  SEQUENCE
Cooling  
CHECK  FOR  DIRTY  CONDENSER  COIL
CHECK  FOR  DIRTY  EVAPORATOR  COIL
CHECK  FOR  REFRIGERANT  PRESSURES/TEMPERATURES
CLEAN  CONDENSATE  PANS  AND  DRAINS
CHECK  CONDITIONED  AIR  DISCHARGE  TEMPERATURE
CHECK  UNIT  COOLING  CONTROL  SEQUENCE

This is a sample of a preventive-maintenance schedule for RTUs. Always take into consideration the make of the
system and manufacturer recommendations when creating a PM schedule for a customer.

pressure switch will not close and the system will not run. Look the building at a slight positive pressure. Some manufactures
for items such as a no call for heat, blocked exhaust, pressure will use dry-bulb or enthalpy sensors to automate this process.
switch is not being made or there is a bad air-pressure switch. It is important you find out which are being used.
If everything appears normal and all safety precautions have
been made, watch the unit as it fires up. Some units have a pilot Preventive maintenance
while others light off directly with no pilot. Is the unit using a Customers are always told that the unit will fail to func-
hot surface igniter or electrodes to light off the fuel. Thirty years tion, not work properly and waste energy if preventive
ago, most items were mechanical, but today most units are full of maintenance (PM) is not performed. Yet, year after year,
electronic boards and will flash a message or use lights to explain customers still neglect to perform preventive maintenance.
what is occurring. In these cases, it is very helpful to attend a It has been made worse by the economy because customers
manufacturer’s training seminar through the manufacturer or attempt to save money by not performing necessary (and
a local supply house. These seminars provide valuable short- sometimes costly) maintenance. It is up to skilled techni-
cuts and information that can be used out in the field. As cians to sell them on the benefits of preventive mainte-
RSES frequently states, education is truly power. nance. Rooftop units are no different than any other piece
It is important to look at the configuration of the return, of equipment. It is always best to follow the manufacturer’s
outside and exhaust dampers, as these will have a significant instructions and PM plans. I have included a generic PM
impact on comfort and energy. The basic function of an RTU schedule on a gas rooftop unit. There are many more items
is to supply conditioned air that returns back to the unit. that can expand the list, depending on the manufacturer
This cycle continues as long as the unit runs. If an outside and what the customer wants.
air damper is added, it will be used to bring in fresh air and Preventive maintenance may also need to be performed after
as an air-side economizer. In the case of the economizer, the hours. On one occasion, a service technician tried to clean the
conditions are just right to use outside air to cool the building condenser coil while the unit was running and the smell went
instead of using mechanical cooling. At this point the return through the outside air dampers, evacuating an entire office
dampers close. When the return dampers close, or bring in building in downtown Washington, D.C., which also brought
outside air, the building would over-pressurize. In this situa- out the hazmat team and the fire department—a lesson that
tion, the exhaust fan comes on and exhausts the air, keeping technician will never forget.

12 RSES Journal MAY 2014 w w w. r s e s j o u r n a l . co m


There are a few PM items on a rooftop unit besides the come up with better ways to service them. The basic principle
normal filter changes and coil cleaning. On many units the behind an ERV wheel in many commercial applications is that
service person might find return dampers, outside air dampers the building is exhausting conditioned air to the outside and
and exhaust dampers that may also include their own fan. bringing in cold, hot or high humidy air back into the building
These dampers are all working together and, as such, are to be used as fresh air. An ERV wheel takes that conditioned
linked together through sensors and controls. In some cases, air (already heated, cooled or dehumidified, depending on
technicians may find a piece of wood holding up a damper, the season) and transfers it to the incoming fresh air. Located
which points to a service technician who did not understand in the rooftop unit, this wheel takes the heat from return
the control sequence or an owner who did not want to spend air that would be exhausted to the outdoors and transfers it
the money for the repair. to the outside air as it becomes the supply air. The opposite
happens in the summer, as it helps dehumidify and lower the
Current technology outside temperature of the incoming air. All of this lowers
More stringent codes and increasing energy costs have made energy use.
manufacturers look at various ways to keep spaces comfortable
while also saving energy. In some cases, buildings are required N. Robert Burgess, Jr., CEM, CEA, LEED AP, is the Owner
to bring in more outside air to keep CO2 levels within accept- of Burgess Green Facilities Service. He is a Master HVACR
able ranges. This sometimes requires extra heating, cooling Technician and works as an advisor for the real-estate industry.
or dehumidification to condition the outside air even more, Burgess, who currently holds 14 certifications and licenses
which increases energy costs. within the engineering and property management field, has
Variable-frequency drives help to save energy. Service tech- served as Vice President of Property Management for various
nicians should check if the fan in units with VFDs needs to companies, has authored three textbooks for BOMI, and has
constantly run at full speed. In most cases, the answer is no, been the lead instructor for the National Association of Power
in which case, cut down on the horsepower to help the owner Engineers for more than 28 years. Currently, he serves on the
save on energy costs. Energy-recovery ventilation wheels, or Board of Directors for the Property Management Association.
enthalpy wheels, have been gaining momentum over the past For more information, e-mail robertburgess@burgessgreenfacilities
few years and have been widely used in rooftop units with var- service.com.
ious results. As energy costs keep rising, manufacturers have

Circle Reader Service No. 48


w w w. r s e s j o u r n a l . co m MAY 2014 RSES Journal 13

Das könnte Ihnen auch gefallen