Presentation
1 2
Run components Connection components and feed units
From 1000 to 5000 A. For connecting the busbar trunking to transformer terminals or to
4 live copper conductors in fixed lengths of 4 metres switchboard connections.
or in 0.50 to 3 metre lengths as required. These components are only available in copper.
2/4 Te
3 4
Components for changing direction Fixing devices
For adapting to all the trunking runs. There are two ways of fixing : horizontal and vertical.
They are available in fixed lengths or made to measure.
Te 2/5
High power busbar trunking
Canalis KTC (1000 to 5000 A)
For low density horizontal distribution in :
industry, commercial and service buildings and infrastructures
Presentation
1 2
Run components Connection components and feed units
From 1000 to 5000 A. For connecting the busbar trunking to switchboard connections.
4 live copper conductors. Feeder components in fixed lengths of These components are only available in copper.
4 metres or in 0.50 to 3 metre lengths as required.
Distribution components in fixed lengths of 2 and 4 metres.
2/6 Te
3 4 5
Components for changing direction Fixing devices Tap-off units
For adapting to all the trunking runs. There are two ways of fixing : horizontal and From 400 to 1250 A for Merlin Gerin Compact NS
They are available in fixed lengths or made to vertical. or Compact C circuit-breakers. For low density
measure. tapping off, the units are mounted on components
designed for this purpose.
Te 2/7
High power busbar trunking
Canalis KTC (1000 to 5000 A)
For high density horizontal distribution in :
industry, commercial and service buildings and infrastructures
Presentation
1 2
Run components Connection components and feed units
From 1000 to 5000 A. For connecting the busbar trunking to switchboard connections.
4 live copper conductors. Feeder components in fixed lengths of These components are only available in copper.
4 metres or in 0.50 to 3 metre lengths as required.
Distribution components in fixed lengths of 2 and 4 metres.
2/8 Te
3 Components for changing direction 4 5
Fixing devices Tap-off units
For adapting to all the trunking runs. There are two ways of fixing : horizontal and There are two types of unit : removable (KS
They are available in fixed lengths or made to vertical. range from 25 to 400 A) and bolt-on for Merlin
measure. Gerin Compact circuit-breakers from 400 to
1250 A.
Te 2/9
High power busbar trunking
Canalis KTC (1000 to 5000 A)
For rising main distribution in :
industry, commercial and service buildings and infrastructures
Presentation
1
Run components
From 1000 to 5000 A.
4 live copper conductors,
in 2.50 to 4 metre lengths according to the
height of the floors.
2
Connection components and feed
units
For connecting busbar trunking
to switchboard connections.
These components are only available in copper.
2/10 Te
3
Components for changing direction
For adapting to all the trunking runs.
They are available in fixed lengths or made to measure.
4
Fixing devices
There are two ways of fixing : horizontal and vertical.
5
Tap-off units
There are two types of unit : removable (KS range from
25 to 400 A) and bolt-on for Merlin Gerin Compact
circuit-breakers from 400 to 1250 A.
Te 2/11
High power busbar trunking
Selection guide : Canalis KTC (1000 to 5000 A)
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3 Description
References :
pages 10174/2 to 10179/5
Dimensions :
pages 10180/2 to 10184/3
General
Canalis KTC trunking is designed to feed and distribute high power in industrial, commercial or service buildings. The
standard range is IP 52 (IP 54 as an option). This trunking has a compact design, namely with plated conductors inside
a metal enclosure. The isolated conductor bars are made of copper. The range is divided into 8 ratings from 1000 to
5000 A. The insulation used on the conductors is halogen-free 130°C class B polyester.
Joints
Each run component (straight length, elbow, tee, etc) includes its own joint kit (delivered under separate cover). The joint
kit comprises all the parts required to provide a mechanical and electrical joint between two components.
The electrical joint is ensured by a single bolt joint block (1 to 2 bolts per busbar). This ensures continuity for all conductors,
and paralleling of both bars in the same phase.
The bolt is made up of a screw and a contraction nut, the external head of which breaks when the tightening torque is
reached. This device ensures the required contact pressure is applied by the joint block to the live conductors.
When the head of the nut breaks, a red washer is released, showing that the electrical joint has been installed correctly.
For disassembly or maintenance operations, a second head is available. The recommended torque is thus 6 Nm.
The joint block contacts are silver-plated copper.
2/12 Te
High power busbar trunking
Selection guide : Canalis KTC (1000 to 5000 A)
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3 Description
References :
pages 10174/2 to 10179/5
Dimensions :
pages 10180/2 to 10184/3
Run components
There are 4 types of straight length (supplied with their busbar connector), types ET, EA, EB and DB.
Te 2/13
High power busbar trunking
Selection guide : Canalis KTC (1000 to 5000 A)
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3 Description
References :
pages 10174/2 to 10179/5
Dimensions :
pages 10180/2 to 10184/3
To connect KTC trunking to the various terminals or connections of transformers, switchboards, generators, etc, Canalis
offers high-performance connection components to meet all requirements. These components ensure flexible, easy
installation together with quick, easy mounting. They also absorb last minute deviations in civil engineering as they can
be adapted on site. Moreover, connections are made using bolts with snap-off heads which at the same time offer easy
installation (use of a standard spanner for tightening) and a visual check before power up.
End cover
2/14 Te
High power busbar trunking
Selection guide : Canalis KTC (1000 to 5000 A)
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3 Description
References :
pages 10174/2 to 10179/5
Dimensions :
pages 10180/2 to 10184/3
yy
@@
ÀÀ
,,
ÀÀy,À@yy
@@
,,
yy @@y,À@yy
ÀÀ
,, @@y,À@
ÀÀ
,,
@@y,À@yy
ÀÀ
,,
yy @@y,À@yy
ÀÀ
,, @@y,À@
ÀÀ
,,
@@y,À@yy
ÀÀ
,,
yy @@y,À@
ÀÀ
,,
Te 2/15
High power busbar trunking
Selection guide : Canalis KTC (1000 to 5000 A)
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3 Description
References :
pages 10174/2 to 10179/5
Dimensions :
pages 10180/2 to 10184/3
i Edgewise tees
Fixing devices
1 1 Horizontal fixing
This consists of a steel bracket and two M10 threaded
rods, 1.2 metres long, the maximum fixing distance is 3
metres.
2 Vertical fixing
This fixes a vertical run component to the structure of the
building.
This type of fixing support has the following advantages :
- The height can be adjusted to correct positioning
errors.
- The spring can be adjusted to ensure the load is
2 distributed at each level.
- The constraints of the building (expansion, vibration
etc) are not transferred to the trunking.
2/16 Te
High power busbar trunking
Selection guide : Canalis KTC (1000 to 5000 A)
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3 Description
References :
pages 10174/2 to 10179/5
Dimensions :
pages 10180/2 to 10184/3
Tap-off units
These are used to instantly connect loads or secondary runs. They conform to installation standards and regulations,
whatever the neutral point connection (TT, IT, TNS or TNC) :
- They can be moved with the power on, with no load.
- The tap-off outlets open and close automatically when units are plugged in or removed.
- When the cover is open, no live part can be accessed and the degree of protection provided is IP 2X.
Tap-off units are produced in a dust and damp proof version, degree of protection IP 54.
A Tap-off units
- Isolation is obtained by removing the unit.
- The electrical equipment and connection terminals can only be accessed when the unit has been removed (power
off).
- A safety device prevents the unit being plugged into the trunking if the cover is not in place.
These units can take certain accessories such as an early break contact on the cover, lead sealing kit, etc.
A
B
PE =
Te 2/17
High power busbar trunking
Selection guide : Canalis KTC (1000 to 5000 A)
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3 Description
References :
pages 10174/2 to 10179/5
Dimensions :
pages 10180/2 to 10184/3
Tap-off units
2/18 Te
High power busbar trunking
Selection guide : Canalis KTC (1000 to 5000 A)
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3 Description
References :
pages 10174/2 to 10179/5
Dimensions :
pages 10180/2 to 10184/3
Te 2/19
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 and 10171/9
Characteristics :
pages 10173/2 and 10173/3 Selection guide
References :
pages 10174/2 to 10179/5
Dimensions :
pages 10180/2 to 10184/3
The rating of a busbar trunking, in amps, represents the maximum intensity of the constant current which the trunking can
continuously support, for an average ambient temperature of 35 °C, and in accordance with standard temperature rises
(IEC 439.2).
Determining the rating according to the temperature rise consists of selecting the busbar trunking rating immediately
above the operating current of the installation. However, as a rule, the intensity of the current which crosses a busbar
trunking is constantly fluctuating. The operating current is therefore defined as that of the constant current which produces
the same thermal effects as the actual current.
It is sometimes difficult to determine the operating current, especially when there is no reading for the installation or for
an equivalent installation. The operating current can be estimated with sufficient precision by calculating the product of
the nominal currents of receivers connected to the busbar trunking by a coefficient known as the “average demand
coefficient”. The average demand coefficient is empirically determined by comparison with existing installations. It is
dependent upon :
- the average quantity of receivers operating
- the load variation of each receiver (a receiver rarely absorbs its maximum power, as peak periods alternate with those
of no-load operation)
- whether several receivers are operating at the same time, whether peaks are superimposed and the duration of these
peaks
As an example, here are a few coefficients for a general mechanical engineering workshop.
2 or 3 0.9
4 or 5 0.8
6 to 9 0.7
10 to 40 0.6
40 plus 0.5
Depending on the ambient temperature, the trunking must be derated (see characteristics pages 10173/2 and 10173/3).
The permissible voltage drop is that which is compatible with the correct operation of the receivers (refer to the
manufacturers' manuals).
i Read the voltage drop in mV/100 m/A in the tables on page 10173/3 for the busbar trunking selected according to the
temperature rise.
i Determine the voltage drop for the most disadvantaged receivers, namely those which are the furthest from the source
and for the highest current. If the voltage drop is not permissible, select the rating immediately above.
i Calculate the intensity of the short-circuit current at the points which are considered to be unfavourable.
i Check, by referring to the tables on pages 10173/2 and 10173/3, that the selected rating of the trunking enables it to
withstand this short-circuit current. If this is not the case, there are two possible solutions :
- Select trunking of a higher rating and repeat the checking procedure.
- Provide a protection system which limits current peaks upstream of the trunking.
2/20 Te
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 and 10171/9
Characteristics :
pages 10173/2 and 10173/3 Selection guide
References :
pages 10174/2 to 10179/5
Dimensions :
pages 10180/2 to 10184/3
The table below can be used to determine the rating of the KTC busbar trunking (copper conductors) and the source circuit
breaker (Merlin Gerin) according to the power of the transformer.
Calculation assumptions
The following calculation assumptions have been made :
- the short-circuit power of the upstream supply : 500 MVA
- the voltage ratio of the transformers : 20 kV/400 V
The circuit-breaker/trunking coordination table below gives directly the maximum short-circuit current for which the KT
trunking is protected, according to the type of circuit-breaker.
Type of trunking KTC-10 KTC-13 KTC-16 KTC-20 KTC-25 KTC-30 KTC-40 KTC-50
Rating (A) 1000 1350 1600 2000 2500 3000 4000 5000
Merlin-Gerin C1001 N 50 50
Compact H 55 70
circuit-breaker L 100 150
C1251 N 50 50
H 55 70
Merlin-Gerin M 10 N1 40 40 40 40
Masterpact M 12 H1 40 50 60 65
circuit-breaker M 16 H2 40 50 60 73
M 10 - 12 L1 55 85
M 20 N1 55 55 55 55
M 25 H1 60 73 75 75
H2 60 73 82 82
M 32 H1 75 75 75
M 40 H2 82 82 90
M 50 H1 90 95
M 63 H2 90 95
Te 2/21
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide :
pages 10172/2 and 10172/3 Characteristics
References :
pages 10174/2 to 10179/5
Dimensions :
pages 10180/2 to 10184/3
Type of trunking KTC-10 KTC-13 KTC-16 KTC-20 KTC-25 KTC-30 KTC-40 KTC-50
General characteristics
Degree of protection (IEC 529) IP 52 for horizontal, edgewise installation and vertical installation, IP 54 as an option.
as standard IP 52 for horizontal, flat installation
Permissible currents
Rated current Ith (2) A 1000 1350 1600 2000 2500 3000 4000 5000
conforming to IEC 439
Rated peak current kA 84 105 130 160 180 180 198 209
Multiplying Temperature °C 35 40 45 50
factors of the
rated current
Ith depending Factor 1 0.95 0.90 0.84
on the average
ambient temperature
Conductor characteristics
Live conductors
Rb0ph Average resistance per m /m 0.042 0.03 0.025 0.019 0.015 0.0125 0.0094 0.0075
conductor, cold state
(ambient temperature 20 °C)
Rb1ph Average resistance per m /m 0.056 0.036 0.03 0.023 0.018 0.015 0.011 0.009
conductor at Ith
(ambient temperature 35 °C)
Xph Average reactance per m /m 0.022 0.016 0.015 0.013 0.01 0.008 0.0074 0.007
conductor
Zph Average impedance per m /m 0.06 0.04 0.034 0.026 0.02 0.017 0.013 0.011
conductor
(1) For 60 to 400 Hz AC or for DC, please consult your Regional Sales Office.
(2) Rated currents Ith are given for an average ambient temperature of 35 °C and for a casing temperature rise of no more
than 55 °K according to the test conditions of standard EN 60 439.2.
2/22 Te
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide :
pages 10172/2 and 10172/3 Characteristics
References :
pages 10174/2 to 10179/5
Dimensions :
pages 10180/2 to 10184/3
Type of trunking KTC-10 KTC-13 KTC-16 KTC-20 KTC-25 KTC-30 KTC-40 KTC-50
Other characteristics
Live conductors
Rb1ph ph or phN Average resistance m /m 0.112 0.072 0.06 0.046 0.036 0.03 0.022 0.018
of fault loops between
live conductors
Rb2ph ph or phN Average resistance m /m 0.134 0.086 0.072 0.055 0.043 0.036 0.026 0.022
of fault loops between
live conductors
Rb1ph PE Average resistance m /m 0.206 0.168 0.153 0.115 0.108 0.101 0.093 0.086
of fault loops between
live conductors and PE
Xb1ph ph or phN Average reactance m /m 0.034 0.026 0.024 0.022 0.019 0.012 0.010 0.010
of fault loops between
live conductors
Xb1ph PE Average reactance m /m 0.13 0.12 0.10 0.10 0.10 0.07 0.056 0.046
of fault loops between
live conductors and PE
Voltage drop Composite voltage drop, hot state, in millivolts per metre and per amp, for three-phase 50 Hz current, with the load
distributed along the run. If the load is concentrated at the end of the run (feed run), voltage drops are half the values
indicated in the table below.
For a power factor ϕ mV/m/A 0.048 0.032 0.0275 0.022 0.017 0.0139 0.0112 0.0098
of 0.7
For a power factor ϕ mV/m/A 0.051 0.033 0.0286 0.023 0.0177 0.0145 0.0115 0.0099
of 0.8
For a power factor ϕ mV/m/A 0.052 0.034 0.029 0.023 0.0178 0.0147 0.0114 0.0097
of 0.9
For a power factor ϕ mV/m/A 0.048 0.031 0.026 0.02 0.0156 0.013 0.0095 0.0078
of 1
Protective conductor
Casing Equivalent copper mm2 120 130 140 155 165 180 190 200
cross-section
Average resistance, m /m 0.15 0.132 0.123 0.115 0.108 0.101 0.093 0.086
cold state (ambient
temperature 20 °C)
Additional Equivalent copper mm2 210 300 360 480 600 720 960 1200
conductor cross-section
Average resistance, m /m 0.081 0.057 0.048 0.037 0.0287 0.024 0.018 0.014
cold state (ambient
temperature 20 °C)
Average weight
3L + N + PE kg/m 29 35 42 48 57 66 82 99
Te 2/23
KTC-iiEAiii KTC-iiETiii
KTC-iiETiii
KTC-iiEAiii
KTC-iiEBiii
2/24 Te
High power busbar trunking
Description : Canalis KTC (1000 A)
pages 10171/2 to 10171/9 IP 52 run components
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
For feeding
Type Length Number of 3L + N + PE 3L + N + PER
Min…Max tap-offs Reference Reference
mm
N
2001…2500 – KTC-10ET42C KTC-10ET72C
N
For rising main distribution with removable tap-off
Expansion
N
IP 54 joint block (2)
Busbar trunking rating 3L + N + PE 3L + N + PER
Reference Reference
A Weight (kg) Weight (kg)
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
(2) Only order if the run has a feed unit at each end.
N : position of neutral
Te 2/25
High power busbar trunking
Description : Canalis KTC (1350 A)
pages 10171/2 to 10171/9 IP 52 run components
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
For feeding
Type Length Number of 3L + N + PE 3L + N + PER
Min…Max tap-offs Reference Reference
mm
N
2001…2500 – KTC-13ET42C KTC-13ET72C
N
For rising main distribution with removable tap-off
Expansion
N
IP 54 joint block (2)
Busbar trunking rating 3L + N + PE 3L + N + PER
Reference Reference
A Weight (kg) Weight (kg)
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
(2) Only order if the run has a feed unit at each end.
N : position of neutral
2/26 Te
High power busbar trunking
Description : Canalis KTC (1600 A)
pages 10171/2 to 10171/9 IP 52 run components
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
For feeding
Type Length Number of 3L + N + PE 3L + N + PER
Min…Max tap-offs Reference Reference
mm
N
2001…2500 – KTC-16ET42C KTC-16ET72C
N
For rising main distribution with removable tap-off
Expansion
N
IP 54 joint block (2)
Busbar trunking rating 3L + N + PE 3L + N + PER
Reference Reference
A Weight (kg) Weight (kg)
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
(2) Only order if the run has a feed unit at each end.
N : position of neutral
Te 2/27
High power busbar trunking
Description : Canalis KTC (2000 A)
pages 10171/2 to 10171/9 IP 52 run components
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
For feeding
Type Length Number of 3L + N + PE 3L + N + PER
Min…Max tap-offs Reference Reference
mm
N
2001…2500 – KTC-20ET42C KTC-20ET72C
N
For rising main distribution with removable tap-off
Expansion
N
IP 54 joint block (2)
Busbar trunking rating 3L + N + PE 3L + N + PER
Reference Reference
A Masse (kg) Masse (kg)
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
(2) Only order if the run has a feed unit at each end.
N : position of neutral
2/28 Te
High power busbar trunking
Description : Canalis KTC (2500 A)
pages 10171/2 to 10171/9 IP 52 run components
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
For feeding
Type Length Number of 3L + N + PE 3L + N + PER
Min…Max tap-offs Référence Reference
mm
N
2001…2500 – KTC-25ET42C KTC-25ET72C
N
For rising main distribution with removable tap-off
Expansion
N
IP 54 joint block (2)
Busbar trunking rating 3L + N + PE 3L + N + PER
Reference Reference
A Weight (kg) Weight (kg)
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
(2) Only order if the run has a feed unit at each end.
N : position of neutral
Te 2/29
High power busbar trunking
Description : Canalis KTC (3000 A)
pages 10171/2 to 10171/9 IP 52 run components
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
For feeding
Type Length Number of 3L + N + PE 3L + N + PER
Min…Max tap-offs Reference Reference
mm
N
2001…2500 – KTC-30ET42C KTC-30ET72C
N
For rising main distribution with removable tap-off
Expansion
N
IP 54 joint block (2)
Busbar trunking rating 3L + N + PE 3L + N + PER
Reference Reference
A Weight (kg) Weight (kg)
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
(2) Only order if the run has a feed unit at each end.
N : position of neutral
2/30 Te
High power busbar trunking
Description : Canalis KTC (4000 A and 5000 A)
pages 10171/2 to 10171/9 IP 52 run components
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
For feeding
Type Length Number of 3L + N + PE 3L + N + PER
Min…Max tap-offs Reference (3) Reference (3)
mm
N
2001…2500 – KTC-iiET42C KTC-iiET72C
N
For rising main distribution with removable tap-off
Expansion
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
(2) Only order if the run has a feed unit at each end.
(3) In the reference : replace ii with 40 for a rating of 4000 A.
with 50 for a rating of 5000 A.
N : position of neutral
Te 2/31
KT0-iiERiii01 KT0-iiERiii03 KT0-iiERiii05
KT0-iiERiii02 KT0-iiERiii04 KT0-iiERiii06
2/32 Te
High power busbar trunking
Description : Canalis KTC (1000 A)
pages 10171/2 to 10171/9 IP 52 feed units
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
Straight length N1
a Straight length N2
Flat elbow N3
e Made to 200…1000 300…1000 80…250 KT0-10ER42C03 KT0-10ER72C03
e
e measure
a
b Flat elbow N4
N3
Made to 200…1000 300…1000 80…250 KT0-10ER42C04 KT0-10ER72C04
N4
measure
Edgewise elbow N5
Edgewise elbow N6
N6 e
e e Made to 200…1000 300…1000 80…250 KT0-10ER42C06 KT0-10ER72C06
measure
N e
7 e Straight length, flat outlets N7
e
Made to 235…1000 _ 160…800 KT0-10ER42B07 KT0-10ER72B07
a measure
N a
10
e Edgewise elbow, flat outlets N11
e
e
Made to 200…1000 300…1000 160…800 KT0-10ER43D11 KT0-10ER73D11
measure
(1) To order the feed unit, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
Te 2/33
High power busbar trunking
Description : Canalis KTC (1350 A)
pages 10171/2 to 10171/9 IP 52 feed units
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
Straight length N1
a Straight length N2
Flat elbow N3
e Made to 200…1000 300…1000 80…250 KT0-13ER42C03 KT0-13ER72C03
e
e measure
a
b Flat elbow N4
N3
Made to 200…1000 300…1000 80…250 KT0-13ER42C04 KT0-13ER72C04
N4
measure
Edgewise elbow N5
Edgewise elbow N6
N6 e
e e Made to 200…1000 300…1000 80…250 KT0-13ER42C06 KT0-13ER72C06
measure
N e
7 e Straight length, flat outlets N7
e
Made to 235…1000 _ 160…800 KT0-13ER42B07 KT0-13ER72B07
a measure
N a
10
e Edgewise elbow, flat outlets N11
e
e
Made to 200…1000 300…1000 160…800 KT0-13ER43D11 KT0-13ER73D11
measure
(1) To order the feed unit, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
2/34 Te
High power busbar trunking
Description : Canalis KTC (1600 A)
pages 10171/2 to 10171/9 IP 52 feed units
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
Straight length N1
a Straight length N2
Flat elbow N3
e Made to 200…1000 300…1000 80…250 KT0-16ER42C03 KT0-16ER72C03
e
e measure
a
b Flat elbow N4
N3
Made to 200…1000 300…1000 80…250 KT0-16ER42C04 KT0-16ER72C04
N4
measure
Edgewise elbow N5
Edgewise elbow N6
N6 e
e e Made to 200…1000 300…1000 80…250 KT0-16ER42C06 KT0-16ER72C06
measure
N e
7 e Straight length, flat outlets N7
e
Made to 235…1000 _ 160…800 KT0-16ER42B07 KT0-16ER72B07
a measure
N a
10
e Edgewise elbow, flat outlets N11
e
e
Made to 200…1000 300…1000 160…800 KT0-16ER43D11 KT0-16ER73D11
measure
(1) To order the feed unit, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
Te 2/35
High power busbar trunking
Description : Canalis KTC (2000 A)
pages 10171/2 to 10171/9 IP 52 feed units
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
Straight length N1
a Straight length N2
Flat elbow N3
e Made to 200…1000 300…1000 80…250 KT0-20ER42C03 KT0-20ER72C03
e
e measure
a
b Flat elbow N4
N3
Made to 200…1000 300…1000 80…250 KT0-20ER42C04 KT0-20ER72C04
N4
measure
Edgewise elbow N5
Edgewise elbow N6
N6 e
e e Made to 260…1000 400…1000 80…250 KT0-20ER42C06 KT0-20ER72C06
measure
N e
7 e Straight length, flat outlets N7
e
Made to 235…1000 _ 160…800 KT0-20ER42B07 KT0-20ER72B07
a measure
N a
10
e Edgewise elbow, flat outlets N11
e
e
Made to 260…1000 400…1000 160…800 KT0-20ER43D11 KT0-20ER73D11
measure
(1) To order the feed unit, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
2/36 Te
High power busbar trunking
Description : Canalis KTC (2500 A)
pages 10171/2 to 10171/9 IP 52 feed units
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
Straight length N1
a Straight length N2
Flat elbow N3
e Made to 200…1000 300…1000 80…250 KT0-25ER42C03 KT0-25ER72C03
e
e measure
a
b Flat elbow N4
N3
Made to 200…1000 300…1000 80…250 KT0-25ER42C04 KT0-25ER72C04
N4
measure
Edgewise elbow N5
Edgewise elbow N6
N6 e
e e Made to 260…1000 400…1000 80…250 KT0-25ER42C06 KT0-25ER72C06
measure
N e
7 e Straight length, flat outlets N7
e
Made to 235…1000 _ 160…800 KT0-25ER42B07 KT0-25ER72B07
a measure
N a
10
e Edgewise elbow, flat outlets N11
e
e
Made to 260…1000 400…1000 160…800 KT0-25ER43D11 KT0-25ER73D11
measure
(1) To order the feed unit, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
Te 2/37
High power busbar trunking
Description : Canalis KTC (3000 A)
pages 10171/2 to 10171/9 IP 52 feed units
Selection guide :
pages 10172/2 et 10172/3
Characteristics : References
pages 10173/2 et 10173/3
Dimensions :
pages 10180/2 to 10184/3
Straight length N1
a Straight length N2
Flat elbow N3
e Made to 200…1000 300…1000 80…250 KT0-30ER42C03 KT0-30ER72C03
e
e measure
a
b Flat elbow N4
N3
Made to 200…1000 300…1000 80…250 KT0-30ER42C04 KT0-30ER72C04
N4
measure
Edgewise elbow N5
Edgewise elbow N6
N6 e
e e Made to 260…1000 400…1000 80…250 KT0-30ER42C06 KT0-30ER72C06
measure
N e
7 e Straight length, flat outlets N7
e
Made to 235…1000 _ 160…800 KT0-30ER42B07 KT0-30ER72B07
a measure
N a
10
e Edgewise elbow, flat outlets N11
e
e
Made to 260…1000 400…1000 160…800 KT0-30ER43D11 KT0-30ER73D11
measure
(1) To order the feed unit, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
2/38 Te
High power busbar trunking
Description : Canalis KTC (4000 A and 5000 A)
pages 10171/2 to 10171/9 IP 52 feed units
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
Straight length N1
a Flat elbow N4
b
N3 Made to 200…1000 300…1000 80…250 KT0-iiER42C04 KT0-iiER72C04
measure
N4
Edgewise elbow N5
N5
a
Edgewise elbow N6
N a
10 Edgewise elbow, flat outlets N11
e
e Made to 340…1000 500…1000 160…800 KT0-iiER43D11 KT0-iiER73D11
e
measure
(1) To order the feed unit, see the procedure on pages 10185/2 to 10185/5.
(2) In the reference : replace ii with 40 for a rating of 4000 A.
Ni : position of neutral with 50 for a rating of 5000 A.
Te 2/39
KT0-iiCS0
KT0-iiYAii24i
KT0-iiYAiii2i KT0-iiYAi106
2/40 Te
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9 Connection accessories
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
A kg
IP 54 protective cover
Use References Weight
KT0-iiCS0
kg
IP 54 end cover
Busbar trunking rating 3L + N + PE
3L + N + PER
Reference Weight
A kg
KT0-00CR1
1000 KT0-10FA 1.200
(1) When ordering, specify the rating of the busbar trunking, the distance between the busbar outlets (dimension e), the
user-definable dimensions indicated, and the position of the neutral.
KT0-iiFA
Te 2/41
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9 Accessories for vibration absorber connection bars
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
(1) The reference corresponds to all the parts required to connect the phases and the neutral including the bolts, washers
and snap-off head nuts.
2/42 Te
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9 Accessories for connection via braids
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
,,
,,
,,
2500 2 (100 x 6) KT0-25YA40236
22.60
,,
,,
,,
31.60
,,,,,,
55.90
,,,,,,
KT0-iiYAii24i
Braids 1000...1600 2 (100 x 6) KT0-16YA4106
65.00
yyyy
@@
ÀÀ
,, y,À@
@@
ÀÀ
,,
3000 3 (120 x 6) KT0-30YA4106
83.80
y,À@yy
ÀÀ
@@
,,
yy y,À@yy
@@
ÀÀ
,, y,À@
@@
ÀÀ
,, 4000 4 (120 x 6) KT0-40YA4106
y,À@yy
@@
ÀÀ
,,
yy y,À@yy
@@
ÀÀ
,, y,À@
@@
ÀÀ
,,
110.40
y,À@y,À@
@@
ÀÀ
,,
yy
5000 5 (120 x 6) KT0-50YA4106
136.80
(1) The reference corresponds to all the parts required to connect the phases and the neutral including the bolts, washers
KT0-iiYAi106 and snap-off head nuts.
Te 2/43
KTC-iiTCiii
KTC-iiTCiii
KTC-iiLCiii
KTC-iiLCiii
KTC-iiLPiii2
KTC-iiLPiii1
KTC-iiLPiii2
KTC-iiLPiii1
2/44 Te
High power busbar trunking
Description : Canalis KTC (1000 A)
pages 10171/2 to 10171/9 IP 52 tees and simple elbows
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
Elbows (1)
Edgewise LC
a Type Dimension a Dimension b Angle α 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
b
mm mm
N
Fixed 300 300 – KTC-10LC406 KTC-10LC706
Flat N1 à 90° LP
a b
N1 Fixed 300 300 – KTC-10LP4061 KTC-10LP7061
Flat N2 à 90° LP
a b
α N2 Made to 301…1000 301…1000 – KTC-10LP42B2 KTC-10LP72B2
measure
Edgewise TC
N Type Dimension a Dimension b Dimension c 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
mm mm mm
Fixing devices
Type Use Reference Weight
kg
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
Te 2/45
High power busbar trunking
Description : Canalis KTC (1350 A)
pages 10171/2 to 10171/9 IP 52 tees and simple elbows
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
Elbows (1)
Edgewise LC
a Type Dimension a Dimension b Angle α 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
b
mm mm
N
Fixed 300 300 – KTC-13LC406 KTC-13LC706
Flat N1 à 90° LP
a b
N1 Fixed 300 300 – KTC-13LP4061 KTC-13LP7061
Flat N2 à 90° LP
a b
α N2 Made to 301…1000 301…1000 – KTC-13LP42B2 KTC-13LP72B2
measure
Edgewise TC
N Type Dimension a Dimension b Dimension c 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
mm mm mm
Fixing devices
Type Use Reference Weight
kg
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
2/46 Te
High power busbar trunking
Description : Canalis KTC (1600 A)
pages 10171/2 to 10171/9 IP 52 tees and simple elbows
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
Elbows (1)
Edgewise LC
a Type Dimension a Dimension b Angle α 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
b
mm mm
N
Fixed 300 300 – KTC-16LC406 KTC-16LC706
Flat N1 à 90° LP
a b
N1 Fixed 300 300 – KTC-16LP4061 KTC-16LP7061
Flat N2 à 90° LP
a b
α N2 Made to 301…1000 301…1000 – KTC-16LP42B2 KTC-16LP72B2
measure
Edgewise TC
N Type Dimension a Dimension b Dimension c 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
mm mm mm
Fixing devices
Type Use Reference Weight
kg
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
Te 2/47
High power busbar trunking
Description : Canalis KTC (2000 A)
pages 10171/2 to 10171/9 IP 52 tees and simple elbows
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
Elbows (1)
Edgewise LC
a Type Dimension a Dimension b Angle α 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
b
mm mm
N
Fixed 400 400 – KTC-20LC408 KTC-20LC708
Flat N1 à 90° LP
a b
N1 Fixed 300 300 – KTC-20LP4061 KTC-20LP7061
Flat N2 à 90° LP
a b
α N2 Made to 301…1000 301…1000 – KTC-20LP42B2 KTC-20LP72B2
measure
Edgewise TC
N Type Dimension a Dimension b Dimension c 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
mm mm mm
Fixing devices
Type Use Reference Weight
kg
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
2/48 Te
High power busbar trunking
Description : Canalis KTC (2000 A)
pages 10171/2 to 10171/9 IP 52 tees and simple elbows
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
Elbows (1)
Edgewise LC
a Type Dimension a Dimension b Angle α 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
b
mm mm
N
Fixed 400 400 – KTC-25LC408 KTC-25LC708
Flat N1 à 90° LP
a b
N1 Fixed 300 300 – KTC-25LP4061 KTC-25LP7061
Flat N2 à 90° LP
a b
α N2 Made to 301…1000 301…1000 – KTC-25LP42B2 KTC-25LP72B2
measure
Edgewise TC
N Type Dimension a Dimension b Dimension c 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
mm mm mm
Fixing devices
Type Use Reference Weight
kg
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
Te 2/49
High power busbar trunking
Description : Canalis KTC (3000 A)
pages 10171/2 to 10171/9 IP 52 tees and simple elbows
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
Elbows (1)
Edgewise LC
a Type Dimension a Dimension b Angle α 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
b
mm mm
N
Fixed 400 400 – KTC-30LC408 KTC-30LC708
Flat N1 à 90° LP
a b
N1 Fixed 300 300 – KTC-30LP4061 KTC-30LP7061
Flat N2 à 90° LP
a b
α N2 Made to 301…1000 301…1000 – KTC-30LP42B2 KTC-30LP72B2
measure
Edgewise TC
N Type Dimension a Dimension b Dimension c 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
mm mm mm
Fixing devices
Type Use Reference Weight
kg
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
2/50 Te
High power busbar trunking
Description : Canalis KTC (4000 A and 5000 A)
pages 10171/2 to 10171/9 IP 52 tees and simple elbows
Selection :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
Elbows (1)
Edgewise LC
a Type Dimension a Dimension b Angle α 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Référence (2) Référence (2)
b
mm mm
N
Fixed 500 500 – KTC-iiLC410 KTC-iiLC710
Flat N1 à 90° LP
a b
N1 Fixed 300 300 – KTC-iiLP4061 KTC-iiLP7061
Flat N2 à 90° LP
a b
α N2 Made to 301…1000 301…1000 – KTC-iiLP42B2 KTC-iiLP72B2
measure
Edgewise TC
N Type Dimension a Dimension b Dimension c 3L + N + PE 3L + N + PER
Min…Max Min…Max Min…Max Reference Reference
mm mm mm
Fixing devices
Type Use Reference Weight
kg
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
(2) In the reference : replace ii with 40 for a rating of 4000 A.
with 50 for a rating of 5000 A.
Ni : position of neutral
Te 2/51
KTC-iiZPiii
KTC-iiZCiii1
KTC-iiTCiii
KTC-iiCPiii4
KTC-iiZCiii2
KTC-iiCPiii1
KTC-iiZLiii2
KTC-iiCPiii2
KTC-iiCPiii3
KTC-iiZLiii4
KTC-iiZLiii2
KTC-iiZLiii1
2/52 Te
High power busbar trunking
Description : Canalis KTC (1000 A)
pages 10171/2 to 10171/9 IP 52 zed units
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
N Edgewise ZC
1
a
N2 Made to 300… 230… 300… – KTC-10ZC43D2 KTC-10ZC73D2
measure 1000 1000 1000 –
b
Edgewise/flat CP
N
2
N1 Made to 300 220… 300 – KTC-10CP41A1 KTC-10CP71A1
measure 600 –
b a
measure 600 –
N1 N2
N
4 N4 Made to 300 230… 220… 300 KTC-10ZL42B4 KTC-10ZL72B4
N
3 measure 600 600
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
Te 2/53
High power busbar trunking
Description : Canalis KTC (1350 A)
pages 10171/2 to 10171/9
Selection guide :
IP 52 zed units
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3
References
Dimensions :
pages 10180/2 to 10184/3
N Edgewise ZC
1
a
N2 Made to 300… 230… 300… – KTC-13ZC43D2 KTC-13ZC73D2
measure 1000 1000 1000 –
b
Edgewise/flat CP
N
2
N1 Made to 300 220… 300 – KTC-13CP41A1 KTC-13CP71A1
measure 600 –
b a
measure 600 –
N1 N2
N
4
N N4 Made to 300 230… 220… 300 KTC-13ZL42B4 KTC-13ZL72B4
3 measure 600 600
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
2/54 Te
High power busbar trunking
Description : Canalis KTC (1600 A)
pages 10171/2 to 10171/9 IP 52 zed units
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
c
Edgewise ZC
b
N Edgewise ZC
1
a
N2 Made to 300… 230… 300… – KTC-16ZC43D2 KTC-16ZC73D2
measure 1000 1000 1000 –
b
Edgewise/flat CP
N
2
N1 Made tor 300 220… 300 – KTC-16CP41A1 KTC-16CP71A1
measure 600 –
b a
measure 600 –
N1 N2
N3 Made to 300 220… 300 – KTC-16CP41A3 KTC-16CP71A3
measure 600 –
b
a
c
N
4 N4 Made to 300 230… 220… 300 KTC-16ZL42B4 KTC-16ZL72B4
N
3 measure 600 600
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
Te 2/56
High power busbar trunking
Description : Canalis KTC (2000 A)
pages 10171/2 to 10171/9 IP 52 zed units
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
c
Edgewise ZC
b
N Edgewise ZC
1
a
N2 Made to 400… 350… 400… – KTC-20ZC43D2 KTC-20ZC73D2
measure 1000 1000 1000 –
b
Edgewise/flat CP
N
2
N1 Made to 300 280… 400 – KTC-20CP41A1 KTC-20CP71A1
measure 700 –
b a
measure 700 –
N1 N2
N3 Made to 300 280… 400 – KTC-20CP41A3 KTC-20CP71A3
measure 700 –
b
a
c
N
4 N4 Made to 400 350… 280… 300 KTC-20ZL42B4 KTC-20ZL72B4
N
3 measure 800 700
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
2/56 Te
High power busbar trunking
Description : Canalis KTC (2500 A)
pages 10171/2 to 10171/9 IP 52 zed units
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
c
Edgewise ZC
b
N Edgewise ZC
1
a
N2 Made to 400… 350… 400… – KTC-25ZC43D2 KTC-25ZC73D2
measure 1000 1000 1000 –
b
Edgewise/flat CP
N
2
N1 Made to 300 280… 400 – KTC-25CP41A1 KTC-25CP71A1
measure 700 –
b a
measure 700 –
N1 N2
N3 Made to 300 280… 400 – KTC-25CP41A3 KTC-25CP71A3
measure 700 –
b
a
c
N
4 N4 Made to 400 350… 280… 300 KTC-25ZL42B4 KTC-25ZL72B4
N
3 measure 800 700
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
Te 2/57
High power busbar trunking
Description : Canalis KTC (3000 A)
pages 10171/2 to 10171/9 IP 52 zed units
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
N Edgewise ZC
1
a
N2 Made to 400… 350… 400… – KTC-30ZC43D2 KTC-30ZC73D2
measure 1000 1000 1000 –
b
Edgewise/flat CP
N
2
N1 Made to 300 280… 400 – KTC-30CP41A1 KTC-30CP71A1
measure 700 –
b a
measure 700 –
N1 N2
N
4 N4 Made to 400 350… 280… 300 KTC-30ZL42B4 KTC-30ZL72B4
N
3 measure 800 700
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
Ni : position of neutral
2/58 Te
High power busbar trunking
Description : Canalis KTC (4000 A and 5000 A)
pages 10171/2 to 10171/9 IP 52 zed units
Selection guide :
pages 10172/2 and 10172/3
Characteristics : References
pages 10173/2 and 10173/3
Dimensions :
pages 10180/2 to 10184/3
N Edgewise ZC
1
a
N2 Made to 500… 510… 500… – KTC-iiZC43D2 KTC-iiZC73D2
measure 1000 1000 1000 –
b
Edgewise/flat CP
N
2
N1 Made to 300 360… 500 – KTC-iiCP42B1 KTC-iiCP72B1
measure 800 –
b a
measure 800 –
N1 N2
N
4 N4 Made to 500 510… 360… 300 KTC-iiZL42B4 KTC-iiZL72B4
N
3 measure 1000 800
(1) To order a made to measure component, see the procedure on pages 10185/2 to 10185/5.
(2) In the reference : replace ii with 40 for a rating of 4000 A.
with 50 for a rating of 5000 A.
Ni : position of neutral
Te 2/59
KSE-10DA4
KSE-10DA4
KSE-iiDBi11
KSE-iiDBi11
KT0-iiCB311
2/60 Te
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide :
KS tap-off units, IP 54 dust and damp proof series, for NF fuses
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3
References
Dimensions :
pages 10180/2 to 10184/3
Tap-off unit
Number of conductors 3L + N + PE 3L + PEN 3L + PE
Tap-off scheme
(2)
Tap-off scheme
(2)
KSE-05SF41 Rating Fuse Reference Reference Reference
A size mm2 Weight (kg) Weight (kg) Weight (kg)
Te 2/61
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide : KS tap-off units, IP 54 dust and damp proof series, for DIN and BS fuses
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3 References
Dimensions :
pages 10180/2 to 10184/3
Tap-off units
Number of conductors 3L + N + PE 3L + PEN 3L + PE
Tap-off scheme
(2)
Tap-off scheme
(2)
2/62 Te
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide : KS tap-off units, IP 54 dust and damp proof series, for equipment
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3 References
Dimensions :
pages 10180/2 to 10184/3
Tap-off scheme
(example with circuit-breaker)
(2)
Tap-off units for Merlin Gerin Compact NS fixed circuit breaker (3)
With extended rotary handle, short axis (3)
Number of conductors 3L + N + PE 3L + PEN 3L + PE
Tap-off scheme
(2)
Rating Type of Reference Reference Reference
A circuit-breaker Weight (kg) Weight (kg) Weight (kg)
Te 2/63
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide : Straight lengths
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3 Dimensions
References :
pages 10174/2 to 10179/5
“Feeder”
KTC-iiETiii
h (1)
L
Type of length L
Fixed 4000
Made to measure 500...3000
“Expansion”
KTC-iiDBiii
h (1)
390
3000
1000 1000
2000
Joint block
14
14
350 144
Rating (A) 1000 1350 1600 2000 2500 3000 4000 5000
(1) h 74 104 124 164 204 244 324 404
2/64 Te
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 and 10171/9
Selection guide : Straight lengths
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3 Dimensions
References :
pages 10174/2 to 10179/5
290
1500 500
2000
290 290
Te 2/65
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9 Feed units
Selection guide :
pages 10172/2 and 10172/3
Characteristics : Dimensions
page 10173/2 and 10173/3
References :
pages 10174/2 to 10179/5
Straight end feed boxes Flat elbow end feed boxes
KT0-iiERiii01 and KT0-iiERiii02 KT0-iiERiii03 and KT0-iiERiii04
b h (1)
140
h (1)
a
a
215
215
ERiii01 ERiii02
Rating (A) y a e a e Rating (A) y a b e
1000...1600 230 235 120 235...1000 80...250 1000...1600 230 200...1000 300...1000 80...250
2000...3000 350 235 120 235...1000 80...250 2000...3000 350 200...1000 300...1000 80...250
4000 and 5000 510 235 120 235...1000 80...250 4000 and 5000 510 200...1000 300...1000 80...250
Rating (A) y a b e
1000...1600 230 200...1000 300...1000 80...250
2000...3000 350 260...1000 400...1000 80...250
4000 and 5000 510 340...1000 500...1000 80...250
130 e e e 130 y
50 50
60 60
50
47,5 65 47,5
100
100
60
60
50 50
35 35
60
60
50
50
50 50 50 50 50 50 50 14x20 50
Rating (A) 1000 1350 1600 2000 2500 3000 4000 5000
Cross-section (mm) 70 x 6 100 x 6 120 x 6 160 x 6 200 x 6 2 x (120 x 6) 2 x (160 x 6) 2 x (200 x 6)
2/66 Te
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide :
Feed units
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3
Dimensions
References :
pages 10174/2 to 10179/5
Straight end feed boxes, flat outlets
KT0-iiERiii07
140
h (1)
a
100
100
Rating (A) y a e
130 e e e 130 y 1000...1600 230 235...1000 160...800
2000...3000 350 235...1000 160...800
4000 and 5000 510 235...1000 160...800
Rating (A) y a b e
130 e e e 130 y 1000...1600 230 200...1000 300...1000 160...800
2000...3000 350 200...1000 300...1000 160...800
4000 and 5000 510 200...1000 300...1000 160...800
Rating (A) y a b e
1000...1600 230 200...1000 300...1000 160...800
130 e e e 130 y 2000...3000 350 260...1000 400...1000 160...800
4000 and 5000 510 340...1000 500...1000 160...800
Te 2/67
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide : Accessories
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3 Dimensions
References :
pages 10174/2 to 10179/5
50 50 50 50 50 50 50 50 5 or 6
67,5 65 47,5
50 50
50
60
75
75
1000
1000
1000
1000
100 100 100 100
50
60
100
100
120
95
75
100
75
67,5 65
100
75
1000
1000
1000
1000
50 50 14 x 20 50 50 60 60 47,5 65 47,5 5 or 6
50
50
50
50
120
120
100
100
100
100
1000
1000
1000
1000
50
120
120
120
120
100
100
100
100
1000
1000
1000
1000
2/68 Te
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide :
Accessories
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3
Dimensions
References :
pages 10174/2 to 10179/5
Connection plates
KT0-20YA40236 KT0-25YA40236 KT0-30YA40336 KT0-40YA40436 KT0-50YA40536 KT0-20YA40235
50 50 14 x 20 50 50 50 50 50 50 50 50 55 50 55
6 6 6 6 6 5
65 47,5
65 47,5
50
50
50
60
120
100
100
110
120
102,5
95
50
100
110
110
65
50
100
50
100
100
102,5
50
100
100
110
50
100
50
100
50
50
50
120
110
110
110
110
50
50
50
50
Braids
,,,
KT0-iiYA4106
References L
50
KT0-16YA4106 100
6
KT0-25YA4106 100
=
L
KT0-20YA4106 120
=
KT0-30YA4106 120
600 300 150 KT0-40YA4106 120
KT0-50YA4106 120
300
97,5
17,5
12,5 12,5 16 x ø7
c
17,5
175 150 175
17,5
35 160 35 35 25 500 25 35
References a b c
KT0-16CS0 230 620 200...650
KT0-30CS0 350 620 200...650
KT0-50CS0 510 620 200...650
Te 2/69
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide :
Simple elbows, tees and zed units
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3
Dimensions
References :
pages 10174/2 to 10179/5
b
h (1)
b a α h (1)
Rating (A) a and b fixed a and b made to measure Rating (A) a and b fixed a and b made to measure α
1000...1600 300 301...1000 1000...5000 300 301...1000 90°
2000...3000 400 401...1000
4000 and 5000 500 501...1000
h (1)
α
b
b
a h (1)
140
a c
Rating (A) a and b made to measure α Rating (A) a, b and c made to measure
1000...5000 300...1000 91°...179° 1000...1600 300...1000
2000...3000 400...1000
4000 and 5000 500...1000
Flat zed units Edgewise zed units
KTC-iiZPiii KTC-iiZCiiii
h (1)
140
b
b
h (1)
c a h (1) a c 140
2/70 Te
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide :
Zed units
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3
Dimensions
References :
pages 10174/2 to 10179/5
Flat/edgewise zed units
KTC-iiCPiiii
b
h (1)
c
c
a h (1)
140
b
Rating (A) a b c
1000...1600 300 220...600 300
2000...3000 300 280...700 400
4000 and 5000 300 360...800 500
h (1)
c a d
140
d
Rating (A) a b c d
1000...1600 300 230...600 220...600 300
2000...3000 400 350...800 280...700 300
4000 and 5000 500 510...1000 360...800 300
Te 2/71
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide : Tap-off units
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3 Dimensions
References :
pages 10174/2 to 10179/5
Removable dust and damp proof tap-off units with/without isolator and fuse carriers
KSE-02CF5 KSE-02CD5
KSE-02CG5
8
8
160
160
50 43
8
50 90
8
93 93
KSE-16SFii
KSE-16SDii
KSE-16SGii
285
430 130 55
455 230
Cable outlet
2/72 Te
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide : Tap-off units with isolator and tap-off units with circuit breaker
pages 10172/2 and 10172/3
Characteristics :
pages 10173/2 and 10173/3 Dimensions
References :
pages 10174/2 to 10179/5
Removable dust and damp proof tap-off units with isolator for modular equipment
KSE-05DAi KSE-10DAi
195
270 50 113* 70 100 40
395 190 52
Cable outlet
Removable dust and damp proof tap-off units for Merlin Gerin circuit breaker
KSE-16DBi11 KSE-25DBi11
15
15
163
163
368
368
KSE-40DBi11
18
163
368
780 275
325
Cable outlet
Bolt-on dust and damp proof tap-off units for Merlin Gerin circuit breaker
KT0-iiCBi11
c
b
Reference a b c
a KT0-06CB 800 350 300
KT0-12CB 1200 550 300
Te 2/73
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide :
pages 10172/2 and 10172/3
Characteristics : Procedure for ordering a made to measure component
pages 10173/2 and 10173/3
References :
pages 10174/2 to 10179/5
The neutral is located next to the fixing hole closest to the end of the unit (a).
Definition of a component
Shape : each shape is characterised by a group of two letters (example : ET for a feeder length).
Dimensions : dimensions are always given in alphabetical order of the measurements (example : a x b x c, etc).
How to order
i Second line
Write the dimensions for the “made to measure” component and any of the options selected :
- If the reference corresponds to a made to measure product, there are one or more variable values : you should
write a x b x etc in alphabetical order.
- If the reference ends in A followed by a number, an option is available (see page 10185/5).
Straight lengths
The nominal length “L” of a straight length is measured from joint axis to joint axis, in millimetres (the joint axis is located
20 mm beyond the end of the bars).
Joint axis
L1
L2
L3
40 N
PE
= =
280
L
Example :
A KTC straight length, rating 1000 A, 3L + N + PE, 1820 mm long, has the following reference :
KTC-10ET42B
L = 1820
2/74 Te
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide :
pages 10172/2 and 10172/3 Procedure for ordering a made to measure component (continued)
Characteristics :
pages 10173/2 and 10173/3
References :
pages 10174/2 to 10179/5
Flat elbows
Example :
A KTC flat elbow, rating 1000 A, 3L + N + PE, type LP, N1 :
- length of limb a = 301 mm
- length of limb b = 500 mm
- angle = 130°
Edgewise elbows
KTC-10LC42B
301 x 500
Zed units
Example :
A KTC 4 limb zed unit, rating 1000 A, 3L + N + PE, ZL, type N3 :
- length of limb a = 300 mm
- length of limb b = 400 mm
- length of limb c = 500 mm
- length of limb d = 300 mm
d
b
Te 2/75
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide :
pages 10172/2 and 10172/3 Procedure for ordering a made to measure component (continued)
Characteristics :
pages 10173/2 and 10173/3
References :
pages 10174/2 to 10179/5
a
Example :
A straight end feed box for KTC run, rating 1000 A, 3L + N
+ PE, type N2 :
- length of limb a = 450 mm
- distance between N and L3 = 100 mm
- distance between L3 and L2 = 120 mm
- distance between L2 and L1 = 150 mm
Example :
b
A flat elbow end feed box, flat outlets for KTC run, rating
1000 A, 3L + N + PE, type N8 :
- length of limb a = 500 mm
- length of limb b = 400 mm
- distance between N and L3 = 250 mm
L1 - distance between L3 and L2 = 180 mm
- distance between L2 and L1 = 250 mm
L2
has the following reference :
L3
KT0-10ER43D08
N 500 x 400 x 250 x 180 x 250
Note : If the run has a feed unit at each end, an additional joint block will be required.
2/76 Te
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide :
pages 10172/2 and 10172/3 Options, installation precautions
Characteristics :
pages 10173/2 and 10173/3
References :
pages 10174/2 to 10179/5
Options
The degree of protection for standard references is IP 52. To obtain degree IP 54, “A1” should be added at the end of the
standard reference (degree IP 54 can only be obtained by factory assembly). Similarly, if the trunking is to be mounted
outside, “A2” should be added at the end of the standard reference. The product is supplied as IP 54 with an aluminium
cover.
Installation precautions
270 270
min min
Flat feed
50
100
Te 2/77
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide :
pages 10172/2 and 10172/3 Installation precautions (continued)
Characteristics :
pages 10173/2 and 10173/3
References :
pages 10174/2 to 10179/5
Edgewise distribution
1000 min
x x
100
min
The fixing distance takes into account the minimum measurement of 100 mm and measurements x of the tap-off units
(see pages 10184/2 and 10184/3).
Flat distribution
500 min
Fixing distance
3000
2/78 Te
High power busbar trunking
Description : Canalis KTC (1000 to 5000 A)
pages 10171/2 to 10171/9
Selection guide :
pages 10172/2 and 10172/3 Installation precautions
Characteristics :
pages 10173/2 and 10173/3
References :
pages 10174/2 to 10179/5
i Positioning of lengths
If you use floor height lengths (from 2.50 to 4 metres),
position the first joint correctly so that the tap-off outlets
are accessible and the fixing device can be mounted. To
ensure this, a minimum distance of 500 mm between the
floor and the first joint axis is required.
This operation requires a made to measure component
L1.
Tap-off outlet
1000
Office)
300
When the run has a blocking component at one or both ends (end feed box, elbows, tees, etc), above a height of 30 metres
an expansion unit should be used. There should be one expansion unit for every 30 metre section.
Te 2/79