Sie sind auf Seite 1von 2

SIEMER Pages: 1 of 2

PRE-COMISSIONING TEST REPORT


TECHNOLOGIES

Client : KRISHNAPANTHAM PORT COMPANY LTD.


Project : 6.6 KV SWITCH GEAR PANEL FOR WAGON LOADING SYSTEM
Location : SS-3
Feeder Detail : PANEL 02 – MR000 CONVEYOR CRD-1 (1) 700 KW
Equipment Details : CURRENT TRANSFORMER
Make : PARGATI ELECTRICALS PVT. LTD.
Sr. No.
R-11/153910 : CORE RATIO CLASS VA
Y-11/153858 : Core-1 150/1A 5P20 15
B-11/153979 : Core-2 150/1A 0.5 15

I. Insulation Resistance Measurement : ( Values in G )


Primary- Earth and Primary to Secondary tested with 2.5kV.
Secondary -Earth and Between Secondary tested with 500V.

R-Ph Y-Ph B-Ph


Primary - Earth 16.9 GΩ 12.0 GΩ 15.0 GΩ
Secondary 1/2- Earth 5.5/4.0 GΩ 6.0/6.5 GΩ 5.6/4.4 GΩ
Primary – Secondary 1/2 38.6/26.1 GΩ 34.0/16.8 GΩ 28.0/17.3 GΩ
Between Secondary 2.3 GΩ 6.65 GΩ 18.9 GΩ

II. CT SECONDARY WINDING RESISTANCE CHECK:

Terminal No. PHASE


R-CT Y-CT B-CT
1S1 – 1S2 6.8 Ω 6.8 Ω 6.7 Ω
2S1 – 2S2 2.1 Ω 2.1 Ω 2.3 Ω

________________________________________________________________________________________

Tested By : Vamish Umar Witnessed by Witnessed by:

SIEMER Technologies VSE Ltd KPPCL

Date :
SIEMER Pages: 2 of 2
PRE-COMISSIONING TEST REPORT
TECHNOLOGIES

III. Primary Injection Test :

Primary Current Amp Secondary Current Amp

Phase % Amp Core 1 Core 2

25 37.5 A 0.24 A 0.23 A

R- ph 50 75.0 A 0.49 A 0.49 A

100 150 A 0.98 A 0.99 A

25 37.5 A 0.23 A 0.24 A

Y-Ph 50 75.0 A 0.48 A 0.49 A

100 150 A 0.97 A 0.99 A

25 37.5 A 0.23 A 0.23 A

B-Ph 50 75.0 A 0.48 A 0.49 A

100 150 A 0.99 A 0.98 A

IV. Polarity Check :


Test set up with P1 +ve P2 -ve

S1 CLOCKWISE +ve kick with respect to S2

Result Core 1 Core 2

R-Ph OK OK

Y-Ph OK OK

B-Ph OK OK

CT found healthy : YES

________________________________________________________________________________________

Tested By : Vamish Umar Witnessed by Witnessed by:

SIEMER Technologies VSE Ltd KPPCL

Date :

Das könnte Ihnen auch gefallen