Circuit Breaker

FACTORY Requirement

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


Inspection substation

0
ELECTRICITY DU CAMBODGE

COOPER VCB 22KV


Vacuum Circuit Breaker FACTORY Requirement

GENERAL INFORMATION

CB Type VN2-24 Serial No.

Rate voltage (Ur) 24kV Pro. Date

Rated Current (Ir) 630A

Rate withstand current/(Ik: 31.5kV) Rated Short-circuit breaking

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


current Isc:31.5kA

Rated operation sequence/ 0-0.3s-C0-180s-CO

Rated duration of short circuit / 4s Charging Motor 110V DC

Opening Coil 110V DC Closing Coil 110V DC

VI Serial No. A B C

EP Serial No. A B C

Test norm IEC 62271-100 GB 1984

MECHANICAL FUNCTION TEST

Technical Test Result


Test Item
Requirement A B C

Clearance between contact(mm) 13 ± 1

Connection stroke (mm) 4±1

Bouncing time of closing contacts(ms) ≤2

Maximum Rebound during opening (mm) ≤2

Closing time (ms) 35~70

Opening time (ms) 20~50

Synchronization on closing (ms) ≤2

Synchronization on opening (ms) ≤2

Average closing speed (m/s, 6mm 0.8 ± 0.2

Average opening speed (m/s, 6mm 1.3 ± 0.2


1
ELECTRICITY DU CAMBODGE

Resistance test on main circuit (DC 100)

Resistance of main circuit (≤ 65 µΩ)

Phase A Phase B Phase C

54.3 52.8 52.3

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB

2
ELECTRICITY DU CAMBODGE

Daqo VCB 22KV


Vacuum Circuit Breaker FACTORY Requirement

GENERAL INFORMATION

CB Type DQV-24/1250-25 Serial No.

Rate voltage (Ur) 24kV Pro. Date

Rated Current (Ir) 630-3150A

Rate withstand current/(Ik: ) Rated Short-circuit

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


breaking current Isc:31.5 kA

Rated operation sequence/ 0-0.3s-C0-180s-CO

Rated duration of short circuit / s Charging 110V DC


Motor

Opening Coil V DC Closing V DC


Coil

VI Serial No. A B C

EP Serial No. A B C

Test norm IEC 62271-100 GB

MECHANICAL FUNCTION TEST

Technical Test Result


Test Item
Requirement A B C

Clearance between contact(mm) 11-13

Connection stroke (mm) 2.3 - 3.5

Bouncing time of closing contacts(ms) ≤2

Maximum Rebound during opening (ms) ≤2

Closing time (ms) 30~60

Opening time (ms) 20~40

Synchronization on closing (ms) ≤2

Synchronization on opening (ms) ≤2

Average closing speed (m/s, 6mm 0.6 – 1 3


Average opening speed (m/s, 6mm 1.2 – 1.8
ELECTRICITY DU CAMBODGE

Resistance test on main circuit (DC 100)

Resistance of main circuit ( µΩ)

630 A ≤ 45

1250 A ≤ 40

Contains no arm 1600 A ≤ 30

2000 A ≤ 25

2500 A ≤ 20

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


630 A ≤ 45

1250 A ≤ 40

Including the arm 1600 A ≤ 35

2000 A ≤ 35

2500 A ≤ 25

4
ELECTRICITY DU CAMBODGE

XD GCB 115KV
GIS- Gas Circuit Breaker FACTORY Requirement

1- Name Plate Check……….


2- Coil Check Test
Technical Requirement Measured
Coils Results
(Ω - at 20ºС) value

Closing Coil 52C 33± 5%

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


52T 19± 5%
Opening Coil
52T2 19± 5%

3- Assembly Dimension Check


Measured value Results
Stroke Technical
measurement Requirement A B C

Stroke 150-50+20
Contacting
27±2
stroke

4- Mechanical Operation Test

Control Voltage Operation Results

Close (80%Ua)

Close (65%Ua) 5 time close and open


Close (110%Ua) operation

Open (120%Ua)

25 time close
Rated (100%Ua)
25 time open

Opening Voltage ≤30%Ua Cannot act

5- Mechanical Characteristics test


a- Closing Operation

Measured value 5
Control Technical
Test item
Voltage Requirement A B C
ELECTRICITY DU CAMBODGE

Closing time limit (ms) 90~120


100%Ua
Closing Velocity(m/s) 1.7~24

Closing Discrepancy time limit (ms) ≤4


b- Opening operation
Measured value
Control Technical
Test item
Voltage Requirement A B C

Opening time limit (ms) 21~33


100%Ua

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


Opening Velocity(m/s) 4.1~4.8
Opening Discrepancy time limit
≤2
(ms)
c- Re-Closing Operation
Measured value
Control Technical
Test item
Voltage Requirement A B C

Closing-opening time
37~60
limit (ms)
Re-Closing
280~300
Velocity(m/s)
Closing time limit (ms) 90~120
100%Ua
Closing Velocity(m/s) 1.7~2.4
Secondary opening
21~33
time limit (ms)
Secondary opening
4.1~4.8
Velocity (m/s)
6- Disconnection Switch (DS)
Mechanical Characteristics Test
Opening Closing Results
Serial No.
Opening time (≤4s) Closing time (≤4s)
7- Fast Earthing Switch (FES)
Mechanical Characteristics test
Opening Closing
Serial No. opening opening Closing closing Results
time (≤8s) Velocity time (≤8s) Velocity(1.9-2.5m/s

6
ELECTRICITY DU CAMBODGE

XD- GCB 230KV


AIS-SF6 Circuit Breaker FACTORY Requirement

CB Type LW25-252 Serial No.

Rate voltage (Ur) 245kV Pro. Date

Rated Current (Ir) 2000A

Rate withstand current Ik: 31.5kA Rated Short-circuit breaking


current Isc:31.5kA, Ip:80kA

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


Rate peak withstand voltage Phase to phase Phase to earth

Rate short time p.f withstand voltage( Up) Rated SF6 gas pressure 0.6MPa
460kV

Lightning impulse withstand voltage 1050kV

Rated operation sequence/ 0-0.3s-C0-180s-CO

Rated duration of short circuit Charging Motor 110V DC/AC

Opening Coil 110 DC Closing Coil 110V DC

VI Serial No. A B C

EP Serial No. A B C

Test norm IEC 62271 GB 1984

1- Inspection of assembly dimension


Specification Measured Results
Inspection items
(mm) value
Stroke 230+2-5 A B C

Contact stroke 38±2

Overshoot gap in opening 20±8


Gap between cam and rolling wheel of
1.4±0.3
lever
Gap between and surface of the
positioning nut of closing spring of 12~47
positioning rod
2- Dimension adjustment measurement of mechanism
Specification Measured Results
Inspection items
(mm) value
Stroke F of opening magnet 2.8~3.2 A B C
7
Gap G between trigger and release 0.8~1.2
ELECTRICITY DU CAMBODGE

F-G 1.6~2.4

Stroke C of closing magnet 5.0~5.5

Gap D between trigger and release 2.0~2.5

C-D 2.5~3.5
Gap E between trigger and anti-pumping
1~2
rod
3- Measurement of resistance of operating coil:
Specification Measured Results
Closing and opening coils
(Ω) value

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


Closing Coil(52C) 33±1.5 A B C

Opening Coil(52T1)
19±2
Opening Coil(52T2)
4- Measurement of Resistance of main circuit (DC 100A)
Specification Measured Results
measurement Items
(µΩ) value
Resistance of main circuit ≤ 45 A B C
5- Mechanical operation test
Operation Result
test items Specification
Voltage
Manually slow open and
Operation is flexible
close for one time each
Operation at 30% rate Open of 3 times, no
30% Ua
voltage operation
Open and close for 30 time
Operation at rated and the operation is reliable
100% Ua
voltage Reclosing for 5 time and the
operation is reliable
open for 5 time and the
120%
operation is reliable
Operation at Max. voltage
Close for 5 time and the
110%
operation is reliable
open for 5 time and the
65%
operation is reliable
Operation at Min. voltage
Close for 5 time and the
80%
operation is reliable
6- Mechanical characteristic test
Closing characteristic
Technical Measured value
Control Results
Measurement items Requirement
Voltage A B C
(ms) 8
100%Ua Closing time 80~110
ELECTRICITY DU CAMBODGE

Synchronism among
≤4
three phase
Opening characteristic
Technical Measured value
Control Results
Measurement items Requirement
Voltage A B C
(ms)
Opening time 20~30

100%Ua Synchronism
≤3
among three phase

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


Reclosing characteristic
Technical Measured value
Control Results
Measurement items Requirement
Voltage A B C
(ms)
First opening time 20~30

Closing time 80~110

100%Ua 2sd opening time 20~35

CO time 50~70

OC Time 280~300
Motor charging inspection
Measured value
Inspection Technical Results
items Requirement(s) A B C

100%Ua 11±2
Test on SF6 gas pressure switch:
Low pressure alarm (MPa) Low pressure lockout (MPa)

Action Resetting Action Resetting

A B C A B C A B C A B C

0.55 0.55 0.55 0.56 0.56 0.56 0.50 0.50 0.50 0.51 0.51 0.51

0.50 0.50 0.50 0.51 0.51 0.51

Result
Standard of the manufacturer (20ºС)
SF6 pressure switch Low pressure alarm (MPa) Low pressure lockout

Action 0.55±0.03 0.50±0.03

Resetting Operating (0.01-0.05) 9


Test on SF6 gas leakage:
ELECTRICITY DU CAMBODGE

Inspection contents Specification Result

Annual SF6 g≤as leakage rate under


≤0.5% /year
the pressure of 0.6 MPa
Micro-Moisture test
Inspection Measured value (ppm)
Specification(ppm)
contents
A B C A B C
Micro-moisture
≤150
7- Disconnecting Switch (GW 4A-252DW)

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


Measurement of Technical requirement A B C
resistance of main
circuit ≤ 75 µΩ

10
ELECTRICITY DU CAMBODGE

CHINT VCB 22KV


Vacuum Circuit Breaker FACTORY Requirement

GENERAL INFORMATION

CB Type NN85-40.5T1250-25 Serial No.

Rate voltage (Ur) 40.4kV Pro. Date

Rated Current (Ir) 1250A

Rate withstand current/Ik: Short-circuit Drop-out Current

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


25 kA

Rated operation sequence/ 0-0.3s-C0-180s-CO

Rated duration of short circuit / Charging Motor 110V DC

Opening Coil 110V DC Closing Coil 110V DC

VI Serial No. A B C

EP Serial No. A B C

Test norm IEC

MECHANICAL FUNCTION TEST

Technical Test Result


Test Item
Requirement A B C

Clearance between contact(mm)

Connection stroke (mm)

Bouncing time of closing contacts(ms)

Maximum Rebound during opening (mm)

Closing time (ms) 50~100

Opening time (ms) 35~60

Synchronization on closing (ms) ≤2

Synchronization on opening (ms) ≤2

Average closing speed (m/s, 6mm

Average opening speed (m/s, 6mm


11
ELECTRICITY DU CAMBODGE

Resistance test on main circuit (DC 100)

Resistance of main circuit (≤ 55 µΩ)

Phase A Phase B Phase C

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB

12
ELECTRICITY DU CAMBODGE

GCB 115KV(CHMC)
SF6 Circuit Breaker FACTORY Requirement(GCB)

GENERAL INFORMATION

CB Type LW36/126W/T3150-40F Serial No.

Rate voltage (Ur) 115V Pro. Date

Rated Current (Ir) 3150A

Rate withstand current/Ik: Short-circuit Drop-out Current

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


40 kA

Rated operation sequence/ 0-0.3s-CO-180s-CO

Rated duration of short circuit / Charging Motor 110V DC

Opening Coil 110V DC Closing Coil 110V DC

VI Serial No. A B C

EP Serial No. A B C

Test norm IEC

MECHANICAL FUNCTION TEST

Technical Test Result


Test Item
Requirement A B C

Clearance between contact(mm)

Connection stroke (mm)

Bouncing time of closing contacts(ms)

Maximum Rebound during opening (mm)

Closing time (ms) 70±8

Opening time (ms) 35±5

Synchronization on closing (ms) ≤4

Synchronization on opening (ms) ≤3

Average closing speed (m/s, 6mm

Average opening speed (m/s, 6mm


13
ELECTRICITY DU CAMBODGE

Resistance test on main circuit (DC 100)

Resistance of main circuit (≤ 35 µΩ)

Phase A Phase B Phase C

Water Content of SF6 Circuit Breaker


Phase Dew Point Water Content of Ex-factory Standard
Temperature(ºС) SF6(ppm) (ppm)

A -41.4

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


B -41.9 ≤ 150
C -41.9
GCB 115KV(CHMC)
SF6 Circuit Breaker FACTORY Requirement(GCB)

GENERAL INFORMATION

CB Type LW36/126W/T3150-40 Serial No.

Rate voltage (Ur) 126V Pro. Date

Rated Current (Ir) 3150A

Rate withstand current/Ik: Short-circuit Drop-out Current


40 kA

Rated operation sequence/ 0-0.3s-CO-180s-CO

Rated duration of short circuit / Charging Motor 110V DC

Opening Coil 110V DC Closing Coil 110V DC

VI Serial No. A B C

EP Serial No. A B C

Test norm IEC

MECHANICAL FUNCTION TEST

Technical Test Result


Test Item
Requirement A B C

Clearance between contact(mm)

Connection stroke (mm)


14
Bouncing time of closing contacts(ms)
ELECTRICITY DU CAMBODGE

Maximum Rebound during opening (mm)

Closing time (ms) 60±8

Opening time (ms) 24~30

Synchronization on closing (ms) ≤3

Synchronization on opening (ms) ≤2

Average closing speed (m/s, 6mm

Average opening speed (m/s, 6mm

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


Resistance test on main circuit (DC 100)

Resistance of main circuit (≤ 40 µΩ)

Phase A Phase B Phase C

Water Content of SF6 Circuit Breaker


Phase Dew Point Water Content of Ex-factory Standard
Temperature(ºС) SF6(ppm) (ppm)

A,B,C -42.4 ≤ 150

Disconnector (Type GW4A-126D(GW)

DS Type GW4A-126D(GW) Serial No.

Rate voltage (Ur) 126V Pro. Date

Rated Current (Ir) 2000A Mechanism Type CJ2

Resistance of main circuit (≤ 130 µΩ)

Phase A Phase B Phase C

15
ELECTRICITY DU CAMBODGE

HY pact GCB115KV (GE)


SF6 Circuit Breaker FACTORY Requirement(GCB)

GENERAL INFORMATION

CB Type Hy pact 145 Serial No.

Rate voltage (Ur) 145V Pro. Date

Rated Current (Ir) 2500A

Rated lightning impulse withstand voltage 640kV

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


Rate power frequency withstand voltage 1min 275kV

Rate short-time withstand current 40kA

Rate duration of short-circuit 3s

Rate peak withstand current 100kA

Rated-pole-to-clear factor 1.5

Rated out-of-phase breaking current 10kA

Rated line-charging breaking current 50A

Rate SF6-gas pressure for interruption 0.64 MPa

Rated supply voltage of closing/opening device 110V DC

Rate supply voltage of motor 110V DC

Busbar Disconnector with commutation contacts 1600A-100V

Rated operation sequence/ 0-0.3s-CO-3min-CO

Test norm IEC 62271-100

MECHANICAL FUNCTION TEST

Technical Test Result


Test Item
Requirement A B C

Clearance between contact(mm)

Connection stroke (mm)

Bouncing time of closing contacts(ms)

Maximum Rebound during opening (mm) 16

Closing time (ms) 60-70


ELECTRICITY DU CAMBODGE

Opening time (ms) 35-39

Synchronization on closing (ms)

Synchronization on opening (ms)

Average closing speed (m/s)

Average opening speed (m/S)

Close- open time (ms) ≤ 80

Deat tim (OC) –(ms) ≤ 300

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


Motor current at rate voltage 12.84A

charging time of closing spring 2.57s

Heating resistor 684 ohm

Resistance test on main circuit (DC 100)

Resistance of main circuit (≤ µΩ)

Phase A Phase B Phase C

126 128 128

17
ELECTRICITY DU CAMBODGE

GCB-115KV (GE)
SF6 Circuit Breaker FACTORY Requirement(GCB)

GENERAL INFORMATION

CB Type GL312F3/4031P Serial No.

Rate voltage (Ur) 123 kV Pro. Date

Rated Current (Ir) 3150A

Rated lightning impulse withstand voltage 550kV

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


Rate power frequency withstand voltage 230kV

Rate short-time withstand current Is 40kA

Rate SF6-gas pressure for interruption 0.64 MPa

Rated supply voltage of closing/opening device 110V DC

Rate supply voltage of motor 110V DC

Rated operation sequence/ 0-0.3s-CO-3min-CO

Test norm IEC 62271-100

MECHANICAL FUNCTION TEST

Technical Test Result


Test Item
Requirement A B C

Clearance between contact(mm)

Connection stroke (mm) 146-154

Bouncing time of closing contacts(ms)

Maximum Rebound during opening (mm)

Closing time (ms) 62-72

Opening time (ms) 26-31

Synchronization on closing (ms) ≤4

Synchronization on opening (ms) ≤ 2.5

Average closing speed (m/s) 4-5

Average opening speed (m/S) 6.4-7 18

Close- open time (ms)


ELECTRICITY DU CAMBODGE

Deat tim (OC) –(ms)

Motor current at rate voltage 5.44A 5.63A 5.58A

charging time of closing spring ≤ 10

Heating resistor 684 ohm

Resistance test on main circuit (DC 100)

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


Resistance of main circuit (≤ 42 µΩ)

Phase A Phase B Phase C

19
ELECTRICITY DU CAMBODGE

ABB-GCB 230KV
SF6 Circuit Breaker FACTORY Requirement (GCB)

GENERAL INFORMATION

CB Type LTB145D1/B(CSB1/3P) Serial No.

Rate voltage (Ur) Pro. Date

Rated Current (Ir)

Rate withstand current/Ik: Short-circuit Drop-out Current

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


kA

Rated operation sequence/

Rated duration of short circuit / Charging Motor 110V DC

Opening Coil 110V DC Closing Coil 110V DC

VI Serial No. A B C

EP Serial No. A B C

Test norm IEC 62271-100

MECHANICAL FUNCTION TEST

Technical Test Result


Test Item
Requirement A B C

Clearance between contact(mm)

Connection stroke (mm)

Bouncing time of closing contacts(ms)

Maximum Rebound during opening (mm)

Closing time (ms) Max. 40ms

Opening time (ms) 19-25ms

Synchronization on closing (ms)

Synchronization on opening (ms)

Average closing speed (m/s, 6mm

Average opening speed (m/s, 6mm


20
Close- Open (CO) Max. 42ms
ELECTRICITY DU CAMBODGE

Open- Close (OC)

Charging time for motor Max. 15s

Resistance test on main circuit (DC 100)

Resistance of main circuit

LTB 72D1/B < 40 µΩ

TRANSMISSION DEPARTMENT(EDC) -TECHNICAL REQUIREMENT OF CB


LTB 145 D1/B < 40 µΩ

LTB 170D1/B < 46 µΩ

Phase A Phase B Phase C