ELECTRICITE DU CAMBODGE
Circuit Breaker
FACTORY Requirement
0
ELECTRICITY DU CAMBODGE
GENERAL INFORMATION
VI Serial No. A B C
EP Serial No. A B C
2
ELECTRICITY DU CAMBODGE
GENERAL INFORMATION
VI Serial No. A B C
EP Serial No. A B C
630 A ≤ 45
1250 A ≤ 40
2000 A ≤ 25
2500 A ≤ 20
1250 A ≤ 40
2000 A ≤ 35
2500 A ≤ 25
4
ELECTRICITY DU CAMBODGE
XD GCB 115KV
GIS- Gas Circuit Breaker FACTORY Requirement
Stroke 150-50+20
Contacting
27±2
stroke
Close (80%Ua)
Open (120%Ua)
25 time close
Rated (100%Ua)
25 time open
Measured value 5
Control Technical
Test item
Voltage Requirement A B C
ELECTRICITY DU CAMBODGE
Closing-opening time
37~60
limit (ms)
Re-Closing
280~300
Velocity(m/s)
Closing time limit (ms) 90~120
100%Ua
Closing Velocity(m/s) 1.7~2.4
Secondary opening
21~33
time limit (ms)
Secondary opening
4.1~4.8
Velocity (m/s)
6- Disconnection Switch (DS)
Mechanical Characteristics Test
Opening Closing Results
Serial No.
Opening time (≤4s) Closing time (≤4s)
7- Fast Earthing Switch (FES)
Mechanical Characteristics test
Opening Closing
Serial No. opening opening Closing closing Results
time (≤8s) Velocity time (≤8s) Velocity(1.9-2.5m/s
6
ELECTRICITY DU CAMBODGE
Rate short time p.f withstand voltage( Up) Rated SF6 gas pressure 0.6MPa
460kV
VI Serial No. A B C
EP Serial No. A B C
F-G 1.6~2.4
C-D 2.5~3.5
Gap E between trigger and anti-pumping
1~2
rod
3- Measurement of resistance of operating coil:
Specification Measured Results
Closing and opening coils
(Ω) value
Opening Coil(52T1)
19±2
Opening Coil(52T2)
4- Measurement of Resistance of main circuit (DC 100A)
Specification Measured Results
measurement Items
(µΩ) value
Resistance of main circuit ≤ 45 A B C
5- Mechanical operation test
Operation Result
test items Specification
Voltage
Manually slow open and
Operation is flexible
close for one time each
Operation at 30% rate Open of 3 times, no
30% Ua
voltage operation
Open and close for 30 time
Operation at rated and the operation is reliable
100% Ua
voltage Reclosing for 5 time and the
operation is reliable
open for 5 time and the
120%
operation is reliable
Operation at Max. voltage
Close for 5 time and the
110%
operation is reliable
open for 5 time and the
65%
operation is reliable
Operation at Min. voltage
Close for 5 time and the
80%
operation is reliable
6- Mechanical characteristic test
Closing characteristic
Technical Measured value
Control Results
Measurement items Requirement
Voltage A B C
(ms) 8
100%Ua Closing time 80~110
ELECTRICITY DU CAMBODGE
Synchronism among
≤4
three phase
Opening characteristic
Technical Measured value
Control Results
Measurement items Requirement
Voltage A B C
(ms)
Opening time 20~30
100%Ua Synchronism
≤3
among three phase
CO time 50~70
OC Time 280~300
Motor charging inspection
Measured value
Inspection Technical Results
items Requirement(s) A B C
100%Ua 11±2
Test on SF6 gas pressure switch:
Low pressure alarm (MPa) Low pressure lockout (MPa)
A B C A B C A B C A B C
0.55 0.55 0.55 0.56 0.56 0.56 0.50 0.50 0.50 0.51 0.51 0.51
Result
Standard of the manufacturer (20ºС)
SF6 pressure switch Low pressure alarm (MPa) Low pressure lockout
10
ELECTRICITY DU CAMBODGE
GENERAL INFORMATION
VI Serial No. A B C
EP Serial No. A B C
12
ELECTRICITY DU CAMBODGE
GCB 115KV(CHMC)
SF6 Circuit Breaker FACTORY Requirement(GCB)
GENERAL INFORMATION
VI Serial No. A B C
EP Serial No. A B C
A -41.4
GENERAL INFORMATION
VI Serial No. A B C
EP Serial No. A B C
15
ELECTRICITY DU CAMBODGE
GENERAL INFORMATION
17
ELECTRICITY DU CAMBODGE
GCB-115KV (GE)
SF6 Circuit Breaker FACTORY Requirement(GCB)
GENERAL INFORMATION
19
ELECTRICITY DU CAMBODGE
ABB-GCB 230KV
SF6 Circuit Breaker FACTORY Requirement (GCB)
GENERAL INFORMATION
VI Serial No. A B C
EP Serial No. A B C
21