© ABB Group
June 21, 2016 l Slide 1
ABB Protective Relay School Webinar Series
Disclaimer
ABB is pleased to provide you with technical information regarding protective
relays. The material included is not intended to be a complete presentation of
all potential problems and solutions related to this topic. The content is
generic and may not be applicable for circumstances or equipment at any
specific facility. By participating in ABB's web-based Protective Relay School,
you agree that ABB is providing this information to you on an informational
basis only and makes no warranties, representations or guarantees as to the
efficacy or commercial utility of the information for any specific application or
purpose, and ABB is not responsible for any action taken in reliance on the
information contained herein. ABB consultants and service representatives
are available to study specific operations and make recommendations on
improving safety, efficiency and profitability. Contact an ABB sales
representative for further information.
© ABB Group
June 21, 2016 l Slide 2
ABB Protective Relay School Webinar Series
He began his career with Areva T&D Ltd in New Delhi, India as a Power
Systems Engineer. He has worked on various EHV substation design
projects throughout India.
Bharadwaj Bharadwaj started at ABB as a consulting engineer for the Power systems
Vasudevan group. With a strong background in real time power system modelling, he
got to work on developing transient system models for a couple of
transmission planning projects under the group.
© ABB Group
June 21, 2016 | Slide 4
Learning objectives
© ABB Group
June 21, 2016 | Slide 5
Instrument transformer symbols
© ABB Group
June 21, 2016 l Slide 6
Purpose
© ABB Group
June 21, 2016 l Slide 8
Types of instrument transformers
Voltage transformation
Electromagnetic voltage transformer
Coupling capacitance voltage transformer
Current transformation
Electromagnetic current transformer
Optical current transformer
Rogowski coil
© ABB Group
June 21, 2016 l Slide 9
Voltage Transformers
© ABB Group
June 21, 2016 l Slide 10
Voltage transformer (VT/PT)
© ABB Group
June 21, 2016 l Slide 12
CCVT (CVT) - Coupling Capacitance Voltage Transformer
C1
Secondary Secondary
L
Passive
T LF CF Ferroresonance
Suppression
ZB ZB
C2 RF
Active RF LF
Ferroresonance
Suppression
N:1
© ABB Group
June 21, 2016 l Slide 14
Parameters that affect CCVT performance
© ABB Group
June 21, 2016 l Slide 16
CCVT frequency response
-10
Response - dB
-20
-30
Passive FSC
-40
-50
Active FSC
-60
© ABB Group
June 21, 2016 l Slide 18
IEEE C57.13 accuracy class
© ABB Group
June 21, 2016 l Slide 19
Current Transformers
© ABB Group
June 21, 2016 l Slide 20
Current transformers
Current transformer primary
connected in series with the line
Primary current is determined
entirely by system load and not by
CT secondary load
Free-standing
BCT - bushing mounted
Internal
External
Bus and cable
Ratio of transformation is
approximately inverse ratio of
© ABB Group
turns
June 21, 2016 l Slide 21
Equivalent circuit of a CT
© ABB Group
June 21, 2016 l Slide 22
Current transformer
Secondary winding should never be open-
circuited
Flux in the core, instead of being the difference of
the primary & secondary ampere-turns, will now
be due to the total primary ampere-turns acting
alone
This causes a large increase in flux, producing
excessive core loss & heating, as well as high
voltage across the secondary terminals
At zero crossing of ac (60 Hz) flux large voltage
spikes occur
© ABB Group
June 21, 2016 l Slide 23
How to choose a CT
Important main factors when selecting current transformers are:
Standard (IEC, IEEE or national)
Rated insulation level (service voltage)
Altitude above sea level (if >1000 m)
Ambient temperature (daily temperature or average over 24 hours)
Rated primary current
Rating factor (maximum continuous current)
Rated secondary current
Short-time current (Transients)
Dynamic current
Number of cores
Burdens (outputs) and accuracies for each core
Pollution level (creepage distance)
© ABB Group
June 21, 2016 l Slide 24
Selection of CTs
Transient performance
© ABB Group
June 21, 2016 l Slide 25
Steady state performance of CT
© ABB Group
June 21, 2016 l Slide 26
Steady state performance of CT
© ABB Group
June 21, 2016 l Slide 27
Steady state performance of CT
Excitation curves method
Exciting current requirements for a
given secondary voltage
Current obtained by applying
voltage to secondary terminals
Knee point
Log-log plot
Square decades
I.e. (.01,1) – (.1,10)
Tangent 45º line
© ABB Group
June 21, 2016 l Slide 28
ANSI accuracy class
Relaying accuracy classes for CTs are
defined with a “C” or “T” classification
Class C indicates that the transformer ratio can
be calculated
leakage flux is negligible
The CT ratio error can thus be calculated
The excitation characteristic can be used directly
to determine performance
Class T indicates that the transformer ratio can
only be determined by test
Leakage impedance is NOT negligible
© ABB Group
June 21, 2016 l Slide 30
ANSI accuracy class
Basis for classification
Error ≤ 10%
Current range 1 – 20 times normal
The classification defines how much voltage
the CT can supply to the output (burden)
without the CT core going into saturation
Standard accuracy classes, which may be
assigned for a relaying CT, are 50, 100, 200,
400 and 800
© ABB Group
June 21, 2016 l Slide 31
ANSI accuracy class
Standard chart for class C current transformers
© ABB Group
June 21, 2016 l Slide 32
Steady state performance of CT
© ABB Group
June 21, 2016 l Slide 33
Steady State Performance of CT
Consider a 1200:5 CT.
AT 10A the excitation voltage is
340V (from curve)
For this CT its Rsec is 0.418
ohms(vendor specific)
So the voltage lost in the CT
itself is 41.8V
So the relay accuracy class
should be 340-41.8=298V
© ABB Group
Steady State Performance of CT
1000
500 V
VSM
VX C400
230 V 10% error for 20 times rated
VK
secondary current (5 A)
Secondary Excitation Voltage, VS
1
0.001 0.01 0.1 1.0 10 100
Secondary Excitation Current, IE
© ABB Group
IEEE C57.13 accuracy class
© ABB Group
June 21, 2016 l Slide 36
IEEE C57.13 accuracy class
© ABB Group
June 21, 2016 l Slide 37
CT Transients
© ABB Group
June 21, 2016 l Slide 38
Transients in power system
© ABB Group
June 21, 2016 l Slide 39
D.C. saturation of a CT
© ABB Group
June 21, 2016 l Slide 40
Remnant Flux
Results from hysteresis Flux Density
R eactance
Air Core
Depends largely on the
Remnant , fR
instantaneous flux in the core S
© ABB Group
Remnant flux
© ABB Group
June 21, 2016 l Slide 42
Remnant Flux and DC Offset
Avoiding Saturation
VX I S Z S
Steady state
X
Effect of primary DC offset VX I S Z S 1
R
X
Effect of worst case saturation I S Z S 1
VX R
1 R
S
© ABB Group
Analyzing Transient Response of CT
© ABB Group
Core saturation effect in current
CT_Saturation_Curve.xls
© ABB Group
June 21, 2016 l Slide 47
Protective relay designs to address CT issues
© ABB Group
June 21, 2016 l Slide 48
REB670 operating principles
© ABB Group
June 21, 2016 l Slide 49
Quick operation for internal fault
Internal Fault
i_out
8
I_IN
6 I_OUT
4
2
0 When ID>Diff
1
6
11
16
21
26
31
36
41
46
51
56
61
66
71
76
81
Operation Level
Samples trip is issued
© ABB Group
June 21, 2016 l Slide 50
Proper and secure restraint REB670 detects this short
interval when i_in=i_out
External Fault with CT Saturation (after every fault current
zero crossing) and
restrain properly during
16
14 external fault
REB670 detects that
12 I_IN=I_OUT at the
10
beginning of the
external fault i_in
Current
i_out
8
I_IN
I_OUT
6
0
1 4 7 10 13 16 19 22 25 28 31 34 37 40 43 46 49 52 55 58 61 64 67 70 73 76 79
Samples
© ABB Group
June 21, 2016 l Slide 51
Fast open CT algorithm
REB670 detects that I_IN
Open CT
doesn't change while
1,6 I_OUT goes down when Diff Operation Level
some of the CTs are Must be set to higher
1,4
open/short circuited value than
1,2 Open CT Level
1
i_in
Current
i_out
0,8
I_IN
0,6 I_OUT
ID>Open CT Level
0,4 second condition
0,2 fulfilled & RED is
blocked
0
1
13
17
21
25
29
33
37
41
45
49
53
57
61
65
69
73
77
81
Samples
© ABB Group
June 21, 2016 l Slide 52
New Sensor Technology
Non-traditional
Instrument Transformers
© ABB Group
June 21, 2016 l Slide 53
New sensor technology
© ABB Group
June 21, 2016 l Slide 54
New sensor technology enables the digital substation
measurement
Fiber-optic current sensors IEC 61850 station
bus
Provides digital signals to
relays using IEC 61850-9-2LE
© ABB Group
June 21, 2016 l Slide 55
Rogowski coils
Primary conductor
i(t) i(t)
M
Winding
© ABB Group
June 21, 2016 l Slide 56
Rogowski coils
Advantages
High measurement accuracy, from less than 1% to 3%
Wide measurement range, up to 100s of kA
Wide frequency range, typically 0.1 Hz to 1.0 MHz
Can withstand unlimited short circuit current
Can be physically small or large for application flexibility
Applicable at all voltage levels
© ABB Group
June 21, 2016 l Slide 57
FOCS
Operating Principle of Optical Current Sensor
Faraday Effect: Left and right circular light waves travel at
different speed through optical material if magnetic field is present
Primary current produces magnetic field which induces a phase
shift FR of circularly polarized light
Optical phase shift is proportional to any instantaneous value of
primary current orthogonal linear retarder left and right circular
Michael Faraday light waves light waves
ca. 1842
source birefringence
modulator
photo
diode
current
reflecting conductor
signal fiber end
processor
André-Marie Ampère
R
𝑩 ∙ 𝑑𝒍 = 𝜇0 𝐼𝑒𝑛𝑐 fiber coil
𝐶
out
© ABB Group
Current-induced phase shift: fR = 4 V N I
Fiber-optic current sensor
Faraday Effect
© ABB Group
June 21, 2016 l Slide 59
Fiber-optic current sensor measuring principle
© ABB Group
June 21, 2016 l Slide 60
Fiber-optic current sensor
Applied to 400kV live tank circuit breaker
Conventional current
measurement
Circuit breakers
© ABB Group
June 21, 2016 l Slide 61
Electro-Optic Voltage Transducer
Pockels effect
feo
Electro-optic crystal
Bi4 Ge3 O12 (BGO)
Orthogonal linearly
polarized light waves x’
Phase shift proportional
to applied voltage
feo = c ⌡E.ds
y’
Electric field introduces refractive index difference for orthogonal light waves
Results in different speeds of light and differential phase shift
© ABB Group
Electro-Optic Voltage Transducer measuring principle
© ABB Group
New sensor technology enables the digital substation
© ABB Group
June 21, 2016 l Slide 65
Hybrid Solution using a Merging Unit (MU)
control house
SAM600-CT
© ABB Group
June 21, 2016
Digital Substation and IEC61850
Today IEC 61850 Station Bus
Replace wiring and legacy
protocols between bays
IEC 61850-8-
by digital communication
1
670 series REB500 650 series
Interface to field
Hardwired point to point
connections between
primary and all secondary
equipment
© ABB Group
Digital Substation and IEC61850
Tomorrow
IEC 61850-8-
1
670 series REB500 650 series
Digital substation
1) All signals digital, station and process
IEC 61850-8-1 2) Analog, status and commands
IEC 61850-9-2 3) Acquire once, distribute on a bus
FOCS
SAM600
Advantages
From copper wiring to process bus
Increased Safety: No open CT conditions, Shorting of VTs.
Less Material.
© ABB Group
June 21, 2016 l Slide 69
Conclusion
Conventional ITs
CCVT’s are commonly used in HV and EHV relaying applications
Transient response of the CCVT needs to be taken into
consideration
Current transformer application needs to consider both static and
dynamic performance when sizing
Time to saturation of a current transformer is an important criteria
in relaying
Burden is a critical factor in CT selection
Non-Conventional ITs
Non conventional instrument transformers avoid many of the
traditional concerns while improving safety and reliability
GIS and AIS solutions available
Hybrid solution with MU offers path to digital substation
© ABB Group
June 21, 2016 l Slide 70
Standards
© ABB Group
June 21, 2016 l Slide 71
Standards
ANSI C93.1-1990
Power-Line Carrier Coupling Capacitors and
Coupling Capacitors and Coupling Capacitor
Voltage Transformers (CCVT) – Requirements
(http://www.ansi.org)
© ABB Group
June 21, 2016 l Slide 72
Standards
ANSI/IEEE C57.13-1993
IEEE Standard Requirements for Instrument
Transformers (http://www.ansi.org)
IEEE C37.110-2007
Guide for the Application of Current
Transformers used for Protective Relaying
(http://standards.ieee.org/)
(http://standards.ieee.org/catalog/olis/relaying.html)
www.youtube.com/ABBSAProductsNAM
© ABB Group
© ABB Group