Beruflich Dokumente
Kultur Dokumente
mm
Grounding of
Industrial Power Systems
Editorially Revised
r, 1 9 6 0
A Report of the
Industrial Power Systems Committee
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
IEEE
NUMBER
142
Oct. 1956
Grounding of
Industrial Power Systems
Editorially Revised
September, 1 9 6 0
A Report of the
Industrial Power Systems Committee
Published by
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS
345 East 47 Street, New York, N. Y. 10017
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
PREFACE
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
CONTENTS
Page Page
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
ACKNOWLEDGMENT
D. M . ALLISON C. C. SAUNDERS
Westinghouse Elec. Corp. Chairman, Working Group, Chapter III
Tulsa, Oklahoma E. I. duPont de Nemours & Co.
Wilmington, Delaware
H . H . ANGEL
Chairman, Working Group, Chapter 11 J. M . SCHMIDT
Bethlehem Steel C o . General Electric Co.
Bethlehem, Pa. Schenectady. N . Y .
J. E. ARBERRY H. E. SPRINGER
Pittsburgh Plate Glass Co. Rayonier, Inc.
Pittsburgh, Pa. Port Angeles, Wash.
K . M . BAUSCH H. M . STEWART
Bechtel Corporation Humble Oil & Refining Co.
San Francisco, Calif. Baytown, Texas
A . J. BISSON T . O . S WE ATT
Consolidated Edison Co. of N . Y . Wearn, Vreeland, Carlson & Sweatt, In<.
New York, N. Y . New York, N . Y .
L . J. CARPENTER H. B. T H A C K E R
General Electric Co. Chairman, Working Group, Chapter I
Schenectady, N . Y . Westinghouse Electric Corp.
East Pittsburgh, Pa.
M . A . LELAND
Chairman, Working Group, Chapter IV B. F . T H O M A S , JR.
Burndy Engineering Co., Inc. N . A . Lougee & Co.
Norwalk, Conn. New Y o r k , N . Y .
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
CHAPTER I
SYSTEM GROUNDING
sideration, and o n the character of service required tem o r portion o f a s y s t e m m a y be said t o b e effec-
at the points of p o w e r consumption. tively g r o u n d e d w h e n for all points o n the system or
specified portion thereof the ratio o f zero-sequence
W h e r e an industrial p o w e r system consists of p o w e r reactance to positive-sequence reactance is n o t greater
generating equipment, transmission circuits, and dis- than three and the ratio of zero-sequence resistance
tribution circuits, the reasons for g r o u n d i n g these to positive-sequence reactance is not greater than
c o m p o n e n t s are often the same as for g r o u n d i n g one for any condition of operation and for any amount
similar c o m p o n e n t s of public utility systems and other of c o n n e c t e d generator capacity."
large p o w e r systems, and the m e t h o d s o f g r o u n d i n g
SYSTEM NEUTRAL
would generally be similar under like conditions o f
service. But in s o m e cases the reasons for g r o u n d i n g
and the m e t h o d s o f g r o u n d i n g certain c o m p o n e n t s o f
an industrial p o w e r system m a y differ a c c o r d i n g to
the requirements of manufacturing o r p r o c e s s opera-
tions.
DEFINITIONS
A g r o u n d e d system is o n e in w h i c h at least o n e
c o n d u c t o r o r point (usually the neutral point of
transformer o r generator w i n d i n g s ) is intentionally
grounded, either solidly o r through a current-limiting
device. V a r i o u s degrees o f g r o u n d i n g are used from
"solid" o r "effective" to the high-reactance g r o u n d i n g
obtained from a small g r o u n d i n g transformer used <c) G R O U N D E D - D E L T A S Y S T E M
only to secure e n o u g h g r o u n d current for relaying.
Figure 1.1
Diagram showing voltages to ground under steady-state conditions
1
Numbers refer to numbered references in bibliography at end of for (a) ungrounded system, (b) grounded-wye system,
this chapter. (c) grounded delta system.
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
FACTORS INFLUENCING CHOICE OF feeder has been r e m o v e d f r o m the system. Should
GROUNDED OR UNGROUNDED SYSTEM it happen that the same phase of t w o different feeders
b e c o m e faulted to g r o u n d at the same time, the faulted
Service Continuity
feeders cannot be located b y r e m o v i n g them from
F o r many years m o s t industrial plant distribution the system o n e at a time. It m a y be necessary to
systems have been operated u n g r o u n d e d at one or r e m o v e all feeders and restore them to service one
m o r e voltage levels. In m o s t cases this has been d o n e at a time c h e c k i n g the g r o u n d detector as each
with the thought o f gaining an additional degree of feeder is restored.
service continuity. T h e fact that any contact o c c u r r i n g
T h e location of a g r o u n d e d feeder o n an un-
between one phase o f the system and g r o u n d is un-
g r o u n d e d s y s t e m m a y be facilitated b y use o f various
likely to cause an immediate outage to any load, m a y
types o f locating apparatus. F o r example, an inter-
6
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
exist for s o m e time. T h e r e is hazard of s h o c k to current z e r o at w h i c h time the stored energy in the
personnel from such a condition should they bridge inductance o f the circuit is z e r o . T h e overvoltages
all o r part of the high impedance g r o u n d path, for thus d e v e l o p e d result f r o m transient oscillation in the
example, contacting the frame of the faulty machine. circuit capacitance and inductance, there being stored
This hazard is particularly bad because there are m o r e e n e r g y in the circuit capacitance at the time o f cur-
possible victims than in the case of persons familiar rent interruption. M o r e serious overvoltages can be
with electric systems w o r k i n g on a circuit. p r o d u c e d b y devices w h i c h interrupt b y forcing cur-
rent z e r o . Such devices as current-limiting fuses
must b e carefully applied because of this o v e r v o l t a g e
Abnormal Voltage Hazards
problem.
T h e possible o v e r v o l t a g e s on the u n g r o u n d e d sys-
tem m a y cause m o r e frequent failure of equipment Neutral g r o u n d i n g is not likely to reduce the total
than if the system w e r e g r o u n d e d . In s o m e cases magnitude o f o v e r v o l t a g e p r o d u c e d b y lightning or
these o v e r v o l t a g e s have caused failures on m o r e than switching surges. It can, h o w e v e r , distribute the volt-
o n e unit o f equipment at the same time. T h e s e m u l - age b e t w e e n phases, reducing the possibility of ex-
tiple failures are not necessarily confined to o n e cessive v o l t a g e stress o n the phase-to-ground insula-
feeder but m a y involve equipment on several different tion o f a particular phase.
feeders.
Static (See Chapter III)
A fault o n o n e phase of an u n g r o u n d e d system
places a sustained o v e r v o l t a g e on the insulation of Build-up o f o v e r v o l t a g e on p o w e r system c o n d u c -
ungrounded phases in a three-phase system. T h i s tors due t o static c h a r g e is not usually a p r o b l e m
overvoltage is 1.73 times the voltage n o r m a l l y on in m o d e r n plants with metal-enclosed circuits and
the insulation. T h i s o r other sustained o v e r v o l t a g e s equipment. Static c h a r g e o n m o v i n g belts can build
or the transient o v e r v o l t a g e s on the u n g r o u n d e d sys- up voltages w h i c h can be transmitted to the p o w e r
tem m a y not immediately cause failure o f insulation, system unless m o t o r frames are p r o p e r l y grounded.
but tend to reduce the life of the insulation. O v e r h e a d o p e n - w i r e lines m a y be subject to static
o v e r v o l t a g e s resulting f r o m certain atmospheric c o n -
T h e reduced o v e r v o l t a g e s experienced o n the ditions. A system g r o u n d connection, even of rela-
g r o u n d e d system are less likely to d a m a g e equipment tively high resistance, can effectively prevent static
o r insulation. v o l t a g e build-up.
P o w e r System Overvoltages 7
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
unfaulted phases will then b e considerably in excess ing these systems. The cost of grounding resistor or
of line-to-line voltage. A n o v e r v o l t a g e due to resonant impedance, however, does represent an extra cost of
or near resonant conditions can be encountered where the grounded neutral system.
tuned inductive-capacitive circuits are used such as for op- Grounding existing systems m a y be v e r y expensive
eration of welders. For example, if the welder is equip- because it m a y be necessary to add g r o u n d i n g trans-
ped with a series capacitor for power factor improvement, formers and their protective equipment, grounding
the voltage across the capacitor and across the trans- impedance if required, and a third current transformer
former winding are each many times the supply line-to- in all circuits to obtain ground-fault relaying o n all
line voltage. A ground fault on the connecting lead be- three phases.
tween the capacitor and the welder transformer imposes T h e r e should b e three overcurrent elements in the
this high voltage on the line-to-ground insulation of protective devices in a g r o u n d e d neutral system. This
every piece of electric equipment connected to these m a y require m o r e expensive m o t o r c o n t r o l devices in
lines. A grounded neutral system would prevent this over- rare cases, but the present practice is t o provide three
voltage by holding the phases to their approximate normal overcurrent elements in all l o w - v o l t a g e air circuit
voltage to ground. breakers. Usually it is not necessary to carry the
neutral wire a l o n g with the three-phase circuits un-
less the circuits supply single-phase loads connected
Restriking G r o u n d Faults from line-to-neutral as in 208Y/120-volt circuits
Field experience and theoretical studies have s h o w n supplying 120-volt lighting load. Therefore, there
is n o additional circuit c o s t t o charge against the
that arcing, restriking o r vibrating g r o u n d faults on
grounded-neutral arrangement. T h e additional costs
ungrounded systems can, under certain conditions,
of grounded-neutral transformers and controls with
produce surge voltages as high as six times normal
three overcurrent elements m a y s e e m significant when
line-to-line voltage. T h e conditions necessary for p r o -
c o m p a r e d with the cost of the devices, but w h e n addi-
ducing these overvoltages require that the dielectric
tional costs are considered as a fraction of the total
strength of the arc path build up at a higher rate
system cost they are generally v e r y small.
after each extinction of the arc than it did after the
preceding extinction or be the result of an intermittent
contact between line and ground. This phenomenon is un- T r e n d s in A p p l i c a t i o n o f S y s t e m G r o u n d i n g
likely to take place in open air between stationary con-
T h e basic reasons for system g r o u n d i n g are three-
tacts because such an arc path is not likely to develop
fold: First, to limit the difference o f electric potential
sufficient dielectric recovery strength. It may occur in
between all uninsulated c o n d u c t i n g o b j e c t s in a local
confined arcs where the pressure m a y increase after
area; second, to p r o v i d e for isolation o f faulty equip-
each conduction period. Neutral g r o u n d i n g is effec- ment and circuits w h e n a fault o c c u r s ; and third, to
tive in reducing transient voltage build-up from such limit overvoltages appearing on the system under
intermittent g r o u n d faults b y reducing neutral dis- various conditions.
placement from g r o u n d potential and reducing de-
structive effectiveness o f any high-frequency v o l t a g e T h e basic reasons for the selection o f ungrounded-
neutral systems is that such systems, particularly at
oscillations following each arc initiation or restrike.
480 and 2400 v o l t s , are slightly less expensive and
m a n y operators feel that the u n g r o u n d e d neutral sys-
Cost tem possesses a service continuity advantage because
the first g r o u n d fault m a y n o t cause a trip-out o f a
Grounded neutral systems may cost at most only a few circuit o r m o t o r . It will be noted that there is today
percent more than ungrounded neutral systems, depend- a divided opinion a m o n g operators as t o the relative
ing upon system voltage and whether it is an existing service continuity of g r o u n d e d and ungrounded-
or new system that is to be grounded. Equipment for neutral systems. M a n y operators feel that a grounded
208Y/120-volt systems almost universally provides for system gives them better overall service continuity
system neutral grounding and, therefore, does not in- than they have obtained f r o m an u n g r o u n d e d system.
volve any extra cost. Wye-connected unit substations
T h e r e has been an increasing trend t o w a r d g r o u n d -
for grounding 480-volt systems are standard but cost
ing industrial systems in o r d e r to o v e r c o m e s o m e of
from nothing more to about six percent more than delta-
the disadvantages attributed to u n g r o u n d e d operation.
connected substations. 2400-volt wye-connected trans-
In recent years a substantial percentage of n e w in-
formers for system neutral grounding of these systems dustrial substation transformers have been purchased
can be obtained at a slight cost premium over 2400-volt with w y e - c o n n e c t e d l o w - v o l t a g e windings suitable for
delta transformers. In addition there is the c o s t of neutral grounding.
the resistor or other g r o u n d i n g impedance if used.
In new installations these transformers offer the ad-
For system voltage of 4.16 and 13.8 kilovolts, wye- vantage that they can be operated ungrounded if desired
connected transformers are standard and, therefore, but possess an available neutral for easy addition of a
there is no price penalty, transformer-wise, for ground- grounding circuit at a later date.
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
METHODS OF SYSTEM GROUNDING degree of g r o u n d i n g p r o v i d e d in the system. A g o o d
guide in answering this question is the magnitude of
G r o u n d i n g the S y s t e m Neutral ground-fault current as c o m p a r e d to the system three-
phase fault current. T h e higher the ground-fault cur-
M o s t g r o u n d e d systems e m p l o y s o m e m e t h o d o f rent in relation to the three-phase fault current, the
grounding the system neutral at o n e o r m o r e points. greater the d e g r e e o f g r o u n d i n g in the system. In
T h e s e m e t h o d s are referred to as ( 1 ) solid g r o u n d - terms of resistance and reactance, "effective g r o u n d -
ing, ( 2 ) resistance grounding, ( 3 ) reactance g r o u n d - ing" of a system is defined o n page 5.
ing, and ( 4 ) ground-fault neutralizer g r o u n d i n g . E a c h
In m o s t generators, solid g r o u n d i n g , i.e., without
method, as named, refers t o the nature o f the external
external i m p e d a n c e , m a y permit the m a x i m u m ground-
circuit from system neutral to g r o u n d rather than t o
fault current f r o m the generator t o exceed the m a x i -
the degree o f g r o u n d i n g . In each case the impedance
m u m three-phase fault current w h i c h the generator
of the generator o r transformer, w h o s e neutral is
can deliver, and for w h i c h its windings are braced.
grounded, is in series with the external circuit. T h u s ,
Consequently, in cases w h e r e effective g r o u n d i n g of
a s o l i d l y - g r o u n d e d generator o r transformer m a y o r
a system is indicated, m o s t generators should b e
may not furnish "effective g r o u n d i n g " to the system,
g r o u n d e d through a reactor having a l o w o h m i c value,
depending o n its impedance.
w h i c h will limit generator phase-current during single
line-to-ground faults to a value n o greater than three-
CIRCUIT EQUIVALANT
phase fault current. In the case o f three-phase, four-
wire systems, limitation o f ground-fault currents to
100 percent o f the three-phase fault current is usually
I. UNGROUNDED practical w i t h o u t interfering with normal four-wire
operation.
3 RESISTANCE GROUNDED
Resistance Grounding
R - R E S I S T A N C E OF GROUNDING RESISTOR
N
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
( 3 ) T o reduce electric s h o c k hazards to personnel, mission lines. T h i s m e t h o d is a s e c o n d choice t o re-
caused by stray ground-fault currents in the sistor g r o u n d i n g , w h i c h p r o v i d e s g r o u n d relaying to
ground return path. disconnect the faulted circuit. It should b e noted that
failures in solid insulations, such as paper, varnished
( 4 ) T o reduce the m o m e n t a r y line v o l t a g e dip c a m b r i c and rubber, are not self-healing as insulator
occasioned b y o c c u r r e n c e and clearing of a flashovers are, and are not extinguished b y the use of
g r o u n d fault. the ground-fault neutralizer.
G r o u n d i n g at P o i n t s O t h e r T h a n S y s t e m Neutral
Ground-Fault Neutralizer 9
10
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
One Phase of A Delta System Grounded of the g r o u n d i n g transformer. T h e m e t h o d o f wind-
at the M i d - P o i n t ing is seen from Figure 1.3 to be such that w h e n these
three equal currents flow, the current in o n e section
W h e r e existing systems at 600 volts and b e l o w are
of the w i n d i n g of each leg of the c o r e is in a direction
supplied b y three single-phase transformers with m i d -
opposite to that in the other section o f the winding
taps available, it is possible to gain s o m e of the ad-
on that leg. T h i s tends to force the ground-fault cur-
vantages of neutral g r o u n d i n g b y g r o u n d i n g the m i d -
rent to have equal division in the three lines and
tap of one phase. The distribution of voltage stress
accounts for the l o w i m p e d a n c e o f the transformer
among the phases remains somewhat unbalanced (50 per-
to g r o u n d currents.
cent overvoltage to ground on one phase conductor).
The system is frequently found in electric utility service A w y e - d e l t a c o n n e c t e d transformer can also be
at 240 volts to supply 240/120 volts single-phase three- utilized as a g r o u n d i n g transformer. T h e delta c o n -
wire, and 240 volts three-phase three-wire simultaneously. nection must b e c l o s e d to p r o v i d e a path for the
zero-sequence current, but the delta can b e designed
SELECTION A N D DESIGN OF for any convenient v o l t a g e level. It m a y o r m a y not
SYSTEM GROUNDING ARRANGEMENTS be used to serve other loads. T h e w y e w i n d i n g must
Obtaining the S y s t e m Neutral be o f the same v o l t a g e rating as the circuit which
is to b e g r o u n d e d . Caution should be exercised in
T h e best w a y to obtain the system neutral for applying single-phase transformer units o f a rating
grounding purposes is to use source transformers o r such that the transformer v o l t a g e rating w h e n ap-
generators with w y e - c o n n e c t e d windings. T h e neutral plied line-to-neutral is not equal to or greater than the
is then readily available. Such transformers are avail- system line-to-line v o l t a g e . T h e reason for this is
able for practically all v o l t a g e s e x c e p t 240 volts. O n that transformer reactance varies inversely as the
new systems, 2 0 8 Y / 1 2 0 o r 4 8 0 Y / 2 7 7 - v o l t transformers square o f the v o l t a g e applied. T h e c o n n e c t i o n s o f the
may be used to g o o d advantage instead o f 240 volts. transformer are s h o w n in Figure 1.4.
For 2400-volt or 4800-volt systems, special 2400 w y e -
or 4800 w y e - c o n n e c t e d source transformers m a y b e
purchased or g r o u n d i n g transformers used.
^
^
Grounding Transformers
•+—
System neutrals m a y not be available, particularly
in m a n y old systems 600 volts o r less and m a n y
existing 2400-, 4800- and 6900-volt systems. W h e n J"
it is desired to g r o u n d existing delta c o n n e c t e d
systems, g r o u n d i n g transformers m a y b e used to
obtain the neutral. G r o u n d i n g transformers m a y b e
either of the z i g - z a g o r w y e - d e l t a type. T h e type o f
g r o u n d i n g transformer m o s t c o m m o n l y used is a
three-phase, z i g z a g transformer with n o s e c o n d a r y
winding. T h e internal c o n n e c t i o n o f this transformer
is illustrated in F i g u r e 1.3. T h e impedance o f the
transformer to three-phase currents is high s o that,
when there is n o fault o n the systems, o n l y a small
magnetizing current flows in the transformer winding.
T h e transformer i m p e d a n c e t o g r o u n d current, h o w -
\
>
Figure 1.4
ever, is l o w so that it allows high g r o u n d current to Vectors representing flow of current in wye-delta transformer used
as grounding transformer. Line-to-ground fault shown.
flow. T h e transformer divides the g r o u n d current
into three equal c o m p o n e n t s ; these currents are in
phase with each other and flow in the three w i n d i n g s T h e short-time k v a rating o f a g r o u n d i n g trans-
former is equal t o rated line-to-neutral voltage times
LINE LEADS rated neutral current. A g r o u n d i n g transformer, is
designed to carry its rated current for a limited time
o n l y such as 10 s e c o n d s o r o n e minute. H e n c e , it is
m u c h smaller in size than an ordinary three-phase
transformer o f the same rated kva.
A g r o u n d i n g transformer should be c o n n e c t e d to
the system in such a manner that the system will
always b e g r o u n d e d . F i g u r e 1.5(a) s h o w s a ground-
ing transformer with an individual line breaker for
c o n n e c t i o n directly t o the main bus of the system.
NEUTRAL LEAD
Figure 1.5(b) s h o w s a m e a n s o f connecting a ground-
ing transformer to a s y s t e m without an individual
[Q) WINDING SHOWN O N CORE <b) SCHEMATIC DIAGRAM
OF C O N N E C T I O N S
line breaker. I n this case, the g r o u n d i n g transformer
Figure 1.3 is c o n n e c t e d b e t w e e n the main transformer bank and
Diagram showing windings of core and schematic diagram
of connections of a 3-phase zigzag grounding transformer. its breaker. If g r o u n d i n g transformers are connected
11
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
resistance grounding is used to reduce the damage
which m a y result due t o a g r o u n d fault in the ma-
chine windings.
In m e d i u m - v o l t a g e systems, w h e n ground-fault p r o -
tection is desired, it is p r o v i d e d b y using standard
overcurrent relays. Positive tripping can b e a c c o m -
plished with l o w magnitudes o f fault current. F o r
this reason resistance g r o u n d i n g is used e x c e p t for
those cases w h e r e the size o f the s y s t e m is s o small
that the m a x i m u m available fault current is n o t t o o
high t o b e o b j e c t i o n a b l e .
12
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
Criteria for L i m i t i n g T r a n s i e n t O v e r v o l t a g e s 1 0
G r o u n d E a c h M a j o r S o u r c e B u s Section
W h e n a p o w e r s y s t e m is g r o u n d e d at the neutral
Multiple P o w e r Sources
of w y e - c o n n e c t e d m o t o r s , o r at the primaries o f
wye-delta s t e p - d o w n transformers, it is necessary to W h e n there are o n l y a f e w generators or p o w e r
g r o u n d a number o f these points simultaneously to transformer banks at a station, individual neutral
insure that the system will remain g r o u n d e d w h e n impedances are frequently used. W i t h this arrange-
one o r m o r e o f these loads are o u t o f service. C o n - ment, the neutral o f each generator o r main trans-
sequently, ground-fault current m a y be e x c e s s i v e l y f o r m e r bank is c o n n e c t e d directly t o its neutral i m -
high w h e n all g r o u n d e d points are in service. Since pedance w i t h o u t intervening switching equipment. N o
p o w e r sources are fewer in n u m b e r than loads and special operating instructions are required since each
are less likely to b e disconnected, they are pre- i m p e d a n c e is automatically c o n n e c t e d w h e n e v e r the
ferred as g r o u n d i n g points. O t h e r disadvantages o f c o r r e s p o n d i n g p o w e r s o u r c e is in use, and is d e -
g r o u n d i n g at the l o a d are: energized w h e n e v e r this s o u r c e is disconnected.
13
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
W h e n individual resistors are used, circulation of Calculation of Ground-Fault Currents
third harmonic currents b e t w e e n paralleled genera-
tors is not a p r o b l e m since the resistance limits the T h e magnitude of current w h i c h will flow in the
W h e n total ground-fault currents with several in- a terminal, the current will b e m o r e than 10 percent
it is suggested that neutral switchgear and a single In the case of delta-connected machines the inter-
resistor be considered for resistance g r o u n d e d systems. nal v o l t a g e t o neutral m a y be c o n s i d e r e d to be 100
W h e n o n l y o n e source is i n v o l v e d , but others are percent at the terminals and 50 percent at the mid-
to be added to the station in the future, it is sug- point o f the w i n d i n g s . T h e mid-points have the l o w -
gested that space be a l l o w e d s o that neutral switch- est potential with respect to the electric neutral of
gear can be added w h e n this b e c o m e s necessary. any part o f the winding. T h e r e f o r e , a g r o u n d fault at
14
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
any point In the w i n d i n g will p r o d u c e a g r o u n d fault to w h i c h it is c o n n e c t e d . W h e n a resistor is used
current o f 50 percent o r m o r e o f the resistor current between neutral and g r o u n d , the current rating o f the
rating. g r o u n d i n g transformer is based o n the resistor rated
current. In either case, the transformer is rated to
carry the required current for rated time without ex-
Reactance G r o u n d i n g ceeding its rated temperature limits. Many system
grounding devices are short-time rated. Care must be
In a reactance-grounded s y s t e m with a single line-
exercised in their application to insure that current will
to-ground fault, the ground-fault current m a y be
be automatically interrupted before the thermal limits of
computed from the f o r m u l a :
components are exceeded.
Ig = 3E (Resistance may
Xi + X% -|- Xo -\- 3X n usually be neglected)
Resistor Ratings
(U)
Xi = System positive-sequence reactance (ohms per T h e determination of the resistor o h m i c value, thus
phase) the magnitude o f ground-fault current, is based o n
X 2 = System negative-sequence reactance (ohms per ( 1 ) p r o v i d i n g sufficient current for satisfactory per-
phase) formance of the s y s t e m relaying scheme, and ( 2 ) lim-
Xo = System zero-sequence reactance (ohms per phase) iting ground-fault current to a value which will p r o -
duce minimum d a m a g e at the point o f fault. In m o s t
X n = Reactance of neutral grounding reactor (ohms)
cases, the ground-fault current is limited b y the neu-
E = Line-to-neutral voltage (volts)
tral resistor to a small fraction of that which would
Ig z= Ground-fault current (amperes) flow for a three-phase fault. T o determine the mini-
mum ground-fault current required, a diagram of the
system must be available, giving ratings of current
Solid G r o u n d i n g
transformers and types of relays for each circuit. This
In a system with solid neutral c o n n e c t i o n to g r o u n d , diagram should include consideration of future changes.
the ground-fault current for a single-line-to-ground
fault, m a y be c o m p u t e d from the formula:
T a b l e 1.1
Ig = 3E (1.2)
Xi -f- X% -f- Xo Selection o f G r o u n d i n g R e s i s t o r
15
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
T h e magnitude o f ground-fault current must b e Ig = Current through reactor for line-to-ground
sufficient for operation o f all relays. In general, if the fault
current is high e n o u g h t o operate the relays o n the
• F o r Xx of generators use transient reactance.
larger circuits, it will be adequate for the smaller cir-
cuits. T h e g r o u n d currents required for satisfactory **X a for turbine generator is same as sub-transient
operation of various types o f relays, expressed in reactance.
terms of current transformer rating, are given in T h e neutral-grounding reactor should b e selected
T a b l e 1.1. N o t e that the ground-fault current under to carry the available current under all practical oper-
all system operating conditions must equal o r exceed ating conditions. W i t h any g i v e n condition o f c o n -
the minimum required f o r relaying each circuit c o n - nected grounded-neutral sources, the addition of un-
nected to the system. T h i s value is established b y g r o u n d e d neutral s o u r c e s and loads will increase the
selecting the highest o f those currents w h i c h m e e t the current flow through the g r o u n d e d neutral c o n n e c t i o n s .
requirements o f the several conditions set forth in
T a b l e 1.1. Grounding Transformer Ratings
A n exception to this rule will be found in high-resis- T h e electrical specifications o f a g r o u n d i n g trans-
tance grounding in which the ground current will be former are:
limited to a very low value approximately equal to the
Voltage — t h e line-to-line v o l t a g e o f the system.
fundamental frequency system-to-ground capacitive charg-
ing current. This will usually be but a few amperes, Current — t h e m a x i m u m neutral current.
insufficient to afford selective ground-current relaying. Time — u s u a l l y designed t o carry rated cur-
rent for a short time, such as 10 sec-
Reactor Ratings o n d s o r 60 s e c o n d s .
T h e reactance of a neutral g r o u n d i n g reactor should Reactance — this quantity is a function of the ini-
be chosen to limit the g r o u n d current and the current tial s y m m e t r i c a l system three-phase
in the faulted phase t o the desired value. In o r d e r to short-circuit kva.
minimize transient overvoltages, the ground-fault cur- Determination o f grounding-transformer reactance
rent must not be less than 25 percent o f three-phase is based o n the f o l l o w i n g : T h e criterion for limiting
fault current. T h i s c o r r e s p o n d s t o a ratio o f Xo/Xi = transient o v e r v o l t a g e s in a s y s t e m is that the ratio
10. F o r reactance g r o u n d i n g o f generators, the cur- Xo/Xi should be equal to or less than 10 (if used in
rent in any w i n d i n g must n o t e x c e e d the three-phase series with a grounding resistor it is necessary only that
fault current. T h i s c o r r e s p o n d s t o a ratio o f XoJX% = the ratio Ro/Xo be 2 or greater. The criterion for using
1. T h i s establishes the criteria for m a x i m u m and grounded-neutral type lightning arresters is that Xo/Xi
minimum value o f neutral reactance. If the neutral should be equal to or less than 3. In a system having a
reactance is selected in a c c o r d a n c e with the f o l l o w i n g grounding transformer, its reactance is the principal part
relationship, the current in the w i n d i n g o f the faulted of Xo in the above criterion. A l s o , the positive-sequence
phase will not exceed the three-phase fault current o f reactance, Xt, is equal to the reactance of the system to
the machine regardless o f system reactance: initial symmetrical root-mean-square three-phase, short-
y _ Xi -Xo (1.3) circuit current. Thus, the grounding transformer re-
Xn 3 actance is a function of the initial symmetrical system
three-phase short-circuit kva.
where X n = Reactance o f neutral reactor
Xi = Generator positive-sequence subtransient O n a system otherwise u n g r o u n d e d , the g r o u n d i n g -
reactance transformer reactance, Xgt in o h m s per phase, re-
quired to p r o v i d e any specified X /Xi ratio is given
Xo = Generator z e r o - s e q u e n c e reactance
0
b y the f o l l o w i n g f o r m u l a :
H o w e v e r , the current w h i c h flows through the g e n -
x Xo/Xr X kv2 X 1000
erator neutral reactor itself is not independent o f System symmetrical 3-phase short-circuit kva
system constants, and m a y often e x c e e d the three- (1.9)
phase fault current of the machine. T h e current rat-
W h e n lightning arresters for grounded-neutral service
ing of a neutral reactor is determined b y the n u m b e r
are to be applied, the grounding-transformer neutral
and characteristics o f system sources and whether
should be solidly g r o u n d e d and its reactance m a y be
they are grounded o r u n g r o u n d e d .
determined b y :
T h i s rating (the thermal current r a t i n g ) , can be x = 3000 X kyg
calculated b y the following f o r m u l a : System initial symmetrical 3-phase short-circuit kva
3£ (1.4) (1.10)
I a =
9
Xx + X , + 3Xn) Special Problems
where: The Influence of Grounding Methods on Control
*Xi = System positive-sequence reactance Circuit Safety in Systems 600 Volts and Below
**X* = System negative-sequence reactance
Frequently, the safety o f a c o n t r o l circuit is offered
Xo = System zero-sequence reactance as a reason for a particular m e t h o d of grounding.
X n = Reactance of neutral-grounding reactor In all cases, w h e n m o t o r starter c o n t r o l circuits are
E = Line-to-neutral voltage set up without c o n t r o l p o w e r transformers, it b e c o m e s
16
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
evident that there are p r o b l e m s with regard t o circuit because of the limited system and the absence of
arrangement w h i c h must be considered in order to switching devices, is satisfactory from the standpoint
minimize operating difficulties and personnel hazards. of transient o v e r v o l t a g e s . Since n o p r o b l e m of relay
Accidental m o t o r starting due to faulty c o n t r o l cir- coordination is involved, the relaying problem is
cuits m a y b e associated with u n g r o u n d e d systems as simple.
well as m o s t types of g r o u n d e d systems.
Three-Phase, F o u r - W i r e Systems
17
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
11. Grounding Principles and Practice I I I — G e n e r a - — H . G. Barnett, Mill and F a c t o r y , M a y 1951 or
tor Neutral G r o u n d i n g D e v i c e s — A . A . Johnson, A I E E Transaction P a p e r N o . 55-689.
Electrical Engineering, M a r c h 1945, pp. 92-99.
16. S y s t e m Neutral G r o u n d i n g in Industrial Plants—
12. Grounding o f Industrial S y s t e m s — W . C. B l o o m - D . L . Beeman, A I E E National P o w e r Conference
quist, General Electric R e v i e w , A u g u s t 1951. P r o c e e d i n g s , Pittsburgh, Pa., A p r i l 1950.
13. Neutral vs. Corner-of-the-Delta Grounding — 17. N e w s Bulletin of the International A s s o c i a t i o n of
W . F. Strong, Electrical W o r l d , S e p t e m b e r 25,
Electrical Inspectors, Interim R e p o r t of A m e r i c a n
1950.
Research C o m m i t t e e o n G r o u n d i n g , M a r c h 1944.
14. Industrial P o w e r Systems H a n d b o o k , Chapters 5,
18. G r o u n d e d vs U n g r o u n d e d L o w - V o l t a g e A - C Sys-
6 and 7, M c G r a w - H i l l B o o k C o . , N e w Y o r k , N . Y .
tems—H. B. Thacker, AISE Paper and Disc,
15. W h y Ground L o w - V o l t a g e Distribution S y s t e m s ? I r o n & Steel Engineer, A p r i l 1954, pp. 65-72.
18
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
CHAPTER II
EQUIPMENT GROUNDING
GENERAL REASONS FOR GROUNDING path in the enclosure will result in arcing and heat-
ing at breaks and joints. If additional current capacity
T h e main purpose of equipment g r o u n d i n g is t o
is required in the return circuit it should be added
provide safety for operators, electricians, repairmen
b y means of c o n d u c t o r s inside the conduit or metallic
and the general public. T h i s is a c c o m p l i s h e d b y in-
enclosure, and not outside.
suring that in general all parts of steel structures,
m o t o r and generator frames, control equipment en-
Types of Equipment to be Grounded
closures, switchgear, cable armor, conduit, portable
electric equipment, and any metallic b o d y enclosing 1. Structures
or near an electric circuit w h i c h is accessible to per-
2. O u t d o o r Stations
sons, shall be at g r o u n d potential. T h i s is e m b o d i e d
in the rules o f the National Electrical C o d e and the 3. L a r g e Generators and M o t o r R o o m s
National Electrical Safety C o d e . 4. Conductor Enclosures
19
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
In isolated-phase stations, where a ground-fault G r o u n d i n g o f O u t d o o r Structures
relay protective scheme is used, it is necessary that
all of the stationary metallic parts of the switchgear Refer to G R O U N D I N G O F S T R U C T U R E S in
this chapter.
not at bus potential be c o n n e c t e d to a fault-current
bus, a section of the latter being p r o v i d e d for each
section of the main bus. In turn, each section of G r o u n d i n g o f O u t d o o r Station F e n c e
fault-current bus is connected to the station ground
A metal fence surrounding an o u t d o o r station should
bus through a current transformer
be grounded. A ground c o n d u c t o r of not less than N o .
Disconnecting switches directly bolted to a steel 1/0 A W G should be installed around the fence, ap-
structure need no further g r o u n d except that operat- proximately 12 to 24 inches away from it and about
ing pipes of all gang-operated disconnecting switches 12 inches deep. This should be brazed or w e l d e d to
should be further grounded b y a N o . 1/0 A W G extra ground rods installed at 10 foot to 40 foot intervals.
flexible c o p p e r cable or equivalent c o n n e c t e d directly All corner fence posts and posts adjacent to ground
above the operating handle and run to the nearest rods should be c o n n e c t e d to the g r o u n d c o n d u c t o r s
part of the grounded supporting structure. being sure to connect to fence strands at these points.
20
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
Figure 2.1
Typical methods of connecting copper weld ground rod
to steel tower using welding method.
General C o m m e n t s
GROUNDING OF LARGE G E N E R A T O R
AND MOTOR ROOMS
21
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
in order to keep the resistance of the g r o u n d bus t o to the point w h e r e the c o n d u c t o r s in the raceway
earth as l o w as possible. E a c h floor should have its system c o n c e r n e d receive their supply.
o w n ground bus.
T h e lead sheaths, shields and a r m o r of three c o n -
F o r mechanical strength, the g r o u n d bus should not ductor and small single c o n d u c t o r (less than 500,000
be smaller than N o . 2 / 0 A W G c o n d u c t o r . Small sta- circular mils) p o w e r cables should be grounded at
tions m a y require N o . 4 / 0 , while large o n e s m a y use both ends. In l o n g cables it is sometimes desirable
500,000 o r 750,000 circular mil size. In extreme cases, that sheaths also be g r o u n d e d at several intermediate
where extremely high ground-fault currents m a y be points.
expected, larger sizes m a y be required.
T h e lead sheath, shield and a r m o r o f large single-
Connections to building c o l u m n s should be not less c o n d u c t o r cables (500,000 circular mils and a b o v e )
than N o . 2 / 0 A W G and be m a d e b y brazing, w e l d i n g should be g r o u n d e d at o n e end o n l y to prevent cir-
or with suitable solderless terminals. G r o u n d c o n n e c - culating currents. T h e sheath, shield and armor of
tions from transformers, switchgear, m o t o r s and g e n - such a cable should b e insulated from g r o u n d through-
erators to the g r o u n d bus should be not less than out the remainder o f its length unless the cable is
N o . 1/0 A W G but must not be smaller in current- too long, in w h i c h case insulating joints must b e p r o -
carrying capacity than 25 percent o f the highest vided to permit g r o u n d i n g at a sufficient number of
continuous rating o f any piece o f primary apparatus points to keep sheath v o l t a g e s d o w n to desirable
to which it is connected. L a r g e generators, m o t o r s limits. F o r example, the mutual reactance t o neutral
and transformers should have t w o c o n n e c t i o n s to the (X )
m for a 500,000 circular mils standard strand cable
ground bus. A l o n g r o w o f switchgear units should varnished c a m b r i c insulated, lead sheathed (approxi-
have a ground connection from each end o f same. mate outside diameter 1.5 inches) with equivalent
Connections to the equipment to be g r o u n d e d m a y spacing between cables o f 3 inches, is approximately
be brazed, w e l d e d or m a d e with suitable solderless 0.0525 o h m per 1000 feet. A s s u m i n g a current (7c)
terminals. of 400 amperes in the c o n d u c t o r , the induced voltage
to neutral per 1000 feet can b e calculated from the
T w o typical g r o u n d i n g systems are s h o w n in F i g - formula:
ures 2.3 and 2.4.
22
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
Figure 2.3
Typical grounding system for a building and
heavy electric apparatus in the building.
23
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
In ice houses, packing plants, etc., w h e r e a great Common Grounding Conductor for Circuits,
deal of moisture is present and w h e r e conduits are Metal Raceways, and Equipment
attached to metal cabinets, cutout, pull, o r junction
b o x e s b y means o f l o c k nuts and bushings, these c o n - T h e g r o u n d i n g c o n d u c t o r of an interior wiring sys-
duits should be b o n d e d together. tem m a y also be used as the g r o u n d i n g c o n d u c t o r
for equipment, conduit, and other metal raceways or
Grounding Connectors enclosures for c o n d u c t o r s , including service conduit
or cable sheath and service equipment, p r o v i d e d such
T h e grounding c o n d u c t o r should be attached to the
g r o u n d i n g c o n d u c t o r meets the current-carrying ca-
grounding electrode b y means o f ( 1 ) a suitable bolted
pacity requirements for service raceways, and provided
clamp of cast b r o n z e , brass or plain o r malleable
further, that the s e c o n d a r y distribution circuit supply-
cast iron, o r ( 2 ) a pipe fitting , plug, o r other suit-
ing the interior wiring system has at least o n e addi-
able device, screwed into the pipe o r into the fitting,
tional g r o u n d at the transformer o r elsewhere.
or ( 3 ) by brazing, w e l d i n g o r the equivalent. Soldered
connections shall not be used. W h e r e practicable the
point of attachment should be accessible. GROUNDING OF MISCELLANEOUS
Ground clamps for use o n c o p p e r water tubing and LARGER MOTORS
copper, brass o r lead pipe should preferably be o f
Method of Obtaining Ground Connections
copper and these for use on galvanized o r iron pipe
should preferably be o f galvanized iron to prevent All larger m o t o r frames should be g r o u n d e d with
electrolysis. the g r o u n d i n g c o n d u c t o r equipped with c o p p e r ter-
T h e sheet metal strap type of g r o u n d clamp is not minal brazed thereto, o r with a suitable solderless
considered adequate unless it has a rigid metal base terminal fastened to the m o t o r beneath the head of
seated on the water pipe o r other electrode and the an end shield bolt, o r b y means o f a 5/16 inch (mini-
strap is of such material and dimensions that it is m u m ) bolt tapped into a suitable place o n the m o t o r
not liable to stretch during o r after installation. frame. Soldered terminals should not be used. A
washer should b e used between b o l t head and ter-
Mechanical protection should be p r o v i d e d for the
minal lug. A t t a c h m e n t under head of foot bolt should
ground wire and connections, if it is necessary. I f a
not be used. T h e other end o f the grounding c o n -
ground wire is installed in a steel conduit, it should
ductor should be fastened with suitable clamps or
be connected at each end o f the conduit to reduce the
terminals to the rigid metallic conduit o r t o the nearest
impedance o f the circuit.
available g r o u n d . T a p s from a g r o u n d bus to larger
T h e point of connection of the g r o u n d i n g c o n d u c t o r m o t o r s and generators m a y b e c o n n e c t e d directly to
to interior metal raceways, cable a r m o r and the like the bed plate. A l s o refer to National Electrical Code.
should be as near as practicable to the point of power
supply.
Size of Grounding Conductors
T h e grounding c o n d u c t o r , b o n d , o r b o n d i n g j u m p e r
should be attached to conduits, cabinets, equipment
In the case of exceptionally large high-current-rated
and the like, b y means o f suitable lugs, pressure c o n -
rotating machines, grounding conductors of 500 to 750
nectors, clamps o r other suitable means. S o l d e r e d c o n -
M C M may be appropriately used. Even larger cross
nections shall not be used.
sections occasionally find application.
24
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
It is desirable that such equipment b e operated from so as to m a k e contact with any o f the line contacts
a w y e - c o n n e c t e d system with its neutral g r o u n d e d in the receptacle. W h e n a plug is inserted in a recep-
through a resistor w h i c h limits ground-fault current tacle, the g r o u n d contact must engage before any of
to 50 amperes o r less. Suitable ground-fault relaying the line contacts make contact.
should be provided .
Maintenance
P o r t a b l e E q u i p m e n t 600 V o l t s o r L e s s
G r o u n d i n g o f portable electric equipment can be
( a ) Portable equipment operating at line v o l t a g e s
a hazard instead o f a safeguard if not properly in-
of 600 volts o r less, e x c e p t for single-phase circuits
stalled and maintained. T h e following precautions
of 150 volts and b e l o w rated not o v e r 15 amperes,
should be o b s e r v e d :
should be g r o u n d e d through a separate g r o u n d i n g
wire or wires (either bare or colored green) in the con- ( a ) Care must b e taken that o n l y the green c o n -
necting cable equal in current-carrying capacity to the d u c t o r is c o n n e c t e d to the parts to be grounded.
largest line conductor. If the cable is not permanently ( A s specified b y National Electrical C o d e )
connected at each end, grounding should be through
separate grounding contacts in the power plug and re- ( b ) Portable t o o l s should b e c h e c k e d for proper
g r o u n d i n g - c o n d u c t o r c o n n e c t i o n s each time they
ceptacle.
are passed to the operator.
( b ) Portable equipment operating from a single-
phase circuit at 150 volts and b e l o w and rated not ( c ) A l l portable cables and their associated plug
over 15 amperes should be g r o u n d e d through a sepa- equipment should be inspected at regular inter-
rate grounding wire (colored green) in the connecting vals.
cable equal in current-carrying capacity to the line con-
ductors. Grounding should be through separate ground- BIBLIOGRAPHY
ing contacts in the plug and receptacle. In new instal-
lations, receptacles of the type having two parallel line 1. Principles and Practices in Grounding — EEI
contacts and one grounding contact should be used ex- Publication N o . D - 9 , 1936.
clusively. It is desirable that existing t w o - c o n t a c t 2. Bureau o f Standards — T e c h n o l o g i c Paper 108-
receptacles be replaced with the a b o v e g r o u n d i n g re- G r o u n d C o n n e c t i o n s for Electric Systems.
ceptacles w h e r e v e r practicable, but until this is d o n e ,
an adapter ( n o w available) can be used to convert the 3. National Electrical C o d e , National Fire Protection
two-terminal to a three-terminal grounding-type re- A s s o c i a t i o n , B o s t o n 10, M a s s .
ceptacle.
4. National Electrical Safety C o d e , National Bureau
( c ) N o t e that portable lamps with n o n - c o n d u c t i n g of Standards, W a s h i n g t o n 25, D . C .
guards and sockets need not be g r o u n d e d . Special c o n -
5. National Bureau o f Standards H a n d b o o k H 4 3 .
sideration must also b e given t o certain equipment,
such as soldering irons, w h e r e g r o u n d i n g m a y c o n - 6. E n g i n e e r i n g Practice — G r o u n d i n g Systems for
stitute a hazard. Generating Stations and Substations G E U - 2 4 D . —
General E l e c t r i c C o .
General Comments
7. E n g i n e e r i n g Standards. E1P, E. I. DuPont de
( a ) A l t h o u g h neutral c o n d u c t o r s are g r o u n d e d at Nemours Co.
the source, they should never be used for equipment
8. S o m e Fundamentals o f E q u i p m e n t G r o u n d i n g Cir-
grounding.
cuit Design, R . H . Kaufmann, A I E E Trans., Appl.
( b ) Equipment g r o u n d i n g c o n d u c t o r s if insulated, & Indus., N o v . 1954, pgs. 227-31.
should be identified with green c o l o r c o d e as speci-
9. I r o n Conduit I m p e d a n c e Effects in G r o u n d Circuit
fied b y National Electrical C o d e .
Systems, A . J. Bisson and E. A . Rochau, A I E E
( c ) It is assumed that an adequate g r o u n d c o n n e c - Trans., Appl. & Indus., V o l . 73, July, 1954, pgs. 104-6.
tion will b e available at the fixed end o r receptacle
10. Voltage Gradients Through the Ground Under Fault
of a portable g r o u n d i n g cable. In general, this should
Conditions, A I E E Committee Report, A I E E Trans-
consist of a direct c o n n e c t i o n to the steel frame of a
actions, P o w e r Apparatus and Systems, October 1958,
building o r other structure w h i c h has been suitably
pages 669-692.
g r o u n d e d o r to the g r o u n d bus of the building. If
such a g r o u n d c o n n e c t i o n is not available, it m a y be 11. Impedance and Inductive Voltage Measurements on
necesary to carry a separate g r o u n d i n g c o n d u c t o r Iron Conductors, W . F. Mackenzie, A I E E Transac-
from the point of c o n n e c t i o n o f the portable cable tions, V o l . 73, 1954, Part I, page 577.
with the supply line b a c k t o a suitable g r o u n d point.
12. Application Guide on Methods of Substation Ground-
( d ) T h e g r o u n d i n g contact in a c o n n e c t i o n plug ing, A I E E Committee report, A I E E Transactions.
should be s o designed that it can never be inserted V o l . 73, 1954, Part I I I A , page 271.
25
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
CHAPTER III
— STATIC GROUNDING —
26
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
T h e degree o f electrostatic charge that m a y exist T A B L E 3.1
between t w o materials will b e proportional t o the
difference in their dielectric constants. A l s o , the p o s i - Range of Static Voltages
tive charge will usually s h o w up o n the material Produced by Various Processes
having the highest dielectric constant. Type of Equipment Voltage Range Observed
Belted D r i v e s 60,000 — 100,000
Speed of Separation Fabric H a n d l i n g 15,000— 80,000
Paper M a c h i n e s 5,000 —100,000
A s the speed o f separation of t w o o p p o s i t e l y c h a r g e d Tank Trucks up to 25,000
substances is increased, the greater the chance for Belt C o n v e y o r s ( G r a i n ) up to 45,000
i m p o u n d i n g the charges o n the materials, thus increas-
ing the potential differences b e t w e e n them. F r o m the table o f sparking distances given in T a b l e
3.2 it can be seen that even v o l t a g e s o f 25,000 volts
Effect of Motion m a y j u m p o v e r o n e inch, such a spark could readily
release e n o u g h e n e r g y to ignite flammable mixtures.
W h i l e friction is not necessarily the cause o f static
charges, it d o e s have the effect o f increasing the F o r a c o m p l e t e discussion o n the explosive limits
degree o f electrification; this m a y be attributed t o of various gas and liquid mixtures as well as the
the m o t i o n permitting m o r e particles o f o n e o f the spark e n e r g y required to ignite such mixtures, refer-
substances c o m i n g into c o n t a c t with the other sub- ence is m a d e to the article "Industrial Fires and
stance; this is particularly true in the flow o f liquids E x p l o s i o n s from Electrostatic O r i g i n " and the b o o k
4
Area in Contact
METHODS OF TESTING FOR STATIC 6
27
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
N e o n T u b e Tester Such an instrument is listed b y U n d e r w r i t e r s ' L a b o r a -
tories for Class I G r o u p s " C " and " D " hazardous
This device is v e r y inexpensive and can be carried
locations.
readily so occasional c h e c k s for static can be m a d e ;
however, it m e r e l y indicates the presence of static
H A Z A R D S IN V A R I O U S T Y P E S OF
and contains no instrument to indicate the v o l t a g e
INDUSTRIES
that m a y exist.
Industries
V a c u u m T u b e V o l t m e t e r and See T a b l e 3.3 for a summation o f the following data.
Vacuum Tube Electrometer
A v i a t i o n Industry. Several fatal e x p l o s i o n s and fires
T h e s e instruments m a y be used to detect the pres- have been the result of liquid m o v e m e n t ( g a s o l i n e )
ence of static electricity but they should have v e r y in this industry. T h e loading o f airships with fuel
high input impedance s o as to limit current drain. is extremely hazardous, and the possibility of static
Instruments are available with input impedances of discharge is always guarded against b y the use of
the order of 1 0 o h m s . If a c o m m e r c i a l type of in-
1 5
g r o u n d networks, etc.
strument is not available an electron tube detector
as described in the next paragraph m a y be c o n - Chemical Industry. T h e m o v e m e n t o f liquids and
structed. gases within the p r o c e s s itself can be responsible for
the creation of electric charges. T h e s e may accumu-
Electron T u b e Detector late o n u n g r o u n d e d c o n d u c t i n g surfaces in sufficient
This detector s h o w n in Figure 3.1 operates in the quantity to result in a static spark to adjacent c o n -
following manner: T h e tube current is adjusted in ducting structures. In the presence of highly c o m -
the plate circuit to s o m e value near the mid-point bustible material o r e x p l o s i v e atmospheres, such
of the characteristic grid voltage—plate current spark discharges are to be a v o i d e d by appropriate
curve b y means of the " C " battery. T h e sensitivity means such as leakage circuits to ground.
of the circuit is determined b y the grid leak, " R " .
Coal Industry. M a n y mine e x p l o s i o n s have been at-
tributed to the accumulation of coal dust and the
m o v e m e n t of particles. M o r e than ordinary precau-
TUBE TYPE 164-G
PROBE k OUTPUT tions against possibility of static discharge spark must
] 3 MlLLlAMPERES
be taken to avoid u n d e r g r o u n d explosions.
B= 4 5 VOLTS
F l o u r and Grain Industry. Material m o v e m e n t and
R =5- MEGOHMS the machinery of manufacture can be responsible for
charge accumulation and resulting static discharge.
Fine particles of grain dust suspended in the air afford
an excellent source o f explosive.
28
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
presence o f lint in the air is d a n g e r o u s . Static dis- Humidity Control
charges from l o o m s , belt drives, and other m a c h i n e r y
have caused fires in m a n y cases. W h e r e high humidity d o e s not affect the material,
this affords o n e o f the best w a y s o f c o n t r o l l i n g static.
Steam ejected into the area, especially near the point
Institutions and Commercial Establishments w h e r e static is accumulating, is perhaps the best w a y
of supplying additional humidification. T h e minimum
Hospitals. M i x t u r e s o f air and certain anesthetics
value o f relative humidity that can b e tolerated is
are flammable o r explosive. O p e r a t i n g r o o m s should
difficult to determine and will v a r y with the process
constantly guard against the possibility o f static dis-
and surrounding c o n d i t i o n s ; h o w e v e r , it is believed
charges w h i c h w o u l d immediately ignite the surround-
that w h e r e the relative humidity is maintained in the
ing atmosphere.
range o f 60 percent, static accumulations are not
Dry Cleaning. T h e m o v e m e n t o f garments, flam- likely to reach d a n g e r o u s p r o p o r t i o n s . W h e r e the
mable liquids causes an extended blanket o f h i g h l y p r o c e s s m a y b e affected b y humidity and the area
flammable v a p o r s . Static sparks are easily generated m a y even be air-conditioned for p r o c e s s c o n t r o l , then
b y this same m o v e m e n t o f the garment. o n e o f the f o l l o w i n g m e t h o d s o f static c o n t r o l m a y
be c o n s i d e r e d .
Offices — Business machines, particularly those
handling materials such as papers often accumulate
Static Collectors or Electrostatic Induction Ionization 7
29
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
be assumed charged to the m a x i m u m charge density S h o e testers are available for determining the resist-
of 2.6 x 1 0 c o u l o m b per square centimeter and the
-9
ance while being w o r n . Such testers are essentially
rate of production is equivalent to 2.6 x 10* W V 9
direct reading ohmeters with internal resistors to limit
c o u l o m b s per second. If the leakage to g r o u n d is to the short-circuit current to 0.5 milliampere.
carry this current with a potential difference w h i c h
is less than the minimum sparking potential of 350 W h e r e c o n d u c t i v e floors and shoes are required, the
volts, the resistance must be less than R = 3 5 0 / ( 2 . 6 resistance b e t w e e n the wearer and g r o u n d must not
x 1 0 " W V ) == 1.3 x 1 0 " / W V o h m s . If the width,
9
exceed o n e million o h m s , w h i c h is the total resistance
W , happens to be 10 centimeters and the velocity, of conductive shoes o n a person plus the resistance
V , 1000 centimeters per s e c o n d , the resistance should of the floor.
be less than 1.3 x 10 o h m s (13 m e g o h m s ) . "
7
30
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
— LIGHTNING PROTECTION GROUNDING —
charge. A l t h o u g h the discharge takes place at the 2. V a l u e and nature o f structure or content.
point where the potential difference exceeds the 3. Personnel hazards.
dielectric strength o f the insulation, which implies
4. Consequential loss, such as loss of production,
l o w resistance relative t o other paths, it is not un-
salaries o f w o r k e r s , d a m a g e suits and other in-
common for the current to f o l l o w a path of high direct losses.
resistance. T h i s m a y b e a tree, a m a s o n r y structure,
5. Effect o n insurance premiums.
o r a porcelain insulator. Obviously, damage due to
direct stroke can b e minimized b y p r o v i d i n g a direct T h e a b o v e factors are listed primarily to call atten-
tion to their importance. N o general conclusions can
path o f l o w resistance to earth.
be d r a w n as to the relative importance o f each o r
L i g h t n i n g can cause d a m a g e to structures b y direct to the necessity for o r the extent of lightning protec-
stroke and to equipment b y surges c o m i n g in o v e r tion for any given c o m b i n a t i o n of conditions. A s a
e x p o s e d p o w e r lines. Surges m a y be the result of matter o f interest, a m a p s h o w i n g the frequency of
direct strokes to the line at s o m e distance away, or thunderstorms for various areas o f the United States
they m a y b e electrostatically induced voltages. is s h o w n in F i g u r e 3.2. It should b e noted, h o w e v e r ,
that the s e v e n t y o f storms is m u c h greater in s o m e
THE NEED FOR PROTECTION local areas than in others and, therefore, the need
D a m a g e t o structures and equipment due to surge for protection is not necessarily in direct proportion
effect is a subject in itself and protection against this t o the frequency.
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
EQUIPMENT AND STRUCTURES T H A T on top of the structure should have an earth con-
SHOULD BE CONSIDERED FOR nection. P r o p e r l y m a d e c o n n e c t i o n s to earth are an
PROTECTION essential feature o f a lightning r o d system for p r o -
tection of buildings. ( S e e Chapter I V . ) It is m o r e
T h e nature o f buildings and their content are im- important to p r o v i d e ample distribution o f metallic
portant in deciding whether lightning protection is contacts in the earth than to p r o v i d e low-resistance
desirable. S o m e of the factors w h i c h should be c o n - connections. L o w - r e s i s t a n c e c o n n e c t i o n s are desirable,
sidered are as f o l l o w s : h o w e v e r , and should be p r o v i d e d w h e r e practicable.
Earth connections should be m a d e at uniform inter-
1. All-metal structures.
vals about the structure, avoiding as m u c h as possible
2. Metal-frame buildings with non-metallic facings. the g r o u p i n g of c o n n e c t i o n s on o n e side. E l e c t r o d e s
should be at least t w o feet a w a y from and should
3. Buildings m a d e entirely o f n o n - c o n d u c t i n g ma-
extend b e l o w building foundations. T h e y should make
terials such as w o o d , stone, brick and tile.
contact with the earth from the surface d o w n w a r d
4. Buildings of historical value. to avoid flashing at the surface.
5. Buildings containing combustible o r explosive
Interior metal parts of buildings o r structures
material.
should b e g r o u n d e d independently, and if they are
6. T a n k s and tank farms. within six feet of metallic r o o f s , walls o r c o n d u c t o r s
7. Transmission lines. running d o w n f r o m the terminals o n t o p o f the struc-
8. P o w e r plants, substations, and water pumping ture, they should be securely c o n n e c t e d thereto.
stations. T e r m i n a l s projecting a b o v e the structure should
be o f ample length to bring the t o p point at least
Metal buildings and structures offer a v e r y satis-
10 inches a b o v e the o b j e c t to be protected. In m a n y
factory path to earth and require little in the w a y
cases a greater height is desirable. Experiments have
of additional protection. Metal-frame buildings with
indicated that a vertical c o n d u c t o r , o r point, will
non-metallic facings require m o r e extensive measures.
divert to itself direct hits w h i c h m i g h t otherwise fall
Buildings m a d e entirely o f n o n - c o n d u c t i n g materials
within a c o n e shaped space, of w h i c h the apex is the
require complete lightning protective systems.
point and the base is a circle w h o s e radius is approxi-
In special cases buildings m a y have historical value mately equal to the height o f the point.
out of all proportion to the intrinsic value and m a y
justify extensive protection systems. P o w e r stations,
PROTECTION OF P O W E R STATIONS
substations, and water p u m p i n g stations p r o v i d i n g
AND SUBSTATIONS
extremely important functions to outside facilities
may demand protective measures far m o r e extensive Station protection against direct stroke should in-
than w o u l d normally be warranted b y the value o f the clude effective shielding of the station structure itself
structure. B y the same token structures containing and at least the first 2000 to 2500 feet of e x p o s e d lines
combustible or explosive material, liquids and gases adjacent to the station. T h i s shielding m a y take the
of a toxic nature o r otherwise harmful to personnel f o r m o f masts or extensions o f the steel structure t o
or property if allowed to escape f r o m their confining provide a p r o p e r c o n e o f protection to apparatus and
walls, m a y justify extensive protective systems. circuits within the station area. T h e s e extensions m a y
be arranged to also support the station end o f the
overhead g r o u n d wires carried o v e r the first 2000 feet
REQUIREMENTS FOR GOOD PROTECTION of line. T h e height of a single mast o r single ground
wire shielding is usually based o n a shielding angle
T h e fundamental theory of lightning protection o f
of 30 degrees. H o w e v e r , w h e n t w o o r m o r e masts
structures is t o p r o v i d e means b y w h i c h a discharge
or g r o u n d wires are used that part of the shielding
m a y enter or leave the earth without passing t h r o u g h
angle that lies between masts or g r o u n d wires is
paths of high resistance. Such a condition is usually
increased to 60 degrees. T h i s p r o v i d e s an unsym-
met b y g r o u n d e d metal o r m e t a l - c o v e r e d structures,
metrical c o n e o r w e d g e w h o s e base is equal to the
and is often met b y g r o u n d e d steel-frame structures.
height o n the outside areas and t o about twice the
Suitable protection is nearly always p r o v i d e d b y the
height in areas b e t w e e n masts o r g r o u n d wires. T h e
installation of lightning c o n d u c t o r s .
overhead g r o u n d wires o n the lines should have an
A lightning c o n d u c t o r system consists o f terminals effective l o w resistance g r o u n d at each structure.
projecting into the air a b o v e the u p p e r m o s t parts o f L i g h t n i n g protection o f p o w e r stations and substations
the structure, with interconnecting and g r o u n d i n g includes the protection o f station equipment b y means
conductors. Terminals should b e placed s o as t o of lightning arresters.
project a b o v e all points w h i c h are likely t o b e struck.
F o r lightning arresters a local g r o u n d i n g c o n n e c -
Conductors should present the least possible i m p e -
tion should b e m a d e b y driving electrodes into the
dance to earth. T h e r e should b e n o sharp bends o r
earth (see Chapter I V ) near the arresters, as s h o w n
loops. Each projecting terminal a b o v e the structure
in Figure 3.3. I n addition, the lightning arrester
should have at least t w o c o n n e c t i n g paths t o earth
g r o u n d i n g c o n d u c t o r should b e c o n n e c t e d into the
and m o r e if practicable.
c o m m o n station g r o u n d bus. F o r the average case
Each c o n d u c t o r running d o w n from the terminals an arbitrary upper limit o f 5 o h m s resistance to
32
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
Structures of this nature m a y be subject to c o m -
plete destruction from a small spark which w o u l d
be of n o c o n s e q u e n c e except for the presence of
combustible or e x p l o s i v e mixtures. Sheet metal of
3/16 inch thickness is adequate to withstand direct
strokes without puncturing. Steel tanks with steel
roofs and floating metal roofs are generally consid-
ered to be self-protecting. T a n k s with non-metallic
roofs are not self-protecting and should usually be
protected with air terminals, conducting masts or
overhead g r o u n d wires. In all cases, joints and piping
connections should be electrically continuous, and all
vapor or gas openings closed o r flameproof.
CHIMNEYS A N D STACKS
METHODS OF PROTECTION
3. R a d i o A m a t e u r s H a n d b o o k — A . F. Collins and
TANKS AND TANK FARMS
D . J. Duffin, T h o m a s Y . C r o w e l l C o m p a n y , N e w
Structures used for the storage of flammable liquids Y o r k , 1949.
and gases m a y require special attention. S o m e of the
4. Industrial Fires and E x p l o s i o n s from Electro-
features which should be considered in protecting
static Origin — R . Beach, Mechanical Engineer-
such structures are as follows:
ing, April 1953.
1. A l l metal, gastight structures.
5. Combustion, Flames and E x p l o s i o n s — B. Lewis
2. T a n k s of partial or total non-metallic material.
and G. V o n E l b e , A c a d e m i c Press, N e w Y o r k ,
3. V a p o r or gas openings. 1951.
33
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
6. Static Electricity — National Fire Protection 9. C o d e for P r o t e c t i o n A g a i n s t Lightning, H a n d -
Association Pamphlet, 60 Batterymarch Street, b o o k 46, U . S. D e p t . o f C o m m e r c e , National Bu-
Boston 10, Mass., 1947. reau o f Standards.
34
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
CHAPTER IV
CONNECTION TO EARTH
35
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
T A B L E 4.4
Hemisphere p _ P
Radius a R
2 ^
• One G r o u n d R o d
Length L, radius a
• • Two Ground R o d s
s > L; spacing s
«-^(^-0 ^0-8 !F-) + +
A Three-Point Star
Length of arm L, depth s/2 R
= dl ( LOG
<T-+ I O G
' 1
- 0 7 1
" A 2 0 9
T+ 0 2 3 8
IT" 0 0 5 4
£• •)
+ Foixr-Point Star
Length of arm L, depth s/2 ^ =
SjtE ( <^ +
LOG LOG
'
2
-T+ 2-912 - 1.071-*-+ 0.645^ - 0.146^...)
* Six-Point Star
Length of arm L, depth s/2
R =
ihh ( *1T
LOG + IOG
* T" + 6 8 5 1 _
3 1 2 8 - 1 - + 1.758-^- - 0.490-j;.. )
* Eight-Point Star
Length of arm L, depth s/2 * - ih. ( LOG
' 1 T + '<*• T-+ 1 0 9 8
" 5 5 1
T +
»-«^~ 1 1 7
T< )
O
R i n g o f Wire
Diameter o f ring D , diameter
of wire d, depth s/2
"Calculation of Resistance to Ground," by H . B. Dwight, Electrical Engineering, vol. 55, p. 1319, December, 1936.
due to capillary action will maintain, in m o s t cases, ductivity. T h e permissible current density for a given
the resistivity o f the earth at the electrode to a temperature rise is inversely proportional to the square
value close to that considered desirable. r o o t o f the soil resistivity. T h e effective resistance
of the earth c o n n e c t i o n w o u l d , therefore, depend o n
W h e r e the earth must dissipate high currents for the number o f such situations w h i c h c o u l d o c c u r in
short durations, n o appreciable a m o u n t o f heat can succession before stable conditions in the earth w e r e
be dissipated b y the normal p r o c e s s o f thermal c o n - re-established.
36
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
Ground currents of high magnitude and l o n g dura- cost. T h e y also require the least amount o f buried
tion are unusual, but could o c c u r as the result of material per o h m of g r o u n d c o n d u c t a n c e . Buried plates
ground faults w h i c h are not cleared promptly. If have not been used extensively in recent years
ground currents of this type are anticipated, the sys- because of the higher c o s t as c o m p a r e d to r o d s or
tem must c o v e r a relatively large area in o r d e r to strips. A l s o , w h e n used in small numbers, they are
keep the current density in the earth to a l o w value. 9
the least reliable type o f m a d e electrode. T h e counter-
poise is a f o r m of buried cable electrode used to
Soil Treatment
g r o u n d transmission line t o w e r s and structures.
Soil resistivity m a y b e reduced anywhere from 15
to 90 percent, depending upon the kind and texture W h e n multiple electrodes are used, spacings o f less
of the soil, b y chemical treatment. T h e r e are a n u m - than ten feet d o not p r o v i d e the m o s t economical use
ber o f chemicals suitable for this purpose, including of materials.
sodium chloride, m a g n e s i u m sulphate, c o p p e r sulphate, In selecting the number and size of grounding termin-
and calcium chloride. C o m m o n salt and magnesium als, their current discharge limitations must be recognized.
sulphate are m o s t c o m m o n l y used. If these are exceeded, the earth around the electrode may
Chemicals are generally applied b y placing them be exploded by steam generation, or may be dried out to
in the circular trench around the electrode in such the extent of becoming nonconductive.
a manner as to prevent direct contact with the elec-
D r i v e n R o d or P i p e
trode. W h i l e the effects o f treatment will not b e c o m e
apparent for a considerable period, they m a y be ac- D r i v e n electrodes m a y b e either r o d s o r pipes, al-
celerated b y saturating the area with water. A l s o , such though r o d s are generally m o r e economical. W h e r e
treatment is not permanent and must b e r e n e w e d soil conditions permit, a f e w deep r o d s are usually
periodically, depending on the nature of the chemical m o r e satisfactory than a multiplicity o f short r o d s
treatment and the characteristics o f the soil. since the v o l u m e o f soil affected increases directly
with the length o f e l e c t r o d e b e l o w the surface and
the soil resistivity generally decreases with depth
GROUND ELECTRODES
due to the increased moisture content. A n article
Existing Electrodes b y J. Z a b o r s z k y and J. W . R i t t e n h o u s e presents a
6
Basically all g r o u n d electrodes m a y b e divided into number o f design charts for determination o f o p t i m u m
t w o groups. T h e first c o m p r i s e s u n d e r g r o u n d metallic g r o u n d r o d dimensions and spacings for a given in-
piping systems, metal building f r a m e w o r k s , well cas- stallation.
ings, steel piling, and other u n d e r g r o u n d metal struc-
B u r i e d Strip, W i r e and Cable
tures installed for purposes other than g r o u n d i n g .
W h e r e b e d r o c k is near the surface, o r w h e r e sand
T h e s e c o n d c o m p r i s e s m a d e electrodes specifically
is encountered, the soil is apt t o b e v e r y dry and
designed for g r o u n d i n g purposes.
of high resistivity and it is necessary to have an
T h e National Electrical C o d e states that continuous earthing c o n n e c t i o n o f considerable extent. U n d e r
underground water o r gas piping systems generally such conditions, buried metal strips, wires o r cables
have a resistance to earth o f less than 3 o h m s , and offer the m o s t e c o n o m i c a l solution. Since the effec-
that metal building frames, local metallic u n d e r g r o u n d tiveness o f this type o f electrode for lightning dis-
piping systems, metal w e l l casings, and the like, have charges is a function o f its inductance, the use o f a
in general a resistance t o earth o f substantially less n u m b e r o f w e l l spaced shorter strips in parallel is
than 25 o h m s . F o r safety g r o u n d i n g and for small preferable to o n e o r m o r e l o n g strips. T h e depth at
distribution systems w h e r e the g r o u n d currents are w h i c h the strips are buried is n o t critical. Tests b y
of relatively l o w magnitude, such electrodes are usually the Bureau o f S t a n d a r d s s h o w that the decrease in
1
preferred because they are e c o n o m i c a l in first cost. resistance f r o m the m i n i m u m depth for cultivation
H o w e v e r , before reliance can b e placed on any elec- to the m a x i m u m practicable — about 18 to 36 inches
trodes of this g r o u p , it is essential that their resistance — is o n l y about 5 percent, based o n uniform soil
to earth be measured to insure that s o m e unforeseen resistivity. Similarily, the effect o f c o n d u c t o r size is
discontinuity has n o t seriously affected their suit- e x t r e m e l y small.
ability. A l s o , care should b e exercised t o insure that
all parts w h i c h m i g h t b e c o m e disconnected are effec- Grid Systems
tively b o n d e d together. Grid systems usually extend o v e r the entire station
yard and m a y extend s o m e distance b e y o n d the
Made Electrodes
b o u n d a r y fence. T h e y consist o f c o n d u c t o r s buried
M a d e electrodes m a y b e subdivided into driven a m i n i m u m o f 6 inches in the g r o u n d o r stone fill
electrodes, buried strips or cables, grids, buried plates, and f o r m i n g a n e t w o r k o f squares T h e size of
and counterpoises. T h e type selected will depend upon squares will v a r y with the v o l t a g e class o f the station
the type o f soil encountered and the available depth. but cable spacings o f 10 to 12 feet are c o m m o n l y
Driven electrodes are generally m o r e satisfactory and used. A l l cable c r o s s i n g s should b e securely b o n d e d
economical w h e r e b e d r o c k is ten feet o r m o r e b e l o w and the system c o n n e c t e d t o the n o r m a l g r o u n d sys-
the surface, while grids, buried strips o r cables are tem as well as t o all equipment and structural steel
preferred for lesser depths. Grids are frequently used w o r k . In r o c k g r o u n d w h e r e driven g r o u n d s are i m -
for substations o r generating stations to p r o v i d e equi- practical, it is s o m e t i m e s m o r e e c o n o m i c a l and desir-
potential areas t h r o u g h o u t the entire station w h e r e able t o use a g r i d s y s t e m in p l a c e o f buried strips,
hazards to life and p r o p e r t y w o u l d justify the higher in w h i c h case the cables are usually buried at a depth
37
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
of one to t w o feet. A n article b y E . T . B . Gross, B. V . at a point not far from the g r o u n d line, thus per-
Chitnis and L . J. S t r a t t o n gives the basic charac-
6
mitting r o d s to be driven to greater depths than
teristics and design elements for extensive grid s y s - w o u l d be possible b y hand sledging. If r o d s are to
tems. be driven o n a comparatively large scale, it is desir-
able to p r o v i d e p o w e r driving equipment. Electric,
Plates
pneumatic, and gasoline driven hammers are avail-
T h e preferred practice with plate electrodes is to able, the first t w o requiring sources of p o w e r . R e -
bury them on e d g e since a minimum o f excavation gardless of the type of driving tool used, precautions
is required and it is possible to obtain better c o n - should be taken to prevent "mushrooming*' o f the
tact with the soil w h e n backfilling. T h e r e appears t o head.
be little difference between the effective resistance
L o c a t i n g W a t e r M a i n ( N e w Construction)
of horizontal and vertical plates. F o r c o m m o n l y used
plates o f 10 to 20 square feet, the o p t i m u m burial Prior to n e w construction, analysis of the soil c o n -
depth is 5 t o 8 feet. dition and location o f the g r o u n d i n g point m a y per-
mit locating a water pipe nearby. T h i s w o u l d eliminate
a l o n g g r o u n d i n g line ( t o a distant water main) with
METHODS A N D TECHNIQUES OF
its inherently high inductance. T h e e c o n o m i c ad-
CONSTRUCTION
vantage o f such an arrangement should not be over-
Choice of Rods looked.
F o r ordinary soil condition, the 10 f o o t length o f A third m e t h o d that ultilities are presently experi-
rod has b e c o m e fairly well established as a m i n i m u m menting with involves the use o f a c o p p e r o r copper
standard length to meet the c o d e requirement o f a alloy c o n n e c t o r w h i c h is squeezed o n to both ground
minimum o f 8 buried feet. r o d and cable simultaneously b y a hydraulic press.
T h i s m e t h o d is e c o n o m i c a l , presents m o s t o f the ad-
vantages o f the thermit process, and eliminates m o s t
Methods of Driving Rods
of the o b j e c t i o n s t o that p r o c e s s .
Sledging requires a m i n i m u m o f driving equipment, O t h e r m e t h o d s o f joining, such as brazing or w e l d -
but m a y require considerable time per f o o t of r o d . ing, are satisfactory if p r o p e r l y d o n e .
A modification of the s l e d g i n g process, consisting
of a chuck and sliding hammer, permits the w o r k to
Joining to Underground Piping Systems
be carried on at a level convenient to the w o r k m a n
without a ladder o r auxiliary platform. A n additional Joining to pipe presents several p r o b l e m s . Clamp
advantage is that the b l o w is delivered to the r o d type fittings are relatively expensive, since they must
38
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
obviously a c c o m m o d a t e large pipe in addition to the MEASUREMENT OF RESISTANCE
relatively small c o n d u c t o r . W e l d i n g or brazing to the TO EARTH
pipe will cause localized- stress w h i c h m a y impair
the function of the pipe, particularly if it contains Need for M e a s u r e m e n t
fluid under high pressure. A typical w e l d e d c o n n e c - In any formula for the determination of the re-
tion to water pipe is s h o w n in Figure 4.1. sistance to earth there are m a n y indeterminate
factors, and t o o m u c h reliance should not be placed
u p o n the calculated results. T h e o n l y certain w a y
is to measure the resistance after the system has
been c o m p l e t e d . A desirable refinement w o u l d be to
measure the resistance of each electrode during in-
stallation.
Methods for Measuring
39
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
It is desirable, in measuring the resistance of the 2. A n Investigation o f Earthing Resistance, b y P. J.
completed system, to a l l o w s o m e time to elapse before H i g g i n s , I . E . E . Journal, V o l . 68, p. 736, Feb. 1930.
measurements are made, so that the earth around
the electrodes will be consolidated. 3. Lightning Arrester G r o u n d s , Parts I, I I , and I I I ,
b y H . M . T o w n e , General Electric R e v i e w , March,
A p r i l and M a y , 1932.
Periodic Testing
4. Calculation o f Resistance to Ground, b y H . B.
T e s t s should be m a d e periodically after the original D w i g h t , A I E E Transactions, V o l . 55, 1936, page
installation and test, so that it can be determined 1319.
whether the resistance is remaining constant or is 5. D e s i g n Charts for D e t e r m i n i n g O p t i m u m Ground
increasing. If later tests s h o w that the resistance R o d Dimensions, b y J. Z a b o r s z k y and J. W .
is increasing to an undesirable value, steps should Rittenhouse, A I E E Trans., Power A p p . & Systems,
be taken to reduce the resistance either b y additional V o l . 72, 1953, pgs. 810-17.
electrodes or b y increasing the moisture content or
by chemical treatment. 6. G r o u n d i n g Grids for H i g h - V o l t a g e Stations, by
E. T . B . G r o s s , B . V . Chitnis and L . J. Stratton,
A I E E Trans., Power A p p . & Systems, V o l . 72, 1953,
CATHODIC PROTECTION pgs. 799-810.
40
Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.