Sie sind auf Seite 1von 41

MNNMMNMMH

mm

Grounding of
Industrial Power Systems

Editorially Revised
r, 1 9 6 0

A Report of the
Industrial Power Systems Committee

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
IEEE
NUMBER
142
Oct. 1956

Grounding of
Industrial Power Systems

Editorially Revised
September, 1 9 6 0

A Report of the
Industrial Power Systems Committee

Published by
INSTITUTE OF ELECTRICAL AND ELECTRONICS ENGINEERS
345 East 47 Street, New York, N. Y. 10017

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
PREFACE

T h e subjects c o v e r e d b y this report are divided into four parts c o r r e s p o n d i n g to


the four chapters.

Chapter I c o v e r s the p r o b l e m s of system g r o u n d i n g ; that is, c o n n e c t i o n o f the


neutral, the corner-of-the-delta or mid-tap of one phase to ground. T h i s chapter dis-
cusses the pros and c o n s of grounded versus u n g r o u n d e d systems. If it is decided to
ground, information is given on h o w to g r o u n d the system, where the system should
be grounded and h o w to select equipment for the g r o u n d i n g of the neutral circuits.

Chapter I I deals with the p r o b l e m s of connecting the frames and enclosures of


electric apparatus such as m o t o r s , switchgear, transformers, buses, cables, conduits,
building frames, portable, equipment, etc., to a g r o u n d system. It also outlines the
fundamentals of m a k i n g the interconnection or g r o u n d c o n d u c t o r system between
electric equipments and the g r o u n d rods, water pipes, etc.

Chapter I I I deals with the p r o b l e m s of static — h o w it is generated, what p r o c -


esses m a y p r o d u c e static, h o w it is measured, and what should be d o n e to prevent
its generation o r to drain the static charges to earth to prevent sparking. It also c o v e r s
the methods of protecting structures against the effects of lightning. It is not a treatise
on the application of lightning arresters but, because the system for protecting struc-
tures against lightning consists entirely of c o n d u c t o r s to earth, it is considered within
the scope of this report to discuss the general aspects of the p r o b l e m .

Chapter I V deals with the p r o b l e m s of obtaining a l o w resistance c o n n e c t i o n to


the earth. T h e use of g r o u n d rods, connections to water pipes, etc., are discussed.

L o o k i n g at the p r o b l e m from an overall standpoint, the g r o u n d i n g of the system


would in m o s t cases be d o n e b y making a metallic connection direct o r through an
impedance between transformer or generator neutrals and the building g r o u n d i n g sys-
tem which is described in Chapter I I . T h e grounding system described in Chapter I I
in turn is connected to earth through the system of ground rods and water pipes
described in Chapter I V .

T h e protective systems discussed for static and lightning protection in Chapter I I I


w o u l d likewise be c o n n e c t e d to the g r o u n d rods and water pipe system as outlined
in Chapter I V .

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
CONTENTS

Page Page

Chapter I — S y s t e m Grounding 5 M e t h o d s o f T e s t i n g for Static 27


Definitions 5 H a z a r d s o f V a r i o u s T y p e s o f Industries— 28
Factors Influencing C h o i c e of G r o u n d e d M e t h o d s of Static Control—
or Ungrounded System 6 G r o u n d i n g and B o n d i n g 29
M e t h o d s o f System G r o u n d i n g 9 L i g h t n i n g P r o t e c t i o n Grounding 31
Selection and D e s i g n of System Nature of L i g h t n i n g 31
Grounding Arrangements 11
T h e N e e d for P r o t e c t i o n . 31
Bibliography 17
E q u i p m e n t and Structures T h a t Should
B e Considered for Protection 32
Chapter I I — E q u i p m e n t G r o u n d i n g 19
Requirements for G o o d Protection 32
General R e a s o n s for G r o u n d i n g 19
P r o t e c t i o n of P o w e r Stations
Grounding o f Structures 19
G r o u n d i n g of O u t d o o r Stations 20 and Substations 32

G r o u n d i n g o f L a r g e Generators and T a n k s and T a n k Farms 33


Motor Rooms 21 Chimneys and Stacks 33
G r o u n d i n g o f C o n d u c t o r Enclosures 22 M e t h o d s of P r o t e c t i o n - 33
G r o u n d i n g o f Miscellaneous L a r g e M o t o r s 24 Bibliography 33
Portable Electric Equipment 24
Bibliography - - 25 Chapter I V — C o n n e c t i o n t o E a r t h 35
Resistance to Earth 35
Chapter I I I — S t a t i c and L i g h t n i n g P r o t e c t i o n Ground Electrodes 37
Grounding 26 M e t h o d s and T e c h n i q u e s o f Construction 38
Static G r o u n d i n g 26 Measurement of Resistance to Earth 39
P u r p o s e o f Static G r o u n d i n g 26 Cathodic P r o t e c t i o n 40
Fundamental Causes o f Static 26 Bibliography 40

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
ACKNOWLEDGMENT

T h e Institute wishes to a c k n o w l e d g e its indebtedness to those w h o have s o freely


given o f their time and k n o w l e d g e to prepare its m a n y publications.

T h i s publication was prepared b y the Industrial Grounding Subcommittee of the


AIEE C o m m i t t e e o n Industrial P o w e r Systems. The members of the Subcommittee
were:

D. L . BEEMAN, Chairman F . R. LONGLEY


General Electric Co. Western Massachusetts Elec. C o .
Schenectady, N . Y . Springfield, Mass.

D. M . ALLISON C. C. SAUNDERS
Westinghouse Elec. Corp. Chairman, Working Group, Chapter III
Tulsa, Oklahoma E. I. duPont de Nemours & Co.
Wilmington, Delaware
H . H . ANGEL
Chairman, Working Group, Chapter 11 J. M . SCHMIDT
Bethlehem Steel C o . General Electric Co.
Bethlehem, Pa. Schenectady. N . Y .

J. E. ARBERRY H. E. SPRINGER
Pittsburgh Plate Glass Co. Rayonier, Inc.
Pittsburgh, Pa. Port Angeles, Wash.

K . M . BAUSCH H. M . STEWART
Bechtel Corporation Humble Oil & Refining Co.
San Francisco, Calif. Baytown, Texas

A . J. BISSON T . O . S WE ATT
Consolidated Edison Co. of N . Y . Wearn, Vreeland, Carlson & Sweatt, In<.
New York, N. Y . New York, N . Y .

L . J. CARPENTER H. B. T H A C K E R
General Electric Co. Chairman, Working Group, Chapter I
Schenectady, N . Y . Westinghouse Electric Corp.
East Pittsburgh, Pa.
M . A . LELAND
Chairman, Working Group, Chapter IV B. F . T H O M A S , JR.
Burndy Engineering Co., Inc. N . A . Lougee & Co.
Norwalk, Conn. New Y o r k , N . Y .

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
CHAPTER I
SYSTEM GROUNDING

T h e question o f whether o r not to g r o u n d a p o w e r Figures 1.1 ( b ) and 1.1 ( c ) s h o w t w o points at


system is o n e w h i c h mu9t be faced s o m e t i m e b y m o s t which a system may be grounded; and the correspond-
engineers charged with planning industrial distribu- ing v o l t a g e relationships.
tion. A decision in favor of a g r o u n d e d system leads
T h e term "solidly g r o u n d e d " , though c o m m o n l y
then to the question of h o w to g r o u n d .
used, is s o m e w h a t confusing since a transformer m a y
It is the intent of this chapter to assist the planning have its neutral " s o l i d l y " c o n n e c t e d to g r o u n d and
engineer to answer these and other m o r e detailed yet be s o small in capacity as to furnish o n l y a very
questions o n the subject, b y presenting basic reasons high impedance g r o u n d to the system to which it
for grounding o r not g r o u n d i n g and b y reviewing is c o n n e c t e d . In o r d e r to m o r e positively and logically
general practices and m e t h o d s of system grounding. define g r o u n d i n g as to degree, the term "effectively
g r o u n d e d " has c o m e into use. T h e term solidly
Practices of the g r o u n d i n g of s y n c h r o n o u s genera- g r o u n d e d will therefore be used in this report only
tors, and for the g r o u n d i n g of transmission s y s t e m s ,
1 2

with reference to a solid metallic connection from


particularly those operated at 23 kilovolts and higher, system neutral to g r o u n d , i.e. with n o impedance
have been summarized in other g u i d e s . T h e practices
3

intentionally added in the g r o u n d i n g circuit.


set forth in those guides are applicable to industrial
p o w e r systems in various degrees, depending o n the Section 32-1.05 of A I E E Standard N o . 32, M a y
type and extent o f the industrial system under c o n - 1947, defines effective g r o u n d i n g as f o l l o w s : " A sys-
4

sideration, and o n the character of service required tem o r portion o f a s y s t e m m a y be said t o b e effec-
at the points of p o w e r consumption. tively g r o u n d e d w h e n for all points o n the system or
specified portion thereof the ratio o f zero-sequence
W h e r e an industrial p o w e r system consists of p o w e r reactance to positive-sequence reactance is n o t greater
generating equipment, transmission circuits, and dis- than three and the ratio of zero-sequence resistance
tribution circuits, the reasons for g r o u n d i n g these to positive-sequence reactance is not greater than
c o m p o n e n t s are often the same as for g r o u n d i n g one for any condition of operation and for any amount
similar c o m p o n e n t s of public utility systems and other of c o n n e c t e d generator capacity."
large p o w e r systems, and the m e t h o d s o f g r o u n d i n g
SYSTEM NEUTRAL
would generally be similar under like conditions o f
service. But in s o m e cases the reasons for g r o u n d i n g
and the m e t h o d s o f g r o u n d i n g certain c o m p o n e n t s o f
an industrial p o w e r system m a y differ a c c o r d i n g to
the requirements of manufacturing o r p r o c e s s opera-
tions.
DEFINITIONS

U n g r o u n d e d system means a system without an ( o ) UNGROUNDED SYSTEM


intentional connection t o g r o u n d e x c e p t through p o -
tential indicating o r measuring devices. T h e neutral
of an u n g r o u n d e d system under reasonably balanced
load conditions will usually be close t o g r o u n d poten-
tial, being held there b y the balanced electrostatic
capacitance b e t w e e n each phase c o n d u c t o r and ground.

Figure 1.1 ( a ) s h o w s an u n g r o u n d e d s y s t e m with (b) GROUNDED - WYE SYSTEM

voltage relations for balanced phase-to-ground ca-


pacitances.

A g r o u n d e d system is o n e in w h i c h at least o n e
c o n d u c t o r o r point (usually the neutral point of
transformer o r generator w i n d i n g s ) is intentionally
grounded, either solidly o r through a current-limiting
device. V a r i o u s degrees o f g r o u n d i n g are used from
"solid" o r "effective" to the high-reactance g r o u n d i n g
obtained from a small g r o u n d i n g transformer used <c) G R O U N D E D - D E L T A S Y S T E M
only to secure e n o u g h g r o u n d current for relaying.
Figure 1.1
Diagram showing voltages to ground under steady-state conditions
1
Numbers refer to numbered references in bibliography at end of for (a) ungrounded system, (b) grounded-wye system,
this chapter. (c) grounded delta system.

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
FACTORS INFLUENCING CHOICE OF feeder has been r e m o v e d f r o m the system. Should
GROUNDED OR UNGROUNDED SYSTEM it happen that the same phase of t w o different feeders
b e c o m e faulted to g r o u n d at the same time, the faulted
Service Continuity
feeders cannot be located b y r e m o v i n g them from
F o r many years m o s t industrial plant distribution the system o n e at a time. It m a y be necessary to
systems have been operated u n g r o u n d e d at one or r e m o v e all feeders and restore them to service one
m o r e voltage levels. In m o s t cases this has been d o n e at a time c h e c k i n g the g r o u n d detector as each
with the thought o f gaining an additional degree of feeder is restored.
service continuity. T h e fact that any contact o c c u r r i n g
T h e location of a g r o u n d e d feeder o n an un-
between one phase o f the system and g r o u n d is un-
g r o u n d e d s y s t e m m a y be facilitated b y use o f various
likely to cause an immediate outage to any load, m a y
types o f locating apparatus. F o r example, an inter-
6

represent an advantage in m a n y plants, varying in


rupted direct v o l t a g e o r superimposed audio signals
its importance a c c o r d i n g to the type of plant.
m a y b e applied t o the feeder bus and the tracing
Grounded systems, in m o s t cases, are set up s o that current detected in the g r o u n d e d feeders. S o m e opera-
circuit protective devices will r e m o v e a faulty circuit tors have reported success with locating apparatus
from the system regardless of the type of fault. A used without de-energizing system feeders. T h i s , of
phase-to-ground fault results in the immediate isola- course, has the advantage of permitting location of
tion of the faulted circuit with the attendant outage g r o u n d s without waiting for light load periods o n the
of the loads o n that circuit. H o w e v e r , experience has system.
s h o w n , in a number of systems, that greater service
6

A n accidental g r o u n d o n a g r o u n d e d system is both


continuity is obtained with g r o u n d e d neutral than
indicated and at least partially located b y an inter-
with ungrounded neutral systems.
ruption of the accidentally g r o u n d e d circuit o r piece
of equipment.
Multiple Faults t o G r o u n d
Safety
W h i l e a g r o u n d fault o n o n e phase of an un-
M a n y o f the hazards to personnel and property
grounded system generally d o e s not cause a service
existing in s o m e industrial electric systems are the
interruption, the o c c u r r e n c e of a s e c o n d g r o u n d fault
result o f p o o r o r non-existent g r o u n d i n g o f electric
on a different phase before the first fault is cleared
equipment and metallic structures. W h i l e the subject
does result in an outage. If both faults are o n the
of E q u i p m e n t G r o u n d i n g is treated in Chapter I I , it
same feeder, that feeder will be d r o p p e d . If the s e c o n d
is important to n o t e here that regardless o f whether
fault is o n a different feeder, both feeders will be
o r not the s y s t e m is g r o u n d e d , safety considerations
dropped.
require t h o r o u g h g r o u n d i n g o f equipment and struc-
T h e longer a g r o u n d is a l l o w e d to remain o n an tures.
ungrounded system, the greater is the likelihood of
Effectively g r o u n d i n g a l o w - v o l t a g e (600 volts or
a s e c o n d g r o u n d o c c u r r i n g o n another phase resulting
less) distribution s y s t e m m a y result in less likelihood
in an outage. T h e advantage an u n g r o u n d e d system,
of accidents t o personnel than leaving the system
in not immediately d r o p p i n g load u p o n the o c c u r r e n c e
s u p p o s e d l y u n g r o u n d e d . If all circuits w e r e treated
of a ground fault, m a y be largely d e s t r o y e d b y the
with the same caution there m i g h t be slightly less
practice of ignoring a g r o u n d until a s e c o n d o n e
hazard o f s h o c k o n the u n g r o u n d e d system in s o m e
occurs and repairs are required to restore service.
cases. H o w e v e r , the impression that o n e phase of
W i t h an ungrounded system it is e x t r e m e l y important
an u n g r o u n d e d system can be safely contacted m a y
that an organized maintenance p r o g r a m be p r o v i d e d
lead t o carelessness in handling the circuit when
such that g r o u n d s are located and r e m o v e d as s o o n
energized. T h e s u b c o n s c i o u s k n o w l e d g e that a circuit
as possible after their detection. A n adequate detec-
is g r o u n d e d generally will result in greater care on
tion system, possibly in c o n j u n c t i o n with an audible
the part o f the w o r k m a n .
alarm, is considered essential for best operation o f
the ungrounded system. D u r i n g the period a g r o u n d fault remains o n one
phase o f an u n g r o u n d e d system, personnel contacting
Experience s h o w s that multiple g r o u n d faults are
o n e o f the other phases and g r o u n d are subjected to
rarely, if ever, experienced o n grounded-neutral
full line-to-line v o l t a g e instead o f the line-to-neutral
systems.
v o l t a g e that w o u l d b e experienced at any time on
Location of Faults the g r o u n d e d system.

O n an u n g r o u n d e d system a g r o u n d fault d o e s not O t h e r hazards o f s h o c k and fire m a y result from


open the circuit. S o m e means o f detecting the presence inadequate g r o u n d i n g o f equipment in either g r o u n d e d
of a g r o u n d o n the system should be installed. L a m p s o r u n g r o u n d e d s y s t e m s . A c c i d e n t a l g r o u n d s are in-
connected to indicate the potential from each phase evitable. T h e current path t o g r o u n d for a w i n d i n g -
to ground will s h o w the presence o f a g r o u n d fault to-frame insulation b r e a k d o w n in a m o t o r m a y in-
and which phase is i n v o l v e d , but will not s h o w o n clude g r e a s y shavings o r other materials that w o u l d
which feeder the fault has o c c u r r e d . L o c a t i n g a be ignited b y sparks o r l o c a l i z e d heating. Such a
ground fault o n o n e o f the several feeders m a y re- high-impedance g r o u n d circuit m a y n o t permit enough
quire the removal f r o m service o f o n e feeder at a current flow to operate protective devices, with the
time until the g r o u n d d e t e c t o r indicates the faulted result that a potential fire and safety hazard m a y

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
exist for s o m e time. T h e r e is hazard of s h o c k to current z e r o at w h i c h time the stored energy in the
personnel from such a condition should they bridge inductance o f the circuit is z e r o . T h e overvoltages
all o r part of the high impedance g r o u n d path, for thus d e v e l o p e d result f r o m transient oscillation in the
example, contacting the frame of the faulty machine. circuit capacitance and inductance, there being stored
This hazard is particularly bad because there are m o r e e n e r g y in the circuit capacitance at the time o f cur-
possible victims than in the case of persons familiar rent interruption. M o r e serious overvoltages can be
with electric systems w o r k i n g on a circuit. p r o d u c e d b y devices w h i c h interrupt b y forcing cur-
rent z e r o . Such devices as current-limiting fuses
must b e carefully applied because of this o v e r v o l t a g e
Abnormal Voltage Hazards
problem.
T h e possible o v e r v o l t a g e s on the u n g r o u n d e d sys-
tem m a y cause m o r e frequent failure of equipment Neutral g r o u n d i n g is not likely to reduce the total
than if the system w e r e g r o u n d e d . In s o m e cases magnitude o f o v e r v o l t a g e p r o d u c e d b y lightning or
these o v e r v o l t a g e s have caused failures on m o r e than switching surges. It can, h o w e v e r , distribute the volt-
o n e unit o f equipment at the same time. T h e s e m u l - age b e t w e e n phases, reducing the possibility of ex-
tiple failures are not necessarily confined to o n e cessive v o l t a g e stress o n the phase-to-ground insula-
feeder but m a y involve equipment on several different tion o f a particular phase.
feeders.
Static (See Chapter III)
A fault o n o n e phase of an u n g r o u n d e d system
places a sustained o v e r v o l t a g e on the insulation of Build-up o f o v e r v o l t a g e on p o w e r system c o n d u c -
ungrounded phases in a three-phase system. T h i s tors due t o static c h a r g e is not usually a p r o b l e m
overvoltage is 1.73 times the voltage n o r m a l l y on in m o d e r n plants with metal-enclosed circuits and
the insulation. T h i s o r other sustained o v e r v o l t a g e s equipment. Static c h a r g e o n m o v i n g belts can build
or the transient o v e r v o l t a g e s on the u n g r o u n d e d sys- up voltages w h i c h can be transmitted to the p o w e r
tem m a y not immediately cause failure o f insulation, system unless m o t o r frames are p r o p e r l y grounded.
but tend to reduce the life of the insulation. O v e r h e a d o p e n - w i r e lines m a y be subject to static
o v e r v o l t a g e s resulting f r o m certain atmospheric c o n -
T h e reduced o v e r v o l t a g e s experienced o n the ditions. A system g r o u n d connection, even of rela-
g r o u n d e d system are less likely to d a m a g e equipment tively high resistance, can effectively prevent static
o r insulation. v o l t a g e build-up.

P o w e r System Overvoltages 7

Contact with Higher-Voltage System


S o m e o f the m o r e c o m m o n sources of o v e r v o l t a g e Contact with a higher-voltage system m a y be caused
on a p o w e r system are: ( a ) lightning, ( b ) switching b y a b r o k e n high-voltage c o n d u c t o r falling o n a
surges, ( c ) static, ( d ) contact with higher-voltage l o w e r - v o l t a g e c o n d u c t o r w h e r e b o t h lines cross or
system, ( e ) Hne-to-ground faults, ( f ) resonant c o n - are carried o n the s a m e poles, o r b y b r e a k d o w n b e -
ditions, ( g ) restriking g r o u n d faults. tween the high- and l o w - v o l t a g e w i n d i n g s of a trans-
former. If the l o w - v o l t a g e system is ungrounded the
Lightning 8
( S e e Chapter I I I ) high v o l t a g e will remain o n the l o w - v o l t a g e system
causing b r e a k d o w n o f insulation possibly at several
M o s t industrial systems are effectively shielded points. A n effectively-grounded l o w - v o l t a g e system,
against direct lightning strokes. M a n y circuits are though resulting in high values o f fault current for
either underground in ducts o r are within g r o u n d e d this condition, will h o l d the system neutral close to
metal conduits o r raceways. E v e n open-wire circuits g r o u n d potential and greatly reduce the overvoltages
are often shielded b y adjacent metallic structures t o g r o u n d o n the l o w - v o l t a g e system.
and buildings. L i g h t n i n g arresters applied at the in-
c o m i n g service limit the surge voltages within the
L i n e - t o - G r o u n d Faults
plant resulting from strokes to the e x p o s e d service
lines. O t h e r arrester applications m a y be necessary A c o m m o n s o u r c e o f sustained o v e r v o l t a g e on an
within the plant t o protect l o w impulse strength d e - u n g r o u n d e d s y s t e m is caused b y o n e phase of a
vices such as rotating machines. W h e r e a plant is three-phase s y s t e m b e c o m i n g g r o u n d e d . In this case
supplied from a substation stepping d o w n from s o m e the insulation o f the other phases is subjected to
higher voltage, lightning arresters may be required 73 percent a b o v e n o r m a l voltage. A grounded-neutral
on the l o w side of the transformer to protect plant system would not have this overvoltage. The cumulative
equipment from surges passed b y the high-side arrest- effect of higher than normal voltage stresses may some-
ers and reflected through the transformer. what reduce insulation life.
Resonant Conditions
S w i t c h i n g Surges
U n g r o u n d e d systems m a y be subjected to resonant
N o r m a l switching operations in the system can o v e r v o l t a g e s . W i t h the high phase-to-ground capaci-
cause o v e r v o l t a g e s . T h e s e are generally not m o r e tance of larger systems there m a y be a condition o f
than three times normal v o l t a g e and of short dura- approximate circuit resonance during a line-to-ground
tion. O v e r c u r r e n t devices such as circuit breakers fault through an inductance such as a faulty coil
or fuses, in general, interrupt a circuit at a normal in a m o t o r starter. T h e voltage to ground of the

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
unfaulted phases will then b e considerably in excess ing these systems. The cost of grounding resistor or
of line-to-line voltage. A n o v e r v o l t a g e due to resonant impedance, however, does represent an extra cost of
or near resonant conditions can be encountered where the grounded neutral system.
tuned inductive-capacitive circuits are used such as for op- Grounding existing systems m a y be v e r y expensive
eration of welders. For example, if the welder is equip- because it m a y be necessary to add g r o u n d i n g trans-
ped with a series capacitor for power factor improvement, formers and their protective equipment, grounding
the voltage across the capacitor and across the trans- impedance if required, and a third current transformer
former winding are each many times the supply line-to- in all circuits to obtain ground-fault relaying o n all
line voltage. A ground fault on the connecting lead be- three phases.
tween the capacitor and the welder transformer imposes T h e r e should b e three overcurrent elements in the
this high voltage on the line-to-ground insulation of protective devices in a g r o u n d e d neutral system. This
every piece of electric equipment connected to these m a y require m o r e expensive m o t o r c o n t r o l devices in
lines. A grounded neutral system would prevent this over- rare cases, but the present practice is t o provide three
voltage by holding the phases to their approximate normal overcurrent elements in all l o w - v o l t a g e air circuit
voltage to ground. breakers. Usually it is not necessary to carry the
neutral wire a l o n g with the three-phase circuits un-
less the circuits supply single-phase loads connected
Restriking G r o u n d Faults from line-to-neutral as in 208Y/120-volt circuits
Field experience and theoretical studies have s h o w n supplying 120-volt lighting load. Therefore, there
is n o additional circuit c o s t t o charge against the
that arcing, restriking o r vibrating g r o u n d faults on
grounded-neutral arrangement. T h e additional costs
ungrounded systems can, under certain conditions,
of grounded-neutral transformers and controls with
produce surge voltages as high as six times normal
three overcurrent elements m a y s e e m significant when
line-to-line voltage. T h e conditions necessary for p r o -
c o m p a r e d with the cost of the devices, but w h e n addi-
ducing these overvoltages require that the dielectric
tional costs are considered as a fraction of the total
strength of the arc path build up at a higher rate
system cost they are generally v e r y small.
after each extinction of the arc than it did after the
preceding extinction or be the result of an intermittent
contact between line and ground. This phenomenon is un- T r e n d s in A p p l i c a t i o n o f S y s t e m G r o u n d i n g
likely to take place in open air between stationary con-
T h e basic reasons for system g r o u n d i n g are three-
tacts because such an arc path is not likely to develop
fold: First, to limit the difference o f electric potential
sufficient dielectric recovery strength. It may occur in
between all uninsulated c o n d u c t i n g o b j e c t s in a local
confined arcs where the pressure m a y increase after
area; second, to p r o v i d e for isolation o f faulty equip-
each conduction period. Neutral g r o u n d i n g is effec- ment and circuits w h e n a fault o c c u r s ; and third, to
tive in reducing transient voltage build-up from such limit overvoltages appearing on the system under
intermittent g r o u n d faults b y reducing neutral dis- various conditions.
placement from g r o u n d potential and reducing de-
structive effectiveness o f any high-frequency v o l t a g e T h e basic reasons for the selection o f ungrounded-
neutral systems is that such systems, particularly at
oscillations following each arc initiation or restrike.
480 and 2400 v o l t s , are slightly less expensive and
m a n y operators feel that the u n g r o u n d e d neutral sys-
Cost tem possesses a service continuity advantage because
the first g r o u n d fault m a y n o t cause a trip-out o f a
Grounded neutral systems may cost at most only a few circuit o r m o t o r . It will be noted that there is today
percent more than ungrounded neutral systems, depend- a divided opinion a m o n g operators as t o the relative
ing upon system voltage and whether it is an existing service continuity of g r o u n d e d and ungrounded-
or new system that is to be grounded. Equipment for neutral systems. M a n y operators feel that a grounded
208Y/120-volt systems almost universally provides for system gives them better overall service continuity
system neutral grounding and, therefore, does not in- than they have obtained f r o m an u n g r o u n d e d system.
volve any extra cost. Wye-connected unit substations
T h e r e has been an increasing trend t o w a r d g r o u n d -
for grounding 480-volt systems are standard but cost
ing industrial systems in o r d e r to o v e r c o m e s o m e of
from nothing more to about six percent more than delta-
the disadvantages attributed to u n g r o u n d e d operation.
connected substations. 2400-volt wye-connected trans-
In recent years a substantial percentage of n e w in-
formers for system neutral grounding of these systems dustrial substation transformers have been purchased
can be obtained at a slight cost premium over 2400-volt with w y e - c o n n e c t e d l o w - v o l t a g e windings suitable for
delta transformers. In addition there is the c o s t of neutral grounding.
the resistor or other g r o u n d i n g impedance if used.
In new installations these transformers offer the ad-
For system voltage of 4.16 and 13.8 kilovolts, wye- vantage that they can be operated ungrounded if desired
connected transformers are standard and, therefore, but possess an available neutral for easy addition of a
there is no price penalty, transformer-wise, for ground- grounding circuit at a later date.

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
METHODS OF SYSTEM GROUNDING degree of g r o u n d i n g p r o v i d e d in the system. A g o o d
guide in answering this question is the magnitude of
G r o u n d i n g the S y s t e m Neutral ground-fault current as c o m p a r e d to the system three-
phase fault current. T h e higher the ground-fault cur-
M o s t g r o u n d e d systems e m p l o y s o m e m e t h o d o f rent in relation to the three-phase fault current, the
grounding the system neutral at o n e o r m o r e points. greater the d e g r e e o f g r o u n d i n g in the system. In
T h e s e m e t h o d s are referred to as ( 1 ) solid g r o u n d - terms of resistance and reactance, "effective g r o u n d -
ing, ( 2 ) resistance grounding, ( 3 ) reactance g r o u n d - ing" of a system is defined o n page 5.
ing, and ( 4 ) ground-fault neutralizer g r o u n d i n g . E a c h
In m o s t generators, solid g r o u n d i n g , i.e., without
method, as named, refers t o the nature o f the external
external i m p e d a n c e , m a y permit the m a x i m u m ground-
circuit from system neutral to g r o u n d rather than t o
fault current f r o m the generator t o exceed the m a x i -
the degree o f g r o u n d i n g . In each case the impedance
m u m three-phase fault current w h i c h the generator
of the generator o r transformer, w h o s e neutral is
can deliver, and for w h i c h its windings are braced.
grounded, is in series with the external circuit. T h u s ,
Consequently, in cases w h e r e effective g r o u n d i n g of
a s o l i d l y - g r o u n d e d generator o r transformer m a y o r
a system is indicated, m o s t generators should b e
may not furnish "effective g r o u n d i n g " to the system,
g r o u n d e d through a reactor having a l o w o h m i c value,
depending o n its impedance.
w h i c h will limit generator phase-current during single
line-to-ground faults to a value n o greater than three-
CIRCUIT EQUIVALANT
phase fault current. In the case o f three-phase, four-
wire systems, limitation o f ground-fault currents to
100 percent o f the three-phase fault current is usually
I. UNGROUNDED practical w i t h o u t interfering with normal four-wire
operation.

Lightning arresters for grounded-neutral service (rated


near but not less than 80 percent of line-to-line voltage)
2 SOLIOLV GROUNDED require that the system be effectively grounded. This
will carry with it a line-to-ground short-circuit current
of at least 60 percent of the three-phase short-circuit
value.

3 RESISTANCE GROUNDED

Resistance Grounding

In resistance g r o u n d i n g , the neutral is connected


to g r o u n d through o n e o r m o r e resistors. In this
4. REACTANCE GROUNDED
m e t h o d , with resistor o h m i c values normally used
and e x c e p t i n g for transient o v e r v o l t a g e s , the line-to-
g r o u n d v o l t a g e s w h i c h exist during a line-to-ground
fault are nearly the same as for an u n g r o u n d e d system.
5. GROUND FAULT
NEUTRALIZER A system p r o p e r l y g r o u n d e d b y resistance is not
subject to destructive transient o v e r v o l t a g e s . F o r re-
- REACTANCE OF GENERATOR OR TRANSFORMER USED FOR GROUNDING sistance-grounded systems at 15 kilovolts and b e l o w ,
X - R E A C T A N C E OF GROUNDING REACTOR
such o v e r v o l t a g e s will n o t ordinarily be of a serious
N

R - R E S I S T A N C E OF GROUNDING RESISTOR
N

nature, unless the resistance is so high as to limit


Figure 1.2
System neutral circuit and equivalent diagrams for ungrounded the ground-fault current t o a small fraction of one
and various types of grounded neutral systems. percent o f the s y s t e m three-phase fault current (less
than the system c h a r g i n g c u r r e n t ) . T h i s m u c h ground
current (usually well b e l o w 50 amperes) is far less
than is n o r m a l l y used with resistance grounding.
Solid G r o u n d i n g
S y s t e m s g r o u n d e d through resistors generally re-
Solid g r o u n d i n g refers t o the c o n n e c t i o n o f the
quire lighting arresters suitable for use o n un-
neutral of a generator, p o w e r transformer o r g r o u n d -
grounded-neutral circuits, i.e., with a voltage rating at
ing transformer directly t o the station g r o u n d o r
least equal to line-to-line voltage.
to the earth. Because o f the reactance o f the
grounded generator o r transformer in series with
T h e reasons for limiting the current b y resistance
the neutral circuit, a solid g r o u n d c o n n e c t i o n cannot
g r o u n d i n g are as f o l l o w s :
be considered as p r o v i d i n g a z e r o i m p e d a n c e neutral
circuit. (1) T o r e d u c e burning and melting effects in
faulted electric equipment such as switchgear,
If the reactance o f the generator o r transformer is transformers, cables, and rotating machines.
too great, the o b j e c t i v e s s o u g h t in g r o u n d i n g , prin-
cipally f r e e d o m f r o m transient o v e r v o l t a g e s , m a y n o t (2) T o reduce mechanical stresses in circuits and
be achieved. T h u s , it is necessary to determine the apparatus carrying fault currents.

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
( 3 ) T o reduce electric s h o c k hazards to personnel, mission lines. T h i s m e t h o d is a s e c o n d choice t o re-
caused by stray ground-fault currents in the sistor g r o u n d i n g , w h i c h p r o v i d e s g r o u n d relaying to
ground return path. disconnect the faulted circuit. It should b e noted that
failures in solid insulations, such as paper, varnished
( 4 ) T o reduce the m o m e n t a r y line v o l t a g e dip c a m b r i c and rubber, are not self-healing as insulator
occasioned b y o c c u r r e n c e and clearing of a flashovers are, and are not extinguished b y the use of
g r o u n d fault. the ground-fault neutralizer.

In s o m e cases, w h e r e it has not been d e e m e d de-


Reactance Grounding sirable b y the plant operators to trip a circuit o n the
T h e term "reactance g r o u n d i n g " describes the case o c c u r r e n c e of a g r o u n d fault, special arrangements
in which a reactor is c o n n e c t e d b e t w e e n the system have been used to limit the d a m a g e due to the flow
neutral and ground. Since the ground-fault current of charging current, and yet be able to easily locate
which m a y flow in a reactance-grounded system is a the faulty feeder. O n e s c h e m e is to use a ground-fault
function o f the neutral reactance, the magnitude of neutralizer in the neutral to limit the ground-fault cur-
ground-fault current is often used as a criterion for rent and to reduce switching surges to safe values. A
describing the degree o f g r o u n d i n g . In a reactance- resistor is arranged to b e c o n n e c t e d in parallel with
g r o u n d e d system, the available ground-fault current the neutralizer w h e n it is desired to pass enough
should be at least 25 percent of the three-phase fault ground-fault current to cause relays to give a signal
current t o prevent serious transient o v e r v o l t a g e s . o r trip the breaker o f the faulty feeder. Because of
This is considerably higher than the m i n i m u m fault the current to be switched, a p o w e r circuit breaker
current desirable in a resistance-grounded system and, should b e used for switching the resistor. T h e resistor
therefore, reactance g r o u n d i n g is usually not c o n - and relay are selected as if the resistor o n l y were
sidered an alternative of resistance g r o u n d i n g . used. Such a s c h e m e is expensive and is o n l y used
in v e r y special cases.
In practice, reactance g r o u n d i n g is generally used
only in the case cited under " S o l i d G r o u n d i n g " , in Care should be taken to keep the ground-fault neu-
which a generator neutral is t o b e c o n n e c t e d directly tralizer tuned to the system capacitance to minimize the
to ground. In this event, it m a y b e necessary t o add development of transient overvoltages. Thus, when sec-
a l o w value reactor to limit the available ground-fault tions of the system are switched on or off, it may be
current through the generator t o a value n o greater necessary to readjust the neutral reactance by changing
than the three-phase fault current contributed b y the neutralizer tap.
the generator.

G r o u n d i n g at P o i n t s O t h e r T h a n S y s t e m Neutral
Ground-Fault Neutralizer 9

In s o m e cases l o w - v o l t a g e systems, (600 volts and


A ground-fault neutralizer is a reactor c o n n e c t e d
b e l o w ) , are g r o u n d e d at s o m e point other than the
between the neutral o f a s y s t e m and g r o u n d , and
system neutral. T h i s has been d o n e to obtain a
having a specially selected, relatively high value of
g r o u n d e d system at a m i n i m u m expense w h e r e exist-
reactance.
ing delta transformer connections do not provide
A line-to-ground fault causes line-to-neutral v o l t a g e access t o the system neutral.
to b e impressed across the neutralizer, w h i c h passes
an inductive current. T h i s current is 180 degrees out
of phase and is a p p r o x i m a t e l y equal in magnitude Corner-of-the-Delta G r o u n d i n g
( w h e n the neutralizer is tuned to the s y s t e m ) to the
In l o w - v o l t a g e systems w h i c h , in the past, have
resultant o f the system c h a r g i n g current of the t w o
nearly all been supplied f r o m transformers with delta-
unfaulted phases. T h e inductive and capacitive c o m -
c o n n e c t e d secondaries, g r o u n d i n g of o n e phase o r one
ponents o f current neutralize each other and the o n l y <x
corner-of-the-delta" has s o m e t i m e s been d o n e as a
remaining current in the fault is due to resistance,
means o f obtaining a g r o u n d e d system. A d v a n t a g e s
insulator leakage and c o r o n a . T h i s current is relatively
are: ( 1 ) may be less costly for existing delta systems;
small, and, as it is in phase with the line-to-neutral
( 2 ) possibility o f slightly better protection with t w o -
voltage, the current and v o l t a g e pass through a z e r o
element m o t o r starters w h e n located in the t w o un-
value at the same instant. In addition, the rate-of-rise
g r o u n d e d phases. W i t h p r o p e r l y c o n n e c t e d control
of r e c o v e r y v o l t a g e o n the faulted phase is v e r y l o w .
circuits, g r o u n d s in the c o n t r o l circuit will n o t start
H e n c e , the arc is extinguished without restriking and
the m o t o r and will not prevent stopping the m o t o r
flashovers in the presence of self-healing dielectrics like
b y pushing the pushbutton. Disadvantages are: ( 1 ) in-
air, are quenched without removing the faulted line sec-
ability t o supply dual v o l t a g e service for lighting and
tion from service.
p o w e r l o a d : ( 2 ) necessity o f positive identification of
O n systems for w h i c h faults in air are relatively g r o u n d e d phase t h r o u g h o u t the s y s t e m to avoid c o n -
frequent, ground-fault neutralizers m a y b e v e r y useful necting meters, instruments and relays in the g r o u n d e d
b y reducing the n u m b e r o f circuit breaker operations phase; ( 3 ) line-to-ground v o l t a g e is higher than in
required t o r e m o v e faults, thus i m p r o v i n g service neutral-grounded system. B e c a u s e o f its limitations
continuity. T h e y have been used primarily o n systems this type o f g r o u n d i n g has n o t been w i d e l y used in
above 15 kilovolts, consisting largely o f o v e r h e a d trans- industrial systems.

10

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
One Phase of A Delta System Grounded of the g r o u n d i n g transformer. T h e m e t h o d o f wind-
at the M i d - P o i n t ing is seen from Figure 1.3 to be such that w h e n these
three equal currents flow, the current in o n e section
W h e r e existing systems at 600 volts and b e l o w are
of the w i n d i n g of each leg of the c o r e is in a direction
supplied b y three single-phase transformers with m i d -
opposite to that in the other section o f the winding
taps available, it is possible to gain s o m e of the ad-
on that leg. T h i s tends to force the ground-fault cur-
vantages of neutral g r o u n d i n g b y g r o u n d i n g the m i d -
rent to have equal division in the three lines and
tap of one phase. The distribution of voltage stress
accounts for the l o w i m p e d a n c e o f the transformer
among the phases remains somewhat unbalanced (50 per-
to g r o u n d currents.
cent overvoltage to ground on one phase conductor).
The system is frequently found in electric utility service A w y e - d e l t a c o n n e c t e d transformer can also be
at 240 volts to supply 240/120 volts single-phase three- utilized as a g r o u n d i n g transformer. T h e delta c o n -
wire, and 240 volts three-phase three-wire simultaneously. nection must b e c l o s e d to p r o v i d e a path for the
zero-sequence current, but the delta can b e designed
SELECTION A N D DESIGN OF for any convenient v o l t a g e level. It m a y o r m a y not
SYSTEM GROUNDING ARRANGEMENTS be used to serve other loads. T h e w y e w i n d i n g must
Obtaining the S y s t e m Neutral be o f the same v o l t a g e rating as the circuit which
is to b e g r o u n d e d . Caution should be exercised in
T h e best w a y to obtain the system neutral for applying single-phase transformer units o f a rating
grounding purposes is to use source transformers o r such that the transformer v o l t a g e rating w h e n ap-
generators with w y e - c o n n e c t e d windings. T h e neutral plied line-to-neutral is not equal to or greater than the
is then readily available. Such transformers are avail- system line-to-line v o l t a g e . T h e reason for this is
able for practically all v o l t a g e s e x c e p t 240 volts. O n that transformer reactance varies inversely as the
new systems, 2 0 8 Y / 1 2 0 o r 4 8 0 Y / 2 7 7 - v o l t transformers square o f the v o l t a g e applied. T h e c o n n e c t i o n s o f the
may be used to g o o d advantage instead o f 240 volts. transformer are s h o w n in Figure 1.4.
For 2400-volt or 4800-volt systems, special 2400 w y e -
or 4800 w y e - c o n n e c t e d source transformers m a y b e
purchased or g r o u n d i n g transformers used.
^
^
Grounding Transformers
•+—
System neutrals m a y not be available, particularly
in m a n y old systems 600 volts o r less and m a n y
existing 2400-, 4800- and 6900-volt systems. W h e n J"
it is desired to g r o u n d existing delta c o n n e c t e d
systems, g r o u n d i n g transformers m a y b e used to
obtain the neutral. G r o u n d i n g transformers m a y b e
either of the z i g - z a g o r w y e - d e l t a type. T h e type o f
g r o u n d i n g transformer m o s t c o m m o n l y used is a
three-phase, z i g z a g transformer with n o s e c o n d a r y
winding. T h e internal c o n n e c t i o n o f this transformer
is illustrated in F i g u r e 1.3. T h e impedance o f the
transformer to three-phase currents is high s o that,
when there is n o fault o n the systems, o n l y a small
magnetizing current flows in the transformer winding.
T h e transformer i m p e d a n c e t o g r o u n d current, h o w -
\
>
Figure 1.4
ever, is l o w so that it allows high g r o u n d current to Vectors representing flow of current in wye-delta transformer used
as grounding transformer. Line-to-ground fault shown.
flow. T h e transformer divides the g r o u n d current
into three equal c o m p o n e n t s ; these currents are in
phase with each other and flow in the three w i n d i n g s T h e short-time k v a rating o f a g r o u n d i n g trans-
former is equal t o rated line-to-neutral voltage times
LINE LEADS rated neutral current. A g r o u n d i n g transformer, is
designed to carry its rated current for a limited time
o n l y such as 10 s e c o n d s o r o n e minute. H e n c e , it is
m u c h smaller in size than an ordinary three-phase
transformer o f the same rated kva.

A g r o u n d i n g transformer should be c o n n e c t e d to
the system in such a manner that the system will
always b e g r o u n d e d . F i g u r e 1.5(a) s h o w s a ground-
ing transformer with an individual line breaker for
c o n n e c t i o n directly t o the main bus of the system.
NEUTRAL LEAD
Figure 1.5(b) s h o w s a m e a n s o f connecting a ground-
ing transformer to a s y s t e m without an individual
[Q) WINDING SHOWN O N CORE <b) SCHEMATIC DIAGRAM
OF C O N N E C T I O N S
line breaker. I n this case, the g r o u n d i n g transformer
Figure 1.3 is c o n n e c t e d b e t w e e n the main transformer bank and
Diagram showing windings of core and schematic diagram
of connections of a 3-phase zigzag grounding transformer. its breaker. If g r o u n d i n g transformers are connected

11

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
resistance grounding is used to reduce the damage
which m a y result due t o a g r o u n d fault in the ma-
chine windings.

In the case o f small s y s t e m s supplied b y genera-


tors, reactance g r o u n d i n g ( t o p r o d u c e n o t less than
25 percent o f three-phase fault currents) m a y b e used
in the interest o f e c o n o m y and because ground-fault
currents are n o t t o o large. If the s y s t e m is small and
supplied b y transformers, they m a y have their neu-
trals g r o u n d e d solidly for the same reason.

In m e d i u m - v o l t a g e systems, w h e n ground-fault p r o -
tection is desired, it is p r o v i d e d b y using standard
overcurrent relays. Positive tripping can b e a c c o m -
plished with l o w magnitudes o f fault current. F o r
this reason resistance g r o u n d i n g is used e x c e p t for
those cases w h e r e the size o f the s y s t e m is s o small
that the m a x i m u m available fault current is n o t t o o
high t o b e o b j e c t i o n a b l e .

A t the present time, it is m o s t c o m m o n practice to


operate 2.4-kilovolt s y s t e m s w i t h o u t the system neu-
tral g r o u n d e d . M o r e and m o r e o p e r a t o r s h o w e v e r
are a p p l y i n g s y s t e m neutral g r o u n d i n g to 2.4-kilovolt
systems. T h e c o n v e n t i o n a l m e t h o d is to p r o v i d e suf-
ficient ground-fault current t o enable selective relay-
ing through the application o f residual o r g r o u n d
relays.

S o m e operators feel that it is desirable t o g r o u n d


Figure 1.5 the 2.4-kilovolt s y s t e m neutral b u t that the g r o u n d -
Methods of connecting grounding transformers to a delta-connected fault current should b e o f a v e r y small magnitude,
or ungrounded power system to form a neutral
for system grounding just e n o u g h t o stabilize the neutral t o prevent severe
transient o v e r v o l t a g e s u p o n the o c c u r r e n c e o f re-
as s h o w n in Figure 1 . 5 ( b ) , there should b e o n e striking g r o u n d s . T h i s d o e s n o t cause a l o a d s h u t d o w n
grounding transformer for each delta-connected bank due t o a g r o u n d fault w h i l e , at the same time, elim-
supplying p o w e r to the s y s t e m ; o r e n o u g h t o assure inating the same types o f transient o v e r v o l t a g e haz-
at least o n e g r o u n d i n g transformer o n the s y s t e m ard. It h o w e v e r d o e s n o t eliminate all types o f o v e r -
at all times. W h e n the g r o u n d i n g transformer is s o voltages. T h e specific value o f ground-fault current
connected it is included in the protective system o f that should b e permitted t o flow has n o t been well
the main transformer. established but s o m e industrial experience indicates
that this value should b e greater than the line charg-
ing current. T h e high-resistance g r o u n d i n g practice
Suggested Grounding Methods
could b e e m p l o y e d with the circuits as s h o w n in
Low-Voltage Systems (600 volts and below)
Figure 1.5. T h e o n l y difference in the various meth-
L o w - v o l t a g e systems are practically always effec- o d s o f resistance g r o u n d i n g is the a m o u n t o f g r o u n d -
tively grounded. O n e reason for this is that n o e x - fault current that flows. W h e r e selective g r o u n d re-
pense is necessary for reactors. A n o t h e r reason is that laying is required, c o n s i d e r a b l y higher values o f
l o w - v o l t a g e switchgear a l m o s t universally uses direct ground-fault current are required.
series trip devices. Such devices d e m a n d high current
magnitudes. F o r these reasons, effective g r o u n d i n g
is used o n systems rated 600 v o l t s and b e l o w . F o r High-Voltage Systems ( a b o v e 15 k i l o v o l t s )
such systems, it is especially important to p r o v i d e S y s t e m s a b o v e 15 k i l o v o l t s are nearly always ef-
low-resistance return paths for ground-fault currents fectively g r o u n d e d , b e c a u s e these are usually trans-
in the plant equipment g r o u n d system. D a m a g e from mission circuits with o p e n lines in w h i c h , in m o s t
high fault current magnitude is m i n i m i z e d because cases, grounded-neutral service lightning arresters are
l o w - v o l t a g e circuit breakers are e x t r e m e l y fast in desirable for better o v e r v o l t a g e protection and l o w e r
operation. cost. In addition, rotating equipment is s e l d o m c o n -
nected directly to these s y s t e m s ; hence, limiting
Medium-Voltage Systems (2.4 kv to 15 kv) ground-fault currents, to prevent burning o f lamina-
tions, is a less important factor than in m e d i u m
M e d i u m - v o l t a g e systems are usually resistance v o l t a g e systems. In addition, v o l t a g e s a b o v e 15 kilo-
grounded. In this range of system v o l t a g e s , limiting volts are n o t usually carried inside buildings, hence
ground-fault current is h i g h l y desirable in the usual personnel hazards due t o h i g h fault currents are not
industrial p o w e r system. C o n n e c t i o n of rotating ma- a factor. Finally, the c o s t o f resistors f o r resistance
chines directly at thetc v o l t a g e s is c o m m o n , h e n c e g r o u n d i n g at these v o l t a g e s is high.

12

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
Criteria for L i m i t i n g T r a n s i e n t O v e r v o l t a g e s 1 0
G r o u n d E a c h M a j o r S o u r c e B u s Section

Transient o v e r v o l t a g e s can be limited effectively to W h e n there are t w o o r m o r e m a j o r s o u r c e bus sec-


safe values, if the f o l l o w i n g criteria are o b s e r v e d : tions, each section should have at least o n e g r o u n d e d
neutral point, since the b u s tie circuit m a y b e open.
1. In resistance-grounded systems, the in-phase com- If there are t w o o r m o r e p o w e r s o u r c e s per bus sec-
ponent of ground-fault current should be at least tion, there should b e p r o v i s i o n for g r o u n d i n g at least
equal to, but preferably greater than, the charging t w o s o u r c e s o n each section.
current of the system.

2. In reactance-grounded systems the ratio of Xo/Xi N e u t r a l Circuit A r r a n g e m e n t s


should be 10 or less, where X is the zero-sequence
0
W h e n the m e t h o d o f g r o u n d i n g and the g r o u n d i n g
reactance of the system, including that of the neutral
point have been selected f o r a particular p o w e r s y s -
reactance and Xi is the positive-sequence reactance
tem, the next question to c o n s i d e r is h o w m a n y g e n -
of the system.
erator o r transformer neutrals will b e used for
3. W h e r e a c o m b i n a t i o n o f g r o u n d i n g transformer g r o u n d i n g and w h e t h e r ( 1 ) each neutral will b e c o n -
and neutral-grounding resistor is used, the nected independently to g r o u n d , o r ( 2 ) a neutral bus
g r o u n d i n g transformer i m p e d a n c e should be l o w with single g r o u n d c o n n e c t i o n will b e established.
relative to the neutral resistance. T h e ratio o f
Ro/Xo should be equal to or greater than 2, where Single P o w e r Source
Ro is the zero-sequence resistance of the circuit,
W h e n a p o w e r s y s t e m has o n l y o n e s o u r c e o f p o w e r
including the neutral resistor, and Xo is the zero-
(generator or transformer), grounding may be accom-
sequence reactance of the circuit, including that of
plished b y c o n n e c t i n g the s o u r c e neutral to earth
the transformer.
either directly o r t h r o u g h a neutral impedance. P r o -
vision o f a switch o r circuit b r e a k e r t o o p e n the
Selection of System Grounding Points neutral circuit is not necessary because neutral cir-
G r o u n d at E a c h V o l t a g e L e v e l cuits have practically z e r o potential with respect to
g r o u n d e x c e p t during the short interval o f a fault,
It is necessary to g r o u n d at each v o l t a g e level to
hence b r e a k d o w n s are n o t likely. A l s o , it is n o t de-
achieve the advantages o f neutral g r o u n d i n g in all
sirable to operate the s y s t e m u n g r o u n d e d b y having
parts o f the system. E a c h v o l t a g e level m a y be
the g r o u n d c o n n e c t i o n o p e n w h i l e the generator o r
g r o u n d e d at the neutral lead o f a generator, p o w e r
transformer is in service. In addition, the neutral
transformer bank, o r g r o u n d i n g transformer. A n y g e n -
switching e q u i p m e n t greatly increases the c o s t o f
erator o r transformer used for g r o u n d i n g should, as
grounding.
far as possible, be o n e w h i c h is a l w a y s c o n n e c t e d t o
the system. Alternatively, a sufficient n u m b e r o f g e n - In the event that s o m e m e a n s o f disconnecting the
erators o r transformers should be g r o u n d e d to insure g r o u n d c o n n e c t i o n is required in a particular case, a
at least o n e g r o u n d c o n n e c t i o n o n the s y s t e m at all metal-clad circuit breaker s h o u l d b e used rather than
times. an o p e n d i s c o n n e c t s w i t c h f o r i n d o o r installations.
T h e latter is h a z a r d o u s t o personnel if a g r o u n d fault
G r o u n d at the P o w e r S o u r c e and n o t at the L o a d should o c c u r at the time the switch is o p e n e d o r closed.

W h e n a p o w e r s y s t e m is g r o u n d e d at the neutral
Multiple P o w e r Sources
of w y e - c o n n e c t e d m o t o r s , o r at the primaries o f
wye-delta s t e p - d o w n transformers, it is necessary to W h e n there are o n l y a f e w generators or p o w e r
g r o u n d a number o f these points simultaneously to transformer banks at a station, individual neutral
insure that the system will remain g r o u n d e d w h e n impedances are frequently used. W i t h this arrange-
one o r m o r e o f these loads are o u t o f service. C o n - ment, the neutral o f each generator o r main trans-
sequently, ground-fault current m a y be e x c e s s i v e l y f o r m e r bank is c o n n e c t e d directly t o its neutral i m -
high w h e n all g r o u n d e d points are in service. Since pedance w i t h o u t intervening switching equipment. N o
p o w e r sources are fewer in n u m b e r than loads and special operating instructions are required since each
are less likely to b e disconnected, they are pre- i m p e d a n c e is automatically c o n n e c t e d w h e n e v e r the
ferred as g r o u n d i n g points. O t h e r disadvantages o f c o r r e s p o n d i n g p o w e r s o u r c e is in use, and is d e -
g r o u n d i n g at the l o a d are: energized w h e n e v e r this s o u r c e is disconnected.

( 1 ) Standard l o w - v o l t a g e unit substations have W h e n o n l y t w o s o u r c e s are i n v o l v e d , this arrange-


delta-connected primaries, therefore, special ment is preferable t o the use o f a neutral bus. W h e n
transformers are required, if the primaries are several s o u r c e s are i n v o l v e d , h o w e v e r , the g r o u n d
to be used as g r o u n d i n g points. current is increased each time a s o u r c e is added, and
m a y be raised t o levels w h i c h are undesirably high.
( 2 ) Since the ground-fault current is dependent o n
the n u m b e r o f feeders o r g r o u n d i n g points in In the case o f resistance g r o u n d i n g , each resistor
operation, it m a y v a r y w i d e l y d e p e n d i n g o n must be rated for sufficient current to assure satis-
system operating conditions. T h i s makes se- factory relaying w h e n operating independently. C o n -
lective relaying m o r e difficult and m a y require sequently, the g r o u n d current w i t h several resistors
additional directional g r o u n d relaying to avoid will be several times the m i n i m u m required for ef-
false tripping o f healthy feeder circuits. fective relaying.

13

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
W h e n individual resistors are used, circulation of Calculation of Ground-Fault Currents
third harmonic currents b e t w e e n paralleled genera-
tors is not a p r o b l e m since the resistance limits the T h e magnitude of current w h i c h will flow in the

circulating current to negligible values. event of a line-to-ground fault o n a g r o u n d e d system


is usually determined b y the reactance o f the grounded
W h e n there are m o r e than t w o or three generators apparatus, the reactance o f the lines o r cables lead-
or p o w e r supply transformer banks at o n e station, it ing to the fault, and the resistance and reactance of
is c o m m o n l y desirable to use o n l y o n e resistor. E a c h the ground return path including any intentional
p o w e r source is then c o n n e c t e d to the resistor through g r o u n d i n g resistance o r reactance. F o r interconnected
a neutral bus and neutral switching equipment. T h i s systems, calculation o f the current may be rather
arrangement keeps the ground-fault current to a prac- complicated. F o r simpler cases, an approximation of
tical minimum, since the ground current from the the available fault current m a y b e obtained.
station is never greater than can b e supplied through
a single resistor. It also assures the same value o f
Resistance Grounding
ground current regardless o f the n u m b e r o f genera-
tors or transformers in use and simplifies ground When a single line-to-ground fault o c c u r s on a
relaying. resistance-grounded s y s t e m , a v o l t a g e appears across
T h e primary purpose of the neutral breakers is to the resistor ( o r resistors), nearly equal to the normal
isolate the generator o r transformer neutrals from line-to-neutral v o l t a g e o f the system.
the neutral bus w h e n the source is taken out o f serv- T h e resistor current is equal to the current in the
ice, because the neutral bus is energized during fault. T h u s , the current is practically equal t o line-
ground faults. to-neutral v o l t a g e divided b y the n u m b e r of o h m s of
Circuit breakers are preferred to disconnecting resistance used. Resistors have a v o l t a g e rating equal
switches for indoor installations to assure safety to to line-to-neutral v o l t a g e and an ampere rating equal
personnel. If disconnecting switches are used, as in to the current w h i c h flows w h e n this v o l t a g e is ap-
s o m e o u t d o o r installations, they should b e elevated o r plied to the resistor. T h u s , for e x a m p l e , a m a x i m u m
metal-enclosed and interlocked in such a manner as ground-fault current o f a p p r o x i m a t e l y 2,000 amperes
to prevent their operation except when the trans- will be obtained o n a s y s t e m w h e n using a 2,000-
former primary and s e c o n d a r y switches o r generator ampere resistor. T h i s v e r y simple m e t h o d o f calculat-
main and field breakers are open. ing the ground-fault current is o n l y suitable when
the ground-fault current is small c o m p a r e d to the
It is sometimes desirable to operate with o n l y o n e three-phase fault current.
generator neutral breaker c l o s e d at a time to elimi-
nate any circulating h a r m o n i c o r z e r o - s e q u e n c e cur- T h e m e t h o d just outlined applied to faults o n lines
rents. W h e n the generator w h o s e neutral is g r o u n d e d or buses, or at the terminals of machines or trans-
is to be shut d o w n , another generator is g r o u n d e d , b y formers. If the fault is internal to a rotating machine
means of its neutral breaker b e f o r e the main and or transformer, the ground-fault current will b e less.
neutral breakers of the first o n e are o p e n e d . H o w e v e r , T h e reduction in current is primarily due to the in-
with similar generators and reasonably equal load ternal v o l t a g e o f the apparatus. In the case o f w y e -
division, circulating currents are negligible, and it is c o n n e c t e d equipment, this internal v o l t a g e is at full
often found practical to operate with neutral break- value at the terminals and is z e r o at the neutral. If
ers of t w o o r more generators closed. This sim- the fault o c c u r s at the neutral of any apparatus, no
plifies operating p r o c e d u r e and increases assurance voltage will appear across the s y s t e m g r o u n d i n g re-
that the system will be g r o u n d e d at all times. sistor, s o the fault current will b e z e r o . A t inter-
mediate points in the w i n d i n g b e t w e e n the neutral
In the case of multiple transformers, all neutral and a terminal, the fault current will b e intermediate
breakers m a y b e n o r m a l l y c l o s e d b e c a u s e the pres- b e t w e e n z e r o and the current t o a terminal fault.
ence of delta-connected w i n d i n g s ( w h i c h are nearly F o r example, at a point 10 percent o f the winding
always present o n at least o n e side o f each trans- length from neutral, the ground-fault current will be
former) minimizes circulation of harmonic current a p p r o x i m a t e l y 10 percent o f the value for a terminal
between transformers. fault. F o r a fault a n y w h e r e b e t w e e n this point and

W h e n total ground-fault currents with several in- a terminal, the current will b e m o r e than 10 percent

dividual resistors w o u l d e x c e e d about 4,000 amperes, of the a m o u n t for a terminal fault.

it is suggested that neutral switchgear and a single In the case of delta-connected machines the inter-
resistor be considered for resistance g r o u n d e d systems. nal v o l t a g e t o neutral m a y be c o n s i d e r e d to be 100
W h e n o n l y o n e source is i n v o l v e d , but others are percent at the terminals and 50 percent at the mid-
to be added to the station in the future, it is sug- point o f the w i n d i n g s . T h e mid-points have the l o w -
gested that space be a l l o w e d s o that neutral switch- est potential with respect to the electric neutral of
gear can be added w h e n this b e c o m e s necessary. any part o f the winding. T h e r e f o r e , a g r o u n d fault at

14

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
any point In the w i n d i n g will p r o d u c e a g r o u n d fault to w h i c h it is c o n n e c t e d . W h e n a resistor is used
current o f 50 percent o r m o r e o f the resistor current between neutral and g r o u n d , the current rating o f the
rating. g r o u n d i n g transformer is based o n the resistor rated
current. In either case, the transformer is rated to
carry the required current for rated time without ex-
Reactance G r o u n d i n g ceeding its rated temperature limits. Many system
grounding devices are short-time rated. Care must be
In a reactance-grounded s y s t e m with a single line-
exercised in their application to insure that current will
to-ground fault, the ground-fault current m a y be
be automatically interrupted before the thermal limits of
computed from the f o r m u l a :
components are exceeded.
Ig = 3E (Resistance may
Xi + X% -|- Xo -\- 3X n usually be neglected)
Resistor Ratings
(U)
Xi = System positive-sequence reactance (ohms per T h e determination of the resistor o h m i c value, thus
phase) the magnitude o f ground-fault current, is based o n
X 2 = System negative-sequence reactance (ohms per ( 1 ) p r o v i d i n g sufficient current for satisfactory per-
phase) formance of the s y s t e m relaying scheme, and ( 2 ) lim-
Xo = System zero-sequence reactance (ohms per phase) iting ground-fault current to a value which will p r o -
duce minimum d a m a g e at the point o f fault. In m o s t
X n = Reactance of neutral grounding reactor (ohms)
cases, the ground-fault current is limited b y the neu-
E = Line-to-neutral voltage (volts)
tral resistor to a small fraction of that which would
Ig z= Ground-fault current (amperes) flow for a three-phase fault. T o determine the mini-
mum ground-fault current required, a diagram of the
system must be available, giving ratings of current
Solid G r o u n d i n g
transformers and types of relays for each circuit. This
In a system with solid neutral c o n n e c t i o n to g r o u n d , diagram should include consideration of future changes.
the ground-fault current for a single-line-to-ground
fault, m a y be c o m p u t e d from the formula:
T a b l e 1.1
Ig = 3E (1.2)
Xi -f- X% -f- Xo Selection o f G r o u n d i n g R e s i s t o r

Note: ( V a l u e s given are m i n i m u m r e c o m m e n d e d


Selection o f G r o u n d i n g E q u i p m e n t R a t i n g s 4
ground-fault currents in percent o f rated
primary current o f current transformers)
Grounding resistors, reactors and g r o u n d i n g trans-
formers are n o r m a l l y rated to carry current for a Equipment Protected Type of Relaying
limited time only. T h e standard time interval rating Ground Differ-
usually applicable for industrial systems, with relays Overcurrent ential Other
arranged to protect the g r o u n d i n g equipment, is 10
seconds. Wye-connected genera- 100% 100% 1

tors, m o t o r s and trans-


T h e v o l t a g e rating o f a g r o u n d i n g resistor should formers
be the line-to-neutral v o l t a g e rating of the system.
D e l t a - c o n n e c t e d genera- 40% 40%
T h e insulation class o f a reactor is determined b y tors, m o t o r s and trans-
the system line-to-neutral v o l t a g e . T h e v o l t a g e rating formers
may be less than line-to-neutral voltage, it being cal-
culated b y multiplying the rated current b y the i m - Lines and cables 20% 2 , 3
Pilot wire-
pedance o f the reactor. 100%
Current
T h e v o l t a g e rating o f a g r o u n d i n g transformer balance-
should be system line-to-line v o l t a g e . 100%
Grounding resistors are rated in terms o f the ini- Buses 50%*
tial current w h i c h will flow through the resistor, with
rated resistor v o l t a g e applied.
Notes for Table 1.1:
T h e rated current o f a g r o u n d i n g reactor is the
1. If ground differential is added to the generator, the ground-
thermal current rating. It is the root-mean-square neu- fault current may be limited to lower values (if other sys-
tem requirements permit).
tral current in amperes w h i c h the reactor will carry
for its rated time without e x c e e d i n g standard tem- 2. Where ground-overcurrent relays for lines and cables also
serve for back-up protection for machines or transformers,
perature- limitations. this value should be 100 percent.

3. When phase relays must be set to wait for other breakers


If a g r o u n d i n g transformer neutral is solidly c o n - to clear any through phase-to-phase fault, required ground
nected to g r o u n d , the current w h i c h will flow during current may have to be as high as 50 percent of the current
transformer rating to avoid false tripping.
a g r o u n d fault is primarily determined b y the react-
4. Based on current differential. If voltage differential is pro-
ance of the g r o u n d i n g transformer and o f the system vided, ground-fault current may be limited to lower values.

15

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
T h e magnitude o f ground-fault current must b e Ig = Current through reactor for line-to-ground
sufficient for operation o f all relays. In general, if the fault
current is high e n o u g h t o operate the relays o n the
• F o r Xx of generators use transient reactance.
larger circuits, it will be adequate for the smaller cir-
cuits. T h e g r o u n d currents required for satisfactory **X a for turbine generator is same as sub-transient
operation of various types o f relays, expressed in reactance.
terms of current transformer rating, are given in T h e neutral-grounding reactor should b e selected
T a b l e 1.1. N o t e that the ground-fault current under to carry the available current under all practical oper-
all system operating conditions must equal o r exceed ating conditions. W i t h any g i v e n condition o f c o n -
the minimum required f o r relaying each circuit c o n - nected grounded-neutral sources, the addition of un-
nected to the system. T h i s value is established b y g r o u n d e d neutral s o u r c e s and loads will increase the
selecting the highest o f those currents w h i c h m e e t the current flow through the g r o u n d e d neutral c o n n e c t i o n s .
requirements o f the several conditions set forth in
T a b l e 1.1. Grounding Transformer Ratings
A n exception to this rule will be found in high-resis- T h e electrical specifications o f a g r o u n d i n g trans-
tance grounding in which the ground current will be former are:
limited to a very low value approximately equal to the
Voltage — t h e line-to-line v o l t a g e o f the system.
fundamental frequency system-to-ground capacitive charg-
ing current. This will usually be but a few amperes, Current — t h e m a x i m u m neutral current.
insufficient to afford selective ground-current relaying. Time — u s u a l l y designed t o carry rated cur-
rent for a short time, such as 10 sec-
Reactor Ratings o n d s o r 60 s e c o n d s .

T h e reactance of a neutral g r o u n d i n g reactor should Reactance — this quantity is a function of the ini-
be chosen to limit the g r o u n d current and the current tial s y m m e t r i c a l system three-phase
in the faulted phase t o the desired value. In o r d e r to short-circuit kva.
minimize transient overvoltages, the ground-fault cur- Determination o f grounding-transformer reactance
rent must not be less than 25 percent o f three-phase is based o n the f o l l o w i n g : T h e criterion for limiting
fault current. T h i s c o r r e s p o n d s t o a ratio o f Xo/Xi = transient o v e r v o l t a g e s in a s y s t e m is that the ratio
10. F o r reactance g r o u n d i n g o f generators, the cur- Xo/Xi should be equal to or less than 10 (if used in
rent in any w i n d i n g must n o t e x c e e d the three-phase series with a grounding resistor it is necessary only that
fault current. T h i s c o r r e s p o n d s t o a ratio o f XoJX% = the ratio Ro/Xo be 2 or greater. The criterion for using
1. T h i s establishes the criteria for m a x i m u m and grounded-neutral type lightning arresters is that Xo/Xi
minimum value o f neutral reactance. If the neutral should be equal to or less than 3. In a system having a
reactance is selected in a c c o r d a n c e with the f o l l o w i n g grounding transformer, its reactance is the principal part
relationship, the current in the w i n d i n g o f the faulted of Xo in the above criterion. A l s o , the positive-sequence
phase will not exceed the three-phase fault current o f reactance, Xt, is equal to the reactance of the system to
the machine regardless o f system reactance: initial symmetrical root-mean-square three-phase, short-
y _ Xi -Xo (1.3) circuit current. Thus, the grounding transformer re-
Xn 3 actance is a function of the initial symmetrical system
three-phase short-circuit kva.
where X n = Reactance o f neutral reactor
Xi = Generator positive-sequence subtransient O n a system otherwise u n g r o u n d e d , the g r o u n d i n g -
reactance transformer reactance, Xgt in o h m s per phase, re-
quired to p r o v i d e any specified X /Xi ratio is given
Xo = Generator z e r o - s e q u e n c e reactance
0

b y the f o l l o w i n g f o r m u l a :
H o w e v e r , the current w h i c h flows through the g e n -
x Xo/Xr X kv2 X 1000
erator neutral reactor itself is not independent o f System symmetrical 3-phase short-circuit kva
system constants, and m a y often e x c e e d the three- (1.9)
phase fault current of the machine. T h e current rat-
W h e n lightning arresters for grounded-neutral service
ing of a neutral reactor is determined b y the n u m b e r
are to be applied, the grounding-transformer neutral
and characteristics o f system sources and whether
should be solidly g r o u n d e d and its reactance m a y be
they are grounded o r u n g r o u n d e d .
determined b y :
T h i s rating (the thermal current r a t i n g ) , can be x = 3000 X kyg
calculated b y the following f o r m u l a : System initial symmetrical 3-phase short-circuit kva
3£ (1.4) (1.10)
I a =

9
Xx + X , + 3Xn) Special Problems
where: The Influence of Grounding Methods on Control
*Xi = System positive-sequence reactance Circuit Safety in Systems 600 Volts and Below
**X* = System negative-sequence reactance
Frequently, the safety o f a c o n t r o l circuit is offered
Xo = System zero-sequence reactance as a reason for a particular m e t h o d of grounding.
X n = Reactance of neutral-grounding reactor In all cases, w h e n m o t o r starter c o n t r o l circuits are
E = Line-to-neutral voltage set up without c o n t r o l p o w e r transformers, it b e c o m e s

16

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
evident that there are p r o b l e m s with regard t o circuit because of the limited system and the absence of
arrangement w h i c h must be considered in order to switching devices, is satisfactory from the standpoint
minimize operating difficulties and personnel hazards. of transient o v e r v o l t a g e s . Since n o p r o b l e m of relay
Accidental m o t o r starting due to faulty c o n t r o l cir- coordination is involved, the relaying problem is
cuits m a y b e associated with u n g r o u n d e d systems as simple.
well as m o s t types of g r o u n d e d systems.
Three-Phase, F o u r - W i r e Systems

Autotransformers In these systems, single-phase loads are connected


P o w e r autotransformers are quite frequently used between phase c o n d u c t o r s and the neutral conductor.
in electric utility p o w e r transmission and distribution T h e neutral c o n d u c t o r is insulated o v e r its entire
systems. Their use in industrial p o w e r systems as a length, except w h e r e it is g r o u n d e d at its source o f
part o f the p o w e r distribution system is relatively in- supply. The neutrals of such systems should be
frequent. Autotransformers are quite c o m m o n , h o w - g r o u n d e d such that, during a g r o u n d fault, the v o l t -
ever, in control and utilization equipment. Systems age between any phase c o n d u c t o r and ground does
using autotransformers m a y be subject to dangerous not appreciably e x c e e d normal line-to-ground v o l t -
fundamental-frequency overvoltage during system age. Four-wire systems should thus be effectively
faults, or from high-frequency or steep-wave-front grounded in such a manner that the ground-fault
transient overvoltages on the lines, originating from currents are a p p r o x i m a t e l y equal to three-phase fault
lightning or switching surges. In some cases, solidly currents. T h i s is usually accomplished b y direct c o n -
grounding the neutral o f the autotransformer is a nection of transformer bank neutrals to ground with-
satisfactory means of eliminating o v e r v o l t a g e s . T h e out any intentional neutral impedance.
disadvantage of solid-neutral grounding is that third
harmonic currents and telephone interference may BIBLIOGRAPHY
b e c o m e excessive in certain cases. T h e s e harmonic
*1. Application Guide for Grounding of Synchronous
problems can usually b e eliminated b y the use o f a
Generator Systems—AIEE Committee Report, A I E E
tertiary delta on the autotransformer.
Transactions, Apparatus and Systems, June 1953,
pages 517-26.

S y s t e m s with Utility Supply *2. Application Guide on Methods of Neutral Ground-


ing of Transmission S y s t e m s — A I E E Transac-
S o m e industrial systems are directly connected at
tions, A u g u s t 1953, pp. 663-668.
their operating v o l t a g e to utility systems. W h e n such
is the case, the s c h e m e o f g r o u n d i n g the industrial *3. Present D a y Grounding Practices on Power Sys-
system should be p r o p e r l y coordinated with that for tems—Third A I E E R e p o r t o n S y s t e m Grounding,
the utility system. A I E E Transactions. V o l . 66, 1947, p. 1525.

If t w o systems are interconnected b y means o f a 4. A I E E Standard N o . 32—Neutral Grounding D e -


vices.
transformer bank, at least o n e w i n d i n g o f the bank
will normally be c o n n e c t e d in delta, and this delta- 5. T h e U s e o f 600-Volt and 460-Volt P o w e r Systems
connected w i n d i n g will make each system independ- with G r o u n d e d Neutrals—James P. E . A r b e r r y ,
ent from the standpoint o f grounding. A I E E National P o w e r Conference Proceedings,
Pittsburgh, Pa., A p r i l 1950.

Generator-Transformer U n i t Installations 11 6. L o c a t i n g G r o u n d s o n 480-Volt, 3-Phase Delta


S y s t e m s — B . G. F o r b e s , P o w e r Generation, Sep-
Generator-transformer unit installations sometimes tember 1949, p p . 60-61.
use an arrangement consisting o f a distribution-type
7. Industrial P o w e r S y s t e m s H a n d b o o k , Chapter 5
transformer, loading resistor and relay in the g e n -
McGraw-Hill B o o k Co., N e w York, N. Y .
erator neutral. T h i s s c h e m e m a y be p r o v i d e d with a
5 or 10 minute rating t o permit time for transferring 8. Protection o f Industrial Plants Against Insula-
load off the affected machine before it is taken out tion B r e a k d o w n and Consequential D a m a g e —
of service. T h e distribution transformer will usually H . R . V a u g h a n , A I E E T e c h n i c a l Paper 46-122,
June 1946.
have a rating o f 25 kva to 50 kva, and the relay m a y
be connected to operate o n resistor current o r v o l t a g e 9. A p p l i c a t i o n o f G r o u n d - F a u l t Neutralizers—AJEE
depending o n the particular installation. C o m m i t t e e R e p o r t , Electrical Engineering, July
1953, p . 606.
T h i s system is used because the c o s t o f the resistor
and distribution-type transformer is often less than 10. Electrical T r a n s m i s s i o n and Distribution Refer-
the c o s t o f a high-voltage low-current resistor con- ence B o o k — W e s t i n g h o u s e Electric Corp., Fourth
nected directly between the neutral and g r o u n d . T h i s Edition, S e p t e m b e r 1950, Chapters 14 and 19.
results in an effective high-resistance g r o u n d w h i c h .
*Also printed as A I E E Grounding Guides, No. 954, October 1954.

17

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
11. Grounding Principles and Practice I I I — G e n e r a - — H . G. Barnett, Mill and F a c t o r y , M a y 1951 or
tor Neutral G r o u n d i n g D e v i c e s — A . A . Johnson, A I E E Transaction P a p e r N o . 55-689.
Electrical Engineering, M a r c h 1945, pp. 92-99.
16. S y s t e m Neutral G r o u n d i n g in Industrial Plants—
12. Grounding o f Industrial S y s t e m s — W . C. B l o o m - D . L . Beeman, A I E E National P o w e r Conference
quist, General Electric R e v i e w , A u g u s t 1951. P r o c e e d i n g s , Pittsburgh, Pa., A p r i l 1950.
13. Neutral vs. Corner-of-the-Delta Grounding — 17. N e w s Bulletin of the International A s s o c i a t i o n of
W . F. Strong, Electrical W o r l d , S e p t e m b e r 25,
Electrical Inspectors, Interim R e p o r t of A m e r i c a n
1950.
Research C o m m i t t e e o n G r o u n d i n g , M a r c h 1944.
14. Industrial P o w e r Systems H a n d b o o k , Chapters 5,
18. G r o u n d e d vs U n g r o u n d e d L o w - V o l t a g e A - C Sys-
6 and 7, M c G r a w - H i l l B o o k C o . , N e w Y o r k , N . Y .
tems—H. B. Thacker, AISE Paper and Disc,
15. W h y Ground L o w - V o l t a g e Distribution S y s t e m s ? I r o n & Steel Engineer, A p r i l 1954, pp. 65-72.

18

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
CHAPTER II

EQUIPMENT GROUNDING

GENERAL REASONS FOR GROUNDING path in the enclosure will result in arcing and heat-
ing at breaks and joints. If additional current capacity
T h e main purpose of equipment g r o u n d i n g is t o
is required in the return circuit it should be added
provide safety for operators, electricians, repairmen
b y means of c o n d u c t o r s inside the conduit or metallic
and the general public. T h i s is a c c o m p l i s h e d b y in-
enclosure, and not outside.
suring that in general all parts of steel structures,
m o t o r and generator frames, control equipment en-
Types of Equipment to be Grounded
closures, switchgear, cable armor, conduit, portable
electric equipment, and any metallic b o d y enclosing 1. Structures
or near an electric circuit w h i c h is accessible to per-
2. O u t d o o r Stations
sons, shall be at g r o u n d potential. T h i s is e m b o d i e d
in the rules o f the National Electrical C o d e and the 3. L a r g e Generators and M o t o r R o o m s
National Electrical Safety C o d e . 4. Conductor Enclosures

In the case o f accidental contact b e t w e e n the elec- 5. Miscellaneous M o t o r s


tric circuit and the metallic b o d y , the latter assumes a 6. Portable Equipment
potential a b o v e g r o u n d equal to that part o f the cir-
cuit with w h i c h it is in contact. Unless this b o d y is
GROUNDING OF STRUCTURES
intentionally g r o u n d e d , it is m o r e than likely to be
simply electrically isolated from g r o u n d . U n d e r this Reasons for L o w Resistance to Earth
condition, it w o u l d be c o n n e c t e d to earth through a
resistance of hundreds o r thousands of o h m s , instead G r o u n d c o n n e c t i o n s must be adequate for both nor-
of a few o h m s if it w e r e g r o u n d e d , o r millions of mal and fault current. It is essential that the resistance
o h m s if it w e r e insulated. T h e r e f o r e , a flow o f current of structures to earth be extremely l o w in order to
w o u l d be permitted, and if the potential differences hold the potential difference as low as possible. Refer-
between the electric circuit and g r o u n d are such as ence 10 describes and defines this problem clearly. Refer
are c o m m o n l y found in practice, not o n l y w o u l d the to Chapter I V for values of resistance to earth.
conducting b o d y be at a potential a b o v e g r o u n d w h i c h
m a y in m a n y cases be dangerous to life, but there will Ground Bus
be a light flow of current to g r o u n d through the leak-
T h i s bus, w h i c h m a y serve for g r o u n d i n g large
age path w h i c h m a y easily be the cause of fire through
m o t o r s , generators, etc., should not b e smaller than
heating o f flammable substances if there are any
N o . 2 / 0 A W G c o n d u c t o r . It should be connected to
present.
water mains and g r o u n d r o d s . Small installations may
require N o . 4 / 0 , while larger ones m a y use 500,000
T h e actual g r o u n d i n g o f the c o n d u c t i n g b o d y al-
or 750,000 circular mil capacity c o p p e r wire or copper
l o w s sufficient current flow in the event o f an acci-
bar or any other suitable c o n d u c t o r . H o w e v e r , the
dent to insulation to insure positive operation o f
current-carrying capacity should never be less than 25
ground-detecting devices and the operation o f fuses
percent of the highest continuous current rating of
and circuit breakers. It also tends to prevent the p o -
any piece of equipment. If materials other than copper
tential b e t w e e n a c o n d u c t i n g b o d y and g r o u n d from
are used, the c o n d u c t i v i t y should be equivalent to
rising to a dangerous value. It is essential therefore
copper. S o m e consideration should be given t o catho-
that the impedance of the return path for g r o u n d -
dic protection w h e r e dissimilar metals are used.
fault currents be as l o w as possible and that the
grounding c o n d u c t o r s be large enough to carry the
m a x i m u m g r o u n d current for a reasonable time with- Structure Ground Connections
out burning off. T h e steel f r a m e w o r k o f buildings should be
g r o u n d e d at the base o f every corner c o l u m n and
T h e 60 c y c l e reactance of any g r o u n d return circuit
intermediate c o l u m n s at distances not greater than
remote from the o u t g o i n g circuit c o n d u c t o r will be 60 feet. T h e c o n n e c t i o n s from the g r o u n d bus o r grid
high c o m p a r e d to its resistance, and will limit the to the structure should not be less than 2/0 copper
magnitude of g r o u n d return current w h i c h it will and should be m a d e b y brazing, thermit welding,
carry. Recent tests " lead to the conclusion that w h e n
8 9
equivalent p r o c e s s , or a suitable solderless terminal.
the circuit c o n d u c t o r s are enclosed in a metallic en- T h e metal structures for switchgear, lightning
closure such as conduit, bus enclosure o r armor, the arresters, d i s c o n n e c t switches, transformers, grillwork,
metallic enclosure will carry a major portion of the etc., should be individually c o n n e c t e d to the ground
return fault current. Failure to p r o v i d e a continuous bus, similar to the building framework.

19

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
In isolated-phase stations, where a ground-fault G r o u n d i n g o f O u t d o o r Structures
relay protective scheme is used, it is necessary that
all of the stationary metallic parts of the switchgear Refer to G R O U N D I N G O F S T R U C T U R E S in
this chapter.
not at bus potential be c o n n e c t e d to a fault-current
bus, a section of the latter being p r o v i d e d for each
section of the main bus. In turn, each section of G r o u n d i n g o f O u t d o o r Station F e n c e
fault-current bus is connected to the station ground
A metal fence surrounding an o u t d o o r station should
bus through a current transformer
be grounded. A ground c o n d u c t o r of not less than N o .
Disconnecting switches directly bolted to a steel 1/0 A W G should be installed around the fence, ap-
structure need no further g r o u n d except that operat- proximately 12 to 24 inches away from it and about
ing pipes of all gang-operated disconnecting switches 12 inches deep. This should be brazed or w e l d e d to
should be further grounded b y a N o . 1/0 A W G extra ground rods installed at 10 foot to 40 foot intervals.
flexible c o p p e r cable or equivalent c o n n e c t e d directly All corner fence posts and posts adjacent to ground
above the operating handle and run to the nearest rods should be c o n n e c t e d to the g r o u n d c o n d u c t o r s
part of the grounded supporting structure. being sure to connect to fence strands at these points.

Inspection T h e r e is a difference of opinion relative to connect-


T o obtain continuous and reliable service from ing the fence ground to the station g r o u n d bus. S o m e
ground connections, g o o d mechanical construction of the basic facts w h i c h underlie this c o n t r o v e r s y
must be supplemented b y adequate inspection. It is are as follows.
recommended that inspection of all c o n n e c t i o n s a b o v e In the event of a heavy flow of current through
the ground surface be m a d e yearly.
the connection to earth, due t o a g r o u n d fault o r a
lightning discharge, the station g r o u n d bus is elevated
GROUNDING OF OUTDOOR STATIONS
above earth potential b y a value equal to the voltage
Establishment o f G r o u n d B u s o r G r i d d r o p in the connection to earth. T h i s v o l t a g e drop
A n ideal grounding system consisting of a single is equal to the p r o d u c t o f the current and the im-
large conducting plate c o v e r i n g the entire area of pedance in the c o n n e c t i o n to earth. If the fence is
the station and connected t o earth at infinite points connected directly to the station g r o u n d bus, it will
is, of course, not practicable. Its effect, h o w e v e r , can also be elevated a b o v e earth potential b y the same
be approached b y installing a suitable g r o u n d grid amount. Because the potential gradient in the earth
surrounding the area o f the o u t d o o r station consisting adjacent to the fence d r o p s v e r y abruptly within the
of a continuous stranded c o p p e r cable, o r any other first three feet a w a y f r o m the fence posts o r other
suitable c o n d u c t o r , buried b e l o w the surface of the connections to earth, there m a y be a serious hazard
ground and connected to driven g r o u n d rods. T h e to personnel standing o n the earth and in contact
ideal size for the g r o u n d bus will depend o n the with the fence.
magnitude of the available ground-fault currents and
operating time of protective equipment. V e r y often the O n the other hand, if the fence g r o u n d is isolated
grounding system will consist of a mesh grid at or slight- from the station ground, the potential difference will
ly below ground level blanketing the substation area. appear between the station equipment and the fence.
Distributed over the area would be a multiplicity of W h e n the fence is separated from the station equip-
earthing terminals connected into this grid. The size ment or structure b y a considerable distance there
of conductor used might range from perhaps 4 / 0 to 500 is little possibility of contacting both at the same time.
M C M copper. U n d e r this condition there is s o m e merit in isolating
In the case of extensive substations with widely spaced the fence g r o u n d from the station g r o u n d .
apparatus items, individual local grids may be established
W h e n the resistance o f the station g r o u n d c o n n e c -
at the various equipment locations. These local grids
tion to earth is extremely l o w the rise in potential
would then be interconnected to form a single over-all
m a y be of no significance. If there is a possibility of
grounding system. Another method is to run several
high-voltage lines falling on the fence, it is desirable
cables across the substation area interconnecting the sides
to provide the least possible impedance in the ground
of the bus and forming a grid. Interconnecting c o n -
return path. U n d e r such conditions it m a y b e desir-
ductors should be not less than the size of the bus. able to interconnect the station g r o u n d and the fence
T h e ground bus should be c o n n e c t e d to any metallic ground.
water pipe, metallic drain o r sewer pipe located in the
In s o m e cases the fence g r o u n d and the station
station area o r within reasonable distance. C o n n e c -
ground are c o n n e c t e d together, and the station ground
tion should be m a d e to t w o points on the pipe at
grid extended to s o m e distance outside the fence to
least 20 feet apart and should consist of a c o n d u c t o r
reduce the abrupt changes in potential gradient in
of not less than the size of the g r o u n d bus.
the earth. (See reference N o . 1 0 ) .
A small local ground grid or metallic grating is often
installed at the spot a man would stand in operating a
G r o u n d i n g o f Circuit Neutrals
switch handle. Its purpose is to safeguard the operator
against a dangerous potential difference between the W h e r e it is necessary to g r o u n d a neutral circuit
switch handle and the ground surface on which he stands. such as the w y e point of a transformer bank or
(See reference No, 1 0 ) . generator, such g r o u n d connection should be made

20

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
Figure 2.1
Typical methods of connecting copper weld ground rod
to steel tower using welding method.

through a c o n d u c t o r of not less than 25 percent of


the conductivity of the largest phase c o n d u c t o r in
the circuit but not smaller than N o . 1/0 A W G . It is
desirable that this c o n n e c t i o n be made to t w o separate
points in the station g r o u n d bus.

General C o m m e n t s

(a) All ground bus and c o n n e c t i n g cable should be


run in such a manner as to be protected from m e -
chanical injury.

( b ) W h e r e g r o u n d cables are run under ground,


they should be laid with a reasonable amount of
slack to reduce the possibility of breakage.

( c ) All electrical conduits, metallic sheathed cable,


etc., in an o u t d o o r station, should be g r o u n d e d to the
station ground bus. Refer to G R O U N D I N G O F
C O N D U C T O R E N C L O S U R E S in this chapter.

Typical grounding c o n n e c t i o n s are s h o w n in Figures


2.1 and 2.2.

GROUNDING OF LARGE G E N E R A T O R
AND MOTOR ROOMS

In large stations, a ground bus of adequate size


should be run around the periphery of the building.
Conductor material should be soft drawn or m e d i u m
hard drawn c o p p e r wire, c o p p e r bar, or equivalent.
T h e g r o u n d bus should be c o n n e c t e d at t w o o r m o r e
points to g r o u n d i n g electrodes, the building structure Figure 2.2
Typical method of making a T connection of a ground wire
and to water mains, metallic drain and sewer pipes using welding method.

21

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
in order to keep the resistance of the g r o u n d bus t o to the point w h e r e the c o n d u c t o r s in the raceway
earth as l o w as possible. E a c h floor should have its system c o n c e r n e d receive their supply.
o w n ground bus.
T h e lead sheaths, shields and a r m o r of three c o n -
F o r mechanical strength, the g r o u n d bus should not ductor and small single c o n d u c t o r (less than 500,000
be smaller than N o . 2 / 0 A W G c o n d u c t o r . Small sta- circular mils) p o w e r cables should be grounded at
tions m a y require N o . 4 / 0 , while large o n e s m a y use both ends. In l o n g cables it is sometimes desirable
500,000 o r 750,000 circular mil size. In extreme cases, that sheaths also be g r o u n d e d at several intermediate
where extremely high ground-fault currents m a y be points.
expected, larger sizes m a y be required.
T h e lead sheath, shield and a r m o r o f large single-
Connections to building c o l u m n s should be not less c o n d u c t o r cables (500,000 circular mils and a b o v e )
than N o . 2 / 0 A W G and be m a d e b y brazing, w e l d i n g should be g r o u n d e d at o n e end o n l y to prevent cir-
or with suitable solderless terminals. G r o u n d c o n n e c - culating currents. T h e sheath, shield and armor of
tions from transformers, switchgear, m o t o r s and g e n - such a cable should b e insulated from g r o u n d through-
erators to the g r o u n d bus should be not less than out the remainder o f its length unless the cable is
N o . 1/0 A W G but must not be smaller in current- too long, in w h i c h case insulating joints must b e p r o -
carrying capacity than 25 percent o f the highest vided to permit g r o u n d i n g at a sufficient number of
continuous rating o f any piece o f primary apparatus points to keep sheath v o l t a g e s d o w n to desirable
to which it is connected. L a r g e generators, m o t o r s limits. F o r example, the mutual reactance t o neutral
and transformers should have t w o c o n n e c t i o n s to the (X )
m for a 500,000 circular mils standard strand cable
ground bus. A l o n g r o w o f switchgear units should varnished c a m b r i c insulated, lead sheathed (approxi-
have a ground connection from each end o f same. mate outside diameter 1.5 inches) with equivalent
Connections to the equipment to be g r o u n d e d m a y spacing between cables o f 3 inches, is approximately
be brazed, w e l d e d or m a d e with suitable solderless 0.0525 o h m per 1000 feet. A s s u m i n g a current (7c)
terminals. of 400 amperes in the c o n d u c t o r , the induced voltage
to neutral per 1000 feet can b e calculated from the
T w o typical g r o u n d i n g systems are s h o w n in F i g - formula:
ures 2.3 and 2.4.

GROUNDING OF CONDUCTOR ENCLOSURES


= 40 x 0.0525 = 21 v o l t s
List of Equipment to be Grounded
F o r lead-sheathed cable in duct, sheath voltage
T h e National Electrical C o d e specifies that e x p o s e d should be limited to 12 to 15 volts. F o r jacketed cable,
conductive materials enclosing electric equipment, o r sheath voltages o f 40 to 50 volts m a y be permitted
forming a part of such equipment, are g r o u n d e d for because the jacket acts as an insulator.
the purpose o f preventing a potential a b o v e g r o u n d
T h e m i n i m u m size g r o u n d c o n d u c t o r for lead cable
on the equipment. T h i s includes items such as cabi-
sheaths should be N o . 1/0 c o p p e r .
nets, junction b o x e s , outlet b o x e s , controllers, service
raceway, conduit, couplings, fittings, cable armor, lead
sheath and grillwork. In addition, there are switch- Service Conductor Enclosures
gear, transformers, s w i t c h b o a r d frames, m o t o r s , gen-
T h e service conduit g r o u n d i n g w i r e should run
erators, elevators, frames and tracks o f cranes and
directly f r o m it t o the g r o u n d c o n n e c t i o n . T h e interior
portable equipment.
conduit, a r m o r e d cable, o r metal raceways, if well
b o n d e d to the service conduit, should need no addi-
Grounding Methods tional g r o u n d connection.
O n account of the great number o f c o n d u c t o r en-
closure items which w o u l d be part of this subject, all Large Enclosures, Such as Switchgear, Transformers,
cannot be discussed in detail, but general principles Motors, Generators, Cranes and Portable Equipment
can be pointed out and s o m e details given for the
T h e s e in general are g r o u n d e d to structures o r ade-
following.
quate size g r o u n d i n g c o n d u c t o r s connecting them
direct to a g r o u n d bus. S o m e o f these items o f equip-
Equipment and W i r e Raceways ment are referred to in m o r e detail in other parts of
Metal b o x e s , cabinets and fittings, o r non-current- this chapter.
carrying metal parts of other fixed equipment, if Contact Surfaces
metallically c o n n e c t e d to g r o u n d e d cable armor or
metal raceway, are considered to be g r o u n d e d b y If conduits, couplings, o r fittings having protective
such connection. W h e r e the metal enclosure of a coating o f n o n c o n d u c t i n g material, such as enamel,
wiring system is used as part of the protective g r o u n d - are used, such coating should b e t h o r o u g h l y r e m o v e d
ing, the electrical continuity of the enclosure should from threads o f b o t h couplings and conduit and such
be assured, with special attention to obtain secure surface o f fittings w h e r e the conduit o r g r o u n d clamp
fastenings. is secured, in o r d e r to obtain the requisite g o o d elec-
tric c o n n e c t i o n . G r o u n d e d pipes should b e free from
F o r conduit, armored cable, or metal raceways, the rust, scale, etc., at the place o f attachment o f ground
ground connection should be as near as practicable clamps.

22

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
Figure 2.3
Typical grounding system for a building and
heavy electric apparatus in the building.

23

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
In ice houses, packing plants, etc., w h e r e a great Common Grounding Conductor for Circuits,
deal of moisture is present and w h e r e conduits are Metal Raceways, and Equipment
attached to metal cabinets, cutout, pull, o r junction
b o x e s b y means o f l o c k nuts and bushings, these c o n - T h e g r o u n d i n g c o n d u c t o r of an interior wiring sys-
duits should be b o n d e d together. tem m a y also be used as the g r o u n d i n g c o n d u c t o r
for equipment, conduit, and other metal raceways or
Grounding Connectors enclosures for c o n d u c t o r s , including service conduit
or cable sheath and service equipment, p r o v i d e d such
T h e grounding c o n d u c t o r should be attached to the
g r o u n d i n g c o n d u c t o r meets the current-carrying ca-
grounding electrode b y means o f ( 1 ) a suitable bolted
pacity requirements for service raceways, and provided
clamp of cast b r o n z e , brass or plain o r malleable
further, that the s e c o n d a r y distribution circuit supply-
cast iron, o r ( 2 ) a pipe fitting , plug, o r other suit-
ing the interior wiring system has at least o n e addi-
able device, screwed into the pipe o r into the fitting,
tional g r o u n d at the transformer o r elsewhere.
or ( 3 ) by brazing, w e l d i n g o r the equivalent. Soldered
connections shall not be used. W h e r e practicable the
point of attachment should be accessible. GROUNDING OF MISCELLANEOUS
Ground clamps for use o n c o p p e r water tubing and LARGER MOTORS
copper, brass o r lead pipe should preferably be o f
Method of Obtaining Ground Connections
copper and these for use on galvanized o r iron pipe
should preferably be o f galvanized iron to prevent All larger m o t o r frames should be g r o u n d e d with
electrolysis. the g r o u n d i n g c o n d u c t o r equipped with c o p p e r ter-
T h e sheet metal strap type of g r o u n d clamp is not minal brazed thereto, o r with a suitable solderless
considered adequate unless it has a rigid metal base terminal fastened to the m o t o r beneath the head of
seated on the water pipe o r other electrode and the an end shield bolt, o r b y means o f a 5/16 inch (mini-
strap is of such material and dimensions that it is m u m ) bolt tapped into a suitable place o n the m o t o r
not liable to stretch during o r after installation. frame. Soldered terminals should not be used. A
washer should b e used between b o l t head and ter-
Mechanical protection should be p r o v i d e d for the
minal lug. A t t a c h m e n t under head of foot bolt should
ground wire and connections, if it is necessary. I f a
not be used. T h e other end o f the grounding c o n -
ground wire is installed in a steel conduit, it should
ductor should be fastened with suitable clamps or
be connected at each end o f the conduit to reduce the
terminals to the rigid metallic conduit o r t o the nearest
impedance o f the circuit.
available g r o u n d . T a p s from a g r o u n d bus to larger
T h e point of connection of the g r o u n d i n g c o n d u c t o r m o t o r s and generators m a y b e c o n n e c t e d directly to
to interior metal raceways, cable a r m o r and the like the bed plate. A l s o refer to National Electrical Code.
should be as near as practicable to the point of power
supply.
Size of Grounding Conductors
T h e grounding c o n d u c t o r , b o n d , o r b o n d i n g j u m p e r
should be attached to conduits, cabinets, equipment
In the case of exceptionally large high-current-rated
and the like, b y means o f suitable lugs, pressure c o n -
rotating machines, grounding conductors of 500 to 750
nectors, clamps o r other suitable means. S o l d e r e d c o n -
M C M may be appropriately used. Even larger cross
nections shall not be used.
sections occasionally find application.

Size Grounding Conductors


The minimum allowable grounding conductor size to PORTABLE ELECTRIC EQUIPMENT
be used under any circumstances is prescribed in article
Definition of Portable Electric Equipment
250 of the National Electrical Code. Under the most
severe grounding system duty in which a single ground- Portable electric equipment is electric equipment
ing conductor must alone meet the full duty, a somewhat which m a y be m o v e d from place to place and which
larger size should be used in accordance with Table 2.1. is supplied with p o w e r through a flexible cable. T h i s
cable m a y be permanently c o n n e c t e d at each end or
T A B L E 2.1 m a y be c o n n e c t e d through a suitable plug o r discon-
COPPER W I R E SIZE OF G R O U N D I N G CON- necting device. Portable electric equipment can be
DUCTOR FOR V A R I O U S SIZES OF P O W E R further subdivided into g r o u p s based o n operating
CONDUCTORS voltage and p o w e r requirements.
A W G Size of Size of
Power Conductor Grounding Conductor
Portable Equipment Above 600 Volts
6 o r smaller 8 stranded
4 6 Portable equipment operating at line voltages above
2 4 600 volts should be supplied through a suitable port-
1 2 able cable permanently connected at both ends. The
0 0 complete equipment including any associated housing
00 0 or structure should be grounded through a ground-
000 00 ing wire or wires in this cable equal in current-
0000 or larger 0000 carrying capacity to the largest line conductor.

24

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
It is desirable that such equipment b e operated from so as to m a k e contact with any o f the line contacts
a w y e - c o n n e c t e d system with its neutral g r o u n d e d in the receptacle. W h e n a plug is inserted in a recep-
through a resistor w h i c h limits ground-fault current tacle, the g r o u n d contact must engage before any of
to 50 amperes o r less. Suitable ground-fault relaying the line contacts make contact.
should be provided .

Maintenance
P o r t a b l e E q u i p m e n t 600 V o l t s o r L e s s
G r o u n d i n g o f portable electric equipment can be
( a ) Portable equipment operating at line v o l t a g e s
a hazard instead o f a safeguard if not properly in-
of 600 volts o r less, e x c e p t for single-phase circuits
stalled and maintained. T h e following precautions
of 150 volts and b e l o w rated not o v e r 15 amperes,
should be o b s e r v e d :
should be g r o u n d e d through a separate g r o u n d i n g
wire or wires (either bare or colored green) in the con- ( a ) Care must b e taken that o n l y the green c o n -
necting cable equal in current-carrying capacity to the d u c t o r is c o n n e c t e d to the parts to be grounded.
largest line conductor. If the cable is not permanently ( A s specified b y National Electrical C o d e )
connected at each end, grounding should be through
separate grounding contacts in the power plug and re- ( b ) Portable t o o l s should b e c h e c k e d for proper
g r o u n d i n g - c o n d u c t o r c o n n e c t i o n s each time they
ceptacle.
are passed to the operator.
( b ) Portable equipment operating from a single-
phase circuit at 150 volts and b e l o w and rated not ( c ) A l l portable cables and their associated plug
over 15 amperes should be g r o u n d e d through a sepa- equipment should be inspected at regular inter-
rate grounding wire (colored green) in the connecting vals.
cable equal in current-carrying capacity to the line con-
ductors. Grounding should be through separate ground- BIBLIOGRAPHY
ing contacts in the plug and receptacle. In new instal-
lations, receptacles of the type having two parallel line 1. Principles and Practices in Grounding — EEI
contacts and one grounding contact should be used ex- Publication N o . D - 9 , 1936.
clusively. It is desirable that existing t w o - c o n t a c t 2. Bureau o f Standards — T e c h n o l o g i c Paper 108-
receptacles be replaced with the a b o v e g r o u n d i n g re- G r o u n d C o n n e c t i o n s for Electric Systems.
ceptacles w h e r e v e r practicable, but until this is d o n e ,
an adapter ( n o w available) can be used to convert the 3. National Electrical C o d e , National Fire Protection
two-terminal to a three-terminal grounding-type re- A s s o c i a t i o n , B o s t o n 10, M a s s .
ceptacle.
4. National Electrical Safety C o d e , National Bureau
( c ) N o t e that portable lamps with n o n - c o n d u c t i n g of Standards, W a s h i n g t o n 25, D . C .
guards and sockets need not be g r o u n d e d . Special c o n -
5. National Bureau o f Standards H a n d b o o k H 4 3 .
sideration must also b e given t o certain equipment,
such as soldering irons, w h e r e g r o u n d i n g m a y c o n - 6. E n g i n e e r i n g Practice — G r o u n d i n g Systems for
stitute a hazard. Generating Stations and Substations G E U - 2 4 D . —
General E l e c t r i c C o .
General Comments
7. E n g i n e e r i n g Standards. E1P, E. I. DuPont de
( a ) A l t h o u g h neutral c o n d u c t o r s are g r o u n d e d at Nemours Co.
the source, they should never be used for equipment
8. S o m e Fundamentals o f E q u i p m e n t G r o u n d i n g Cir-
grounding.
cuit Design, R . H . Kaufmann, A I E E Trans., Appl.
( b ) Equipment g r o u n d i n g c o n d u c t o r s if insulated, & Indus., N o v . 1954, pgs. 227-31.
should be identified with green c o l o r c o d e as speci-
9. I r o n Conduit I m p e d a n c e Effects in G r o u n d Circuit
fied b y National Electrical C o d e .
Systems, A . J. Bisson and E. A . Rochau, A I E E
( c ) It is assumed that an adequate g r o u n d c o n n e c - Trans., Appl. & Indus., V o l . 73, July, 1954, pgs. 104-6.
tion will b e available at the fixed end o r receptacle
10. Voltage Gradients Through the Ground Under Fault
of a portable g r o u n d i n g cable. In general, this should
Conditions, A I E E Committee Report, A I E E Trans-
consist of a direct c o n n e c t i o n to the steel frame of a
actions, P o w e r Apparatus and Systems, October 1958,
building o r other structure w h i c h has been suitably
pages 669-692.
g r o u n d e d o r to the g r o u n d bus of the building. If
such a g r o u n d c o n n e c t i o n is not available, it m a y be 11. Impedance and Inductive Voltage Measurements on
necesary to carry a separate g r o u n d i n g c o n d u c t o r Iron Conductors, W . F. Mackenzie, A I E E Transac-
from the point of c o n n e c t i o n o f the portable cable tions, V o l . 73, 1954, Part I, page 577.
with the supply line b a c k t o a suitable g r o u n d point.
12. Application Guide on Methods of Substation Ground-
( d ) T h e g r o u n d i n g contact in a c o n n e c t i o n plug ing, A I E E Committee report, A I E E Transactions.
should be s o designed that it can never be inserted V o l . 73, 1954, Part I I I A , page 271.

25

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
CHAPTER III

STATIC A N D LIGHTNING PROTECTION GROUNDING

— STATIC GROUNDING —

PURPOSE OF STATIC GROUNDING If losses such as cited a b o v e can b e avoided by


proper static control, the expenditure required to
Introduction
secure this protection is g o o d insurance.
Industrial plants, c o m m e r c i a l establishments and
A n additional need for static control m a y be for
institutions handling solvents, dusty materials, or
i m p r o v e m e n t in p r o d u c t quality. F o r example, static
other flammable products, often have a potential
in grinding operations prevents grinding to a fine
hazardous operation condition because o f static ac-
degree. Static in certain textile operations causes
cumulating on equipment, on materials being handled
fibers to stand on end instead of lying flat which
or even on operating personnel.
often affects the quality o f the material.
T h e discharge of a static charge to g r o u n d or to
other equipment in the presence of flammable or ex- Static charges on materials handled b y chutes or
plosive materials is often the cause of fires and ex- ducts have been k n o w n to c l o g them b y clinging to
plosions which result in the loss of m a n y lives each the inside of the chutes and ducts.
year, and with an a c c o m p a n y i n g financial loss of
millions of dollars. F U N D A M E N T A L CAUSES OF STATIC

T h e simple expedient of g r o u n d i n g equipment is T h e o r y of Static


not always the solution of the p r o b l e m ; therefore, it A difference in potential will exist between t w o
is necessary to study each installation in order that materials or substances when one holds a positive
an adequate method of control m a y be selected. charge and the other holds a negative charge. T h e s e
T h i s guide has been prepared to set forth s o m e of charges accumulate w h e n dissimilar substances, one
the considerations that must be taken into account of w h i c h must be in insulator, are brought into c o n -
in the study of static p r o b l e m s . tact with each other. U n d e r this condition the nega-
tive electrons will migrate from the surface of one
T h e material contained in this chapter is not neces-
substance to the surface o f the s e c o n d substance, leav-
sarily new, but has been gleaned from many excellent
ing the positive ions on the first substance. Simply 1

papers and booklets on the subject and due credit


stated, then, o n e substance has a positive charge and
is given the authors and c o m m i t t e e s in the biblio-
the s e c o n d has a negative charge. U p o n separation of
graphy at the end o f this chapter.
t w o such oppositely c h a r g e d materials, a static dis-
Excerpts of these articles are included in this report charge m a y take place.
to place in the hands o f the electrical engineer charged
with protecting life and p r o p e r t y from the hazard o f
Conditions Affecting the Production of Static Charges
static sufficient information to r e c o g n i z e the possibili-
ties of static generation and s o m e means that m a y T h e possibility of p r o d u c i n g electrification (static)
be effective in protecting against it. and the degree that it will be p r o d u c e d will depend
mainly o n :
1. Material characteristics
Basic Objectives
2. Speed of separation
Protection of human life is the first o b j e c t i v e in
attempting to control static charges. Besides the danger 3. A r e a in contact
to lives because o f explosions o r fires that m a y result 4. T h e m o t i o n b e t w e e n substances
from a static discharge, there is also the danger o f
5. A t m o s p h e r i c c o n d i t i o n s
a person b e c o m i n g startled if suddenly subjected to
a static shock, w h i c h m a y result in falling o r acci-
dentally c o m i n g into contact with s o m e m o v i n g equip- Material Characteristics
ment. It has been previously stated that o n e of the mate-
rials o r substances will have insulating properties to
T h e second aim in eliminating o r controlling static
at least s o m e degree. T h e physical forms m a y be
is to prevent the loss o f :
solids, liquids o r gases; the solids m a y be in the form
1. Capital investment in buildings and equipment of sheeting, rods, etc., o r m a y be b r o k e n up into
2. Operating funds in stored materials particles that f o r m a dust.

3. Profits because of the loss of production


1
Numbers refer to numbered references in bibliography at end of
chapter.

26

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
T h e degree o f electrostatic charge that m a y exist T A B L E 3.1
between t w o materials will b e proportional t o the
difference in their dielectric constants. A l s o , the p o s i - Range of Static Voltages
tive charge will usually s h o w up o n the material Produced by Various Processes
having the highest dielectric constant. Type of Equipment Voltage Range Observed
Belted D r i v e s 60,000 — 100,000
Speed of Separation Fabric H a n d l i n g 15,000— 80,000
Paper M a c h i n e s 5,000 —100,000
A s the speed o f separation of t w o o p p o s i t e l y c h a r g e d Tank Trucks up to 25,000
substances is increased, the greater the chance for Belt C o n v e y o r s ( G r a i n ) up to 45,000
i m p o u n d i n g the charges o n the materials, thus increas-
ing the potential differences b e t w e e n them. F r o m the table o f sparking distances given in T a b l e
3.2 it can be seen that even v o l t a g e s o f 25,000 volts
Effect of Motion m a y j u m p o v e r o n e inch, such a spark could readily
release e n o u g h e n e r g y to ignite flammable mixtures.
W h i l e friction is not necessarily the cause o f static
charges, it d o e s have the effect o f increasing the F o r a c o m p l e t e discussion o n the explosive limits
degree o f electrification; this m a y be attributed t o of various gas and liquid mixtures as well as the
the m o t i o n permitting m o r e particles o f o n e o f the spark e n e r g y required to ignite such mixtures, refer-
substances c o m i n g into c o n t a c t with the other sub- ence is m a d e to the article "Industrial Fires and
stance; this is particularly true in the flow o f liquids E x p l o s i o n s from Electrostatic O r i g i n " and the b o o k
4

in a pipe w h e r e a turbulent c o n d i t i o n m a y exist. " C o m b u s t i o n , Flames and E x p l o s i o n s " .


6

Liquids sprayed o r expelled f r o m a n o z z l e , particu-


larly if they impinge o n a surface, often p r o d u c e high- T A B L E 3.2
voltage charges.
Sparking Distances in Air
Materials in a tank m a y accumulate static charges for Various Voltages Between Needle Points 3

because o f agitation o f the liquid either purposely ( R M S Values)


or because o f tank m o t i o n .
Distance Distance
Volts Inches Centimeter Volts Inches Centimeter
A n example o f m o t i o n p r o d u c i n g alternate contact
5,000 0.255 0.57 60,000 4.65 11.8
and separation o f materials is the passing o f a belt
10,000 0.470 1.19 70,000 5.85 14.9
o v e r a pulley, and as p r e v i o u s l y pointed out the higher
15,000 0.725 1.84 80,000 7.10 18.0
the speed the oftener these alternations o c c u r and the
20,000 1.000 2.54 90,000 8.35 21.2
greater the static charge on the belt. T h e same prin-
25,000 1.300 3.30 100,000 9.60 24.4
ciple applies to any sheeting passing o v e r rolls such
30,000 1.625 4.10 110,000 10.75 27.3
as in the manufacture and p r o c e s s i n g o f rubber m a -
terials, papers, textiles, etc. R u b b e r t i r e s rolling o v e r
2 35,000 2,000 5.10 120,000 11.85 30.1
streets and r o a d s p r o d u c e the same effect and m a y 40,000 2.450 6.20 130,000 12.95 32.9
account for static charges o n automobiles, tank 45,000 2.95 7.50 140,000 13.95 35.4
trucks, etc. 50,000 3.55 9.00 150,000 15.00 38.1

Area in Contact
METHODS OF TESTING FOR STATIC 6

T h e area of substances in contact has a direct


bearing on the degree o f electrification because of Gold-Leaf Electroscope
the greater ease o f transmitting positive ions and nega-
tive electrons f r o m o n e substance to the other. T h e familiar gold-leaf e l e c t r o s c o p e because o f its
delicate construction is primarily a laboratory instru-
m e n t ; but, if handled with care, it m a y be used to
Atmospheric Conditions
detect static charges. Its advantage is that because
T e m p e r a t u r e and humidity conditions as related to of its l o w capacity, it d r a w s practically n o spark upon
production o f static are p r o b a b l y w e l l k n o w n to e v e r y - c h a r g e o r discharge and thus m a y b e used in locations
one because o f personal d i s c o m f o r t experienced in w h e r e flammable substances m a y b e present. T h i s de-
touching a metal o b j e c t o n a c o l d , d r y day after a c - vice, of c o u r s e , w o u l d o n l y indicate the presence of
cumulating a c h a r g e b y w a l k i n g across a rug or static and not its magnitude.
c o m i n g into contact with s o m e other insulating
material. T h i s s h o w s clearly the hazard that can exist
in an operation that m a y require c o n t r o l l e d tempera- Electrostatic Voltmeter
ture and humidity conditions.
A s static charges are characterized b y high voltage
and l o w e n e r g y , instruments that have practically
Voltages Possible no current drain must be used for voltage measure-
ments. T h e electrostatic v o l t m e t e r is such an instru-
V o l t a g e s that have been o b s e r v e d in a f e w indus- m e n t and, w h i l e it m a y n o t have high accuracy
tries o r have been created in tests are s h o w n in characteristics, it is sufficiently accurate for voltage
Table 3.1. determination o f static charges.

27

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
N e o n T u b e Tester Such an instrument is listed b y U n d e r w r i t e r s ' L a b o r a -
tories for Class I G r o u p s " C " and " D " hazardous
This device is v e r y inexpensive and can be carried
locations.
readily so occasional c h e c k s for static can be m a d e ;
however, it m e r e l y indicates the presence of static
H A Z A R D S IN V A R I O U S T Y P E S OF
and contains no instrument to indicate the v o l t a g e
INDUSTRIES
that m a y exist.
Industries
V a c u u m T u b e V o l t m e t e r and See T a b l e 3.3 for a summation o f the following data.
Vacuum Tube Electrometer
A v i a t i o n Industry. Several fatal e x p l o s i o n s and fires
T h e s e instruments m a y be used to detect the pres- have been the result of liquid m o v e m e n t ( g a s o l i n e )
ence of static electricity but they should have v e r y in this industry. T h e loading o f airships with fuel
high input impedance s o as to limit current drain. is extremely hazardous, and the possibility of static
Instruments are available with input impedances of discharge is always guarded against b y the use of
the order of 1 0 o h m s . If a c o m m e r c i a l type of in-
1 5

g r o u n d networks, etc.
strument is not available an electron tube detector
as described in the next paragraph m a y be c o n - Chemical Industry. T h e m o v e m e n t o f liquids and
structed. gases within the p r o c e s s itself can be responsible for
the creation of electric charges. T h e s e may accumu-
Electron T u b e Detector late o n u n g r o u n d e d c o n d u c t i n g surfaces in sufficient
This detector s h o w n in Figure 3.1 operates in the quantity to result in a static spark to adjacent c o n -
following manner: T h e tube current is adjusted in ducting structures. In the presence of highly c o m -
the plate circuit to s o m e value near the mid-point bustible material o r e x p l o s i v e atmospheres, such
of the characteristic grid voltage—plate current spark discharges are to be a v o i d e d by appropriate
curve b y means of the " C " battery. T h e sensitivity means such as leakage circuits to ground.
of the circuit is determined b y the grid leak, " R " .
Coal Industry. M a n y mine e x p l o s i o n s have been at-
tributed to the accumulation of coal dust and the
m o v e m e n t of particles. M o r e than ordinary precau-
TUBE TYPE 164-G
PROBE k OUTPUT tions against possibility of static discharge spark must
] 3 MlLLlAMPERES
be taken to avoid u n d e r g r o u n d explosions.

B= 4 5 VOLTS
F l o u r and Grain Industry. Material m o v e m e n t and
R =5- MEGOHMS the machinery of manufacture can be responsible for
charge accumulation and resulting static discharge.
Fine particles of grain dust suspended in the air afford
an excellent source o f explosive.

C s 7.5 V O L T S A s |.5 V O L T S G a s Industry. M o v e m e n t of the gas itself in s o m e


cases m a y cause static accumulation and spark. W h e n
this o c c u r s in the presence o f volatilized atmosphere,
STATIC DETECTOR explosions o c c u r .
Figure 3.1 Paint Industry. M o v e m e n t of liquids and process
One line diagram o f a static ground detector. in the manufacture m a y cause hazardous conditions
Usually 5 m e g o h m s give a satisfactory result. T h e due to the static electricity discharge.
lead marked " p r o b e " m a y consist o f a shielded lead
P a p e r and Printing Industries. T h e m o v e m e n t of
connected to a tinsel bar about 3 o r 4 inches long,
the paper itself over the various rolls and the ma-
or just the bare end of the wire leading to the grid
chinery of manufacture tends t o cause static voltages.
of the tube: If the p r o b e is b r o u g h t near a substance
that held a positive charge, this charge w o u l d be re- Refining Industry. M o v e m e n t o f gas and liquids
flected on the grid o f the tube and an increase in and the spraying o f caustic solutions in tanks and
plate current w o u l d result, likewise if the p r o b e w a s acid bubbling has caused static discharges in m a n y
brought near a substance h o l d i n g a negative charge cases. T h e surrounding atmosphere due to the p r o c -
a decrease in plate current w o u l d b e indicated. A n ess makes it necessary that a m a x i m u m amount of
indicating milliammeter is usually used in this cir- effort be directed t o w a r d reducing the hazard of
cuit although possibly a graphic meter c o u l d b e used, static electricity.
which w o u l d permit r e c o r d i n g the relative intensities
P o w d e r Industry. T h e v e r y nature of manufacture
even though observers m a y n o t b e present.
and the possibility o f contaminated atmosphere make
Industrial Static I n d i c a t o r possible m a n y hazards. T h e m o v e m e n t o f material
and the manufacturing p r o c e s s can b e the s o u r c e of
There is c o m m e r c i a l l y available an instrument that static v o l t a g e s .
detects the presence of static charges, gives an alarm
both visual and audible. It also contains an instru- R u b b e r Industry. T h e various rolls and presses in
ment to indicate the magnitude o f the charge. T h i s the manufacturing p r o c e s s with the resulting m o v e -
device is portable o r m a y b e installed in a permanent ment o f material often cause static accumulation.
location with an antenna system installed in the T e x t i l e Industry. T h i s industry offers possible c o n -
operating areas to pick up a signal if static is present. trol of hazardous conditions by humidity, but the

28

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
presence o f lint in the air is d a n g e r o u s . Static dis- Humidity Control
charges from l o o m s , belt drives, and other m a c h i n e r y
have caused fires in m a n y cases. W h e r e high humidity d o e s not affect the material,
this affords o n e o f the best w a y s o f c o n t r o l l i n g static.
Steam ejected into the area, especially near the point
Institutions and Commercial Establishments w h e r e static is accumulating, is perhaps the best w a y
of supplying additional humidification. T h e minimum
Hospitals. M i x t u r e s o f air and certain anesthetics
value o f relative humidity that can b e tolerated is
are flammable o r explosive. O p e r a t i n g r o o m s should
difficult to determine and will v a r y with the process
constantly guard against the possibility o f static dis-
and surrounding c o n d i t i o n s ; h o w e v e r , it is believed
charges w h i c h w o u l d immediately ignite the surround-
that w h e r e the relative humidity is maintained in the
ing atmosphere.
range o f 60 percent, static accumulations are not
Dry Cleaning. T h e m o v e m e n t o f garments, flam- likely to reach d a n g e r o u s p r o p o r t i o n s . W h e r e the
mable liquids causes an extended blanket o f h i g h l y p r o c e s s m a y b e affected b y humidity and the area
flammable v a p o r s . Static sparks are easily generated m a y even be air-conditioned for p r o c e s s c o n t r o l , then
b y this same m o v e m e n t o f the garment. o n e o f the f o l l o w i n g m e t h o d s o f static c o n t r o l m a y
be c o n s i d e r e d .
Offices — Business machines, particularly those
handling materials such as papers often accumulate
Static Collectors or Electrostatic Induction Ionization 7

static charges that m a y interfere with the operation


of the machine. Metallic c o m b s o r bars o f tinsel are sometimes
effective if placed v e r y c l o s e t o the sheeting at the
TABLE 3.3 point o f greatest accumulation. In the case o f tinsel
it m a y e v e n b e p l a c e d in c o n t a c t w i t h the material
Processes W h i c h Are Likely to
assuming that the material w o u l d not b e affected b y
Product Static in Various Industries such contact.
Material Movement Machinery Process Neutralizers
Industry Solids Liquids Gases
Aviation X
Neutralizers are n o w available c o m m e r c i a l l y w h i c h
Chemical X X X ionize the air w h e n placed near the m o v i n g material.
Coal X T h e s e neutralizers either a c c o m p l i s h ionization b y the
Flour & Grain X X use o f radioactive m a t e r i a l s w h i c h emit alpha par-
7

Gas X X ticles o r b y h i g h - v o l t a g e stressing o f the air; in the


Paint X X latter case t w o types are e m p l o y e d , the first requires
Paper & Printing X X a g r o u n d b a r in c l o s e p r o x i m i t y t o the material, the
Refining X X X s e c o n d d o e s n o t e m p l o y such a g r o u n d bar and
Powder X X X operates at a higher potential. In the application o f
Rubber X X X neutralizers, care must b e taken to p r o t e c t operating
Textiles X X and maintenance personnel f r o m h i g h - v o l t a g e circuits
D r y Cleaning X X o r f r o m harmful radiation in the case o f radioactive
Service Stations X neutralizers.
Hospitals X
Conductive Belts
Offices X
M o s t belts are c o n s t r u c t e d o f insulating materials.
T h e s e , pressed into c o n t a c t with pulleys, constitute
METHODS OF STATIC CONTROL —
o n e o f the m o s t prolific generators o f static charges.
GROUNDING AND BONDING
In locations w h e r e such c h a r g e s are a real hazard,
M a n y static p r o b l e m s can b e s o l v e d b y b o n d i n g consideration should b e given to direct drives rather
the various parts o f the equipment t o g e t h e r and than belted drives.
g r o u n d i n g the entire system. N o attempt will b e
W h e r e it is necessary to use belted drives considera-
made here to describe in detail h o w and w h e r e such
tion should b e given t o the use o f c o n d u c t i v e rubber
b o n d i n g and g r o u n d i n g c o n n e c t i o n s s h o u l d b e m a d e ,
belts, w h i c h have the ability to drain off at least a
but reference is m a d e t o the National Fire P r o t e c -
certain amount o f static charges.
tion A s s o c i a t i o n ' s bulletin "Static E l e c t r i c i t y " , for
6

s o m e detailed m e t h o d s . T h e r e s e e m s to b e n o industry-wide standard as


to the m a x i m u m resistance that a belt m a y have and
G r o u n d i n g , h o w e v e r , is n o t a cure-all; f o r e x a m p l e ,
still b e c o n s i d e r e d adequate from a static dissipation
if the material b e i n g p r o c e s s e d is rather b u l k y and
standpoint. T h e National Bureau o f Standards Bulle-
has high dielectric characteristics, the c h a r g e o n the
tin C - 4 3 8 gives fundamental principles to determine
10

upper portion o f the material will b e v e r y effectively


the resistivity o f material w h i c h can be related to
insulated from g r o u n d and m a y result in a spark
its ability to dissipate static at a satisfactory rate and
discharge. E v e n films o r o t h e r sheet materials, either
the f o l l o w i n g e x a m p l e is given.
because o f the area in c o n t a c t o r the s p e e d o f separa-
tion, accumulate c h a r g e s that c a n n o t b e drained off ' T n the case o f an insulated m a c h i n e driven b y a
adequately b y g r o u n d i n g and the f o l l o w i n g m e t h o d s belt o f w i d t h W centimeters, running at a linear
o f c o n t r o l are often utilized. v e l o c i t y o f V centimeters per s e c o n d , the belt m a y

29

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
be assumed charged to the m a x i m u m charge density S h o e testers are available for determining the resist-
of 2.6 x 1 0 c o u l o m b per square centimeter and the
-9
ance while being w o r n . Such testers are essentially
rate of production is equivalent to 2.6 x 10* W V 9
direct reading ohmeters with internal resistors to limit
c o u l o m b s per second. If the leakage to g r o u n d is to the short-circuit current to 0.5 milliampere.
carry this current with a potential difference w h i c h
is less than the minimum sparking potential of 350 W h e r e c o n d u c t i v e floors and shoes are required, the
volts, the resistance must be less than R = 3 5 0 / ( 2 . 6 resistance b e t w e e n the wearer and g r o u n d must not
x 1 0 " W V ) == 1.3 x 1 0 " / W V o h m s . If the width,
9
exceed o n e million o h m s , w h i c h is the total resistance
W , happens to be 10 centimeters and the velocity, of conductive shoes o n a person plus the resistance
V , 1000 centimeters per s e c o n d , the resistance should of the floor.
be less than 1.3 x 10 o h m s (13 m e g o h m s ) . "
7

O n e manufacturer o f belts considers that a belt Special P r e c a u t i o n s


which s h o w s a 10 m e g o h m resistance when measured
In addition to the use o f c o n d u c t i v e floors and
on an S A inch section will have sufficient static
J

shoes, other controls m a y b e considered such as:


properties to make the belt safe throughout its life,
some feel that a m u c h higher resistance will still 1. P r o v i d i n g wearing apparel with l o w static pro-
permit dissipating static satisfactorily; h o w e v e r , it is ducing qualities.
desirable to keep the resistance as l o w as possible
2. Establishing rigid operating procedures.
to provide a g o o d margin of safety.
3. W h e r e c o n d u c t i v e floor is not used throughout
A v e r y important consideration in applying c o n - an area, c o n d u c t i v e rubber mats m a y be c o n -
ductive rubber belts is to be sure that b o t h the drive sidered.
and the equipment are well g r o u n d e d .
Hospital operating r o o m s (because of the extreme
O n e method for testing belts is to place t w o ^ - i n c h hazard o f anesthetic agents, and the possibility of
diameter electrodes o n the belt & A inches apart. T h e
T
creating static from n o z z l e s , operators with improper
electrodes should be moistened before placing o n the attire, and other causes) utilize m o s t of the above
belt and each should have 3 p o u n d s per square inch techniques. T h e subject of protection is well c o v e r e d
pressure applied. T h e resistance can then be measured in published bulletins and the details will not be
8

b y means of a standard 500-volt m e g o h m m e t c r . c o v e r e d here. In industrial areas with extremely


hazardous conditions it m a y be well to consider these
Belts other than o f the conductive type can b e recommendations.
made safe b y the application of certain c o n d u c t i v e
solutions, s o m e o f w h i c h are available c o m m e r c i a l l y .
T h e National Fire Protection A s s o c i a t i o n lists a n u m - Follow-Up
ber o f solutions in their bulletin "Static E l e c t r i c i t y " . 6

L i k e any piece o f equipment, static control devices


are no better than the maintenance that they receive,
Conductive F l o o r s therefore, it is imperative that regularly scheduled in-
spections should be m a d e t o :
W h e r e extremely hazardous operating conditions
exist such as in the production o f s o m e explosives, 1. Determine if all b o n d i n g and g r o u n d i n g c o n n e c -
or those involving gases o r certain solvent-air m i x - tions are intact.
tures, the use o f conductive flooring m a y be required.
W h e r e such flooring is required, it must b e of n o n - 2. Ascertain the resistance t o g r o u n d . T h i s m a y be
sparking materials, such as c o n d u c t i v e rubber, lead found b y the use o f c o m m e r c i a l l y available o h m -
or other conductive c o m p o u n d s . meters. T h e resistance to g r o u n d should, if at all
possible, b e limited to o n e o h m .
T h e electric resistance, as measured between g r o u n d
3. E x a m i n e static neutralizers to b e sure they are
and a five-pound electrode in direct contact with five
in the correct position and if of the high-voltage
square inches o f floor area, must not e x c e e d 250,000
type that they are energized.
ohms. T h e electrode should be m o v e d about the floor
to determine if any high resistance areas exist. 4. T e s t belts to see if they have lost their c o n d u c t -
ing characteristics.
If w a x e s or other floor preservants are used, they
should have conductive qualities. C o n d u c t i v e floors 5. T a k e resistance measurements of conductive
m a y increase in resistance with age, therefore, should flooring.
be tested at regular intervals.
6. T a k e instrument readings to determine if static
charges are accumulating, either because o f the
loss of o n e o f the static control devices o r because
Conductive Shoes
of a change in operating conditions such as a
W h e n conductive flooring is used operators o r others change in machine speed, o r the addition o f
entering the area must wear conductive, non-sparking material-handling equipment or change in the
shoes. Their resistance should be c h e c k e d at regular materials w h i c h m a y have different character-
intervals or before entering the w o r k area. istics.

30

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
— LIGHTNING PROTECTION GROUNDING —

NATURE OF LIGHTNING type of d a m a g e is not within the s c o p e o f this chapter


Lightning is an electric discharge between clouds except as g r o u n d i n g is involved. T h i s portion of the
o r between c l o u d s and earth. Charges o f o n e polarity subject is discussed under PROTECTION OF
are accumulated in the c l o u d s , and of the opposite P O W E R STATIONS A N D SUBSTATIONS.
polarity in the earth. W h e n the charge increases to the It is not possible to positively protect a structure
point that the insulation b e t w e e n can n o l o n g e r c o n - against d a m a g e f r o m direct stroke except to c o m -
tain it, a discharge takes place. T h i s discharge is pletely e n c l o s e it with metal. T h e extent to which
evidenced b y a flow o f current, usually great in lightning protection should b e provided is governed
magnitude, but extremely short in time. b y w e i g h i n g the c o s t o f protection against the possible
consequences o f b e i n g struck. T h e factors to be c o n -
D a m a g e to buildings and structures is the result
sidered are:
of heat and mechanical forces p r o d u c e d b y the pass-
age of current through resistance in the path of dis- 1. F r e q u e n c y and severity o f thunderstorms.

charge. A l t h o u g h the discharge takes place at the 2. V a l u e and nature o f structure or content.
point where the potential difference exceeds the 3. Personnel hazards.
dielectric strength o f the insulation, which implies
4. Consequential loss, such as loss of production,
l o w resistance relative t o other paths, it is not un-
salaries o f w o r k e r s , d a m a g e suits and other in-
common for the current to f o l l o w a path of high direct losses.
resistance. T h i s m a y b e a tree, a m a s o n r y structure,
5. Effect o n insurance premiums.
o r a porcelain insulator. Obviously, damage due to
direct stroke can b e minimized b y p r o v i d i n g a direct T h e a b o v e factors are listed primarily to call atten-
tion to their importance. N o general conclusions can
path o f l o w resistance to earth.
be d r a w n as to the relative importance o f each o r
L i g h t n i n g can cause d a m a g e to structures b y direct to the necessity for o r the extent of lightning protec-
stroke and to equipment b y surges c o m i n g in o v e r tion for any given c o m b i n a t i o n of conditions. A s a
e x p o s e d p o w e r lines. Surges m a y be the result of matter o f interest, a m a p s h o w i n g the frequency of
direct strokes to the line at s o m e distance away, or thunderstorms for various areas o f the United States
they m a y b e electrostatically induced voltages. is s h o w n in F i g u r e 3.2. It should b e noted, h o w e v e r ,
that the s e v e n t y o f storms is m u c h greater in s o m e
THE NEED FOR PROTECTION local areas than in others and, therefore, the need
D a m a g e t o structures and equipment due to surge for protection is not necessarily in direct proportion
effect is a subject in itself and protection against this t o the frequency.

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
EQUIPMENT AND STRUCTURES T H A T on top of the structure should have an earth con-
SHOULD BE CONSIDERED FOR nection. P r o p e r l y m a d e c o n n e c t i o n s to earth are an
PROTECTION essential feature o f a lightning r o d system for p r o -
tection of buildings. ( S e e Chapter I V . ) It is m o r e
T h e nature o f buildings and their content are im- important to p r o v i d e ample distribution o f metallic
portant in deciding whether lightning protection is contacts in the earth than to p r o v i d e low-resistance
desirable. S o m e of the factors w h i c h should be c o n - connections. L o w - r e s i s t a n c e c o n n e c t i o n s are desirable,
sidered are as f o l l o w s : h o w e v e r , and should be p r o v i d e d w h e r e practicable.
Earth connections should be m a d e at uniform inter-
1. All-metal structures.
vals about the structure, avoiding as m u c h as possible
2. Metal-frame buildings with non-metallic facings. the g r o u p i n g of c o n n e c t i o n s on o n e side. E l e c t r o d e s
should be at least t w o feet a w a y from and should
3. Buildings m a d e entirely o f n o n - c o n d u c t i n g ma-
extend b e l o w building foundations. T h e y should make
terials such as w o o d , stone, brick and tile.
contact with the earth from the surface d o w n w a r d
4. Buildings of historical value. to avoid flashing at the surface.
5. Buildings containing combustible o r explosive
Interior metal parts of buildings o r structures
material.
should b e g r o u n d e d independently, and if they are
6. T a n k s and tank farms. within six feet of metallic r o o f s , walls o r c o n d u c t o r s
7. Transmission lines. running d o w n f r o m the terminals o n t o p o f the struc-
8. P o w e r plants, substations, and water pumping ture, they should be securely c o n n e c t e d thereto.
stations. T e r m i n a l s projecting a b o v e the structure should
be o f ample length to bring the t o p point at least
Metal buildings and structures offer a v e r y satis-
10 inches a b o v e the o b j e c t to be protected. In m a n y
factory path to earth and require little in the w a y
cases a greater height is desirable. Experiments have
of additional protection. Metal-frame buildings with
indicated that a vertical c o n d u c t o r , o r point, will
non-metallic facings require m o r e extensive measures.
divert to itself direct hits w h i c h m i g h t otherwise fall
Buildings m a d e entirely o f n o n - c o n d u c t i n g materials
within a c o n e shaped space, of w h i c h the apex is the
require complete lightning protective systems.
point and the base is a circle w h o s e radius is approxi-
In special cases buildings m a y have historical value mately equal to the height o f the point.
out of all proportion to the intrinsic value and m a y
justify extensive protection systems. P o w e r stations,
PROTECTION OF P O W E R STATIONS
substations, and water p u m p i n g stations p r o v i d i n g
AND SUBSTATIONS
extremely important functions to outside facilities
may demand protective measures far m o r e extensive Station protection against direct stroke should in-
than w o u l d normally be warranted b y the value o f the clude effective shielding of the station structure itself
structure. B y the same token structures containing and at least the first 2000 to 2500 feet of e x p o s e d lines
combustible or explosive material, liquids and gases adjacent to the station. T h i s shielding m a y take the
of a toxic nature o r otherwise harmful to personnel f o r m o f masts or extensions o f the steel structure t o
or property if allowed to escape f r o m their confining provide a p r o p e r c o n e o f protection to apparatus and
walls, m a y justify extensive protective systems. circuits within the station area. T h e s e extensions m a y
be arranged to also support the station end o f the
overhead g r o u n d wires carried o v e r the first 2000 feet
REQUIREMENTS FOR GOOD PROTECTION of line. T h e height of a single mast o r single ground
wire shielding is usually based o n a shielding angle
T h e fundamental theory of lightning protection o f
of 30 degrees. H o w e v e r , w h e n t w o o r m o r e masts
structures is t o p r o v i d e means b y w h i c h a discharge
or g r o u n d wires are used that part of the shielding
m a y enter or leave the earth without passing t h r o u g h
angle that lies between masts or g r o u n d wires is
paths of high resistance. Such a condition is usually
increased to 60 degrees. T h i s p r o v i d e s an unsym-
met b y g r o u n d e d metal o r m e t a l - c o v e r e d structures,
metrical c o n e o r w e d g e w h o s e base is equal to the
and is often met b y g r o u n d e d steel-frame structures.
height o n the outside areas and t o about twice the
Suitable protection is nearly always p r o v i d e d b y the
height in areas b e t w e e n masts o r g r o u n d wires. T h e
installation of lightning c o n d u c t o r s .
overhead g r o u n d wires o n the lines should have an
A lightning c o n d u c t o r system consists o f terminals effective l o w resistance g r o u n d at each structure.
projecting into the air a b o v e the u p p e r m o s t parts o f L i g h t n i n g protection o f p o w e r stations and substations
the structure, with interconnecting and g r o u n d i n g includes the protection o f station equipment b y means
conductors. Terminals should b e placed s o as t o of lightning arresters.
project a b o v e all points w h i c h are likely t o b e struck.
F o r lightning arresters a local g r o u n d i n g c o n n e c -
Conductors should present the least possible i m p e -
tion should b e m a d e b y driving electrodes into the
dance to earth. T h e r e should b e n o sharp bends o r
earth (see Chapter I V ) near the arresters, as s h o w n
loops. Each projecting terminal a b o v e the structure
in Figure 3.3. I n addition, the lightning arrester
should have at least t w o c o n n e c t i n g paths t o earth
g r o u n d i n g c o n d u c t o r should b e c o n n e c t e d into the
and m o r e if practicable.
c o m m o n station g r o u n d bus. F o r the average case
Each c o n d u c t o r running d o w n from the terminals an arbitrary upper limit o f 5 o h m s resistance to

32

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
Structures of this nature m a y be subject to c o m -
plete destruction from a small spark which w o u l d
be of n o c o n s e q u e n c e except for the presence of
combustible or e x p l o s i v e mixtures. Sheet metal of
3/16 inch thickness is adequate to withstand direct
strokes without puncturing. Steel tanks with steel
roofs and floating metal roofs are generally consid-
ered to be self-protecting. T a n k s with non-metallic
roofs are not self-protecting and should usually be
protected with air terminals, conducting masts or
overhead g r o u n d wires. In all cases, joints and piping
connections should be electrically continuous, and all
vapor or gas openings closed o r flameproof.

T a n k s should be well g r o u n d e d to c o n d u c t current


of direct strokes to earth and avoid building up
potentials that w o u l d cause arcing to ground. Steel
tanks with intimate contact with the earth are usually
considered to be well g r o u n d e d .

CHIMNEYS A N D STACKS

Chimneys and stacks m a y be primarily used for


c o m b u s t i o n gases or for ventilation. W h e r e ventilat-
ing stacks emit explosive gases o r dust, the terminals
projecting a b o v e the structure should extend at least
five feet a b o v e the opening. If explosive mixtures are
emitted under forced draft these terminals should
project at least fifteen feet a b o v e the openings.

METHODS OF PROTECTION

Suggested m e t h o d s of providing lightning protection


are summarized a b o v e . A m o r e detailed description
of the characteristics of lightning, factors to be c o n -
sidered and m e t h o d s , m a y be found in the National
Figure 3.3
Typical method of grounding a lightning arrester. Bureau of Standards H a n d b o o k 46, titled " C o d e for
Protection A g a i n s t Lightning".

ground has been established. L o w e r values m a y be


desirable, depending on the degree of protection re- BIBLIOGRAPHY
quired. T h e connection from arrester to g r o u n d should
be as short and as straight as possible. T h e National 1. Static Electricity in Industry — R . Beach, E l e c -
Electrical C o d e states that a lightning arrester g r o u n d trical Engineering, V o l . 65 N o . 5 pages 184-94,
c o n d u c t o r shall not be smaller than N o . 6 A W G . 1945.
A larger sized c o n d u c t o r is desirable as the system
voltage increases. 2. Protection Against Static Electricity — J. M.
Pearson, A u t o m o t i v e T r a n s . V o l . 21, 1940.

3. R a d i o A m a t e u r s H a n d b o o k — A . F. Collins and
TANKS AND TANK FARMS
D . J. Duffin, T h o m a s Y . C r o w e l l C o m p a n y , N e w
Structures used for the storage of flammable liquids Y o r k , 1949.
and gases m a y require special attention. S o m e of the
4. Industrial Fires and E x p l o s i o n s from Electro-
features which should be considered in protecting
static Origin — R . Beach, Mechanical Engineer-
such structures are as follows:
ing, April 1953.
1. A l l metal, gastight structures.
5. Combustion, Flames and E x p l o s i o n s — B. Lewis
2. T a n k s of partial or total non-metallic material.
and G. V o n E l b e , A c a d e m i c Press, N e w Y o r k ,
3. V a p o r or gas openings. 1951.

33

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
6. Static Electricity — National Fire Protection 9. C o d e for P r o t e c t i o n A g a i n s t Lightning, H a n d -
Association Pamphlet, 60 Batterymarch Street, b o o k 46, U . S. D e p t . o f C o m m e r c e , National Bu-
Boston 10, Mass., 1947. reau o f Standards.

10. Static Electricity — National Bureau of Stand-


7. Electrostatic Neutralizer D i s c h a r g e and Safety
Characteristics — R . Beach, Mechanical E n g i - ards Circular C-438.
neering, V o l . 71 N o . 4, pages 329-34. 11. Static Electricity — F a c t o r y Mutual Bulletin N o .
12.21.
8. R e c o m m e n d e d Safe Practice for Hospital O p e r a t -
ing R o o m s — National Fire Protection A s s o c i a - 12. Electrostatic Hazards and T h e i r Control — R.
tion Pamphlet, June 1952. Beach.

34

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
CHAPTER IV

CONNECTION TO EARTH

RESISTANCE TO EARTH T A B L E 4.2

Recommended Acceptable Values THE EFFECT OF MOISTURE CONTENT ON


THE RESISTIVITY OF SOIL
T h e m o s t elaborate g r o u n d i n g system that can b e
designed m a y p r o v e to be inadequate unless the c o n - Moisture Content Resistivity (Ohms Per CM Cube)
nection of the system to the earth is adequate and (Percent by weight) Top Soil Sandy Loam
has a l o w resistance. It f o l l o w s , therefore, that the 0 >l,000xl0 a
>l,000xl0 a

earth connection is one of the m o s t important parts 2.5 250,000 150,000


of the w h o l e g r o u n d i n g system. It is also the m o s t 5 165,000 43,000
difficult part to design and to obtain. 10 53,000 18,500
15 19,000 10,500
T h e perfect connection to earth should have z e r o 20 12,000 6,300
resistance, but this is impossible to obtain. G r o u n d 30 6,400 4,200
resistances of less than o n e o h m can b e obtained,
although this l o w a resistance m a y n o t b e necessary T A B L E 4.3
in m a n y cases. Since the desired resistance varies
T H E EFFECT OF TEMPERATURE ON THE
inversely with the fault current to g r o u n d , the larger
RESISTIVITY OF SOIL
the fault current the l o w e r must b e the resistance.
( S a n d y L o a m 15.2 percent M o i s t u r e )
For larger substations and generating stations, the
earth resistance should not exceed one o h m . For Temperature Resistivity
smaller substations and for industrial plants, in g e n - C F (Ohms per CM Cube)
eral, a resistance o f less than five o h m s should b e 20 68 7,200
obtained if practicable. T h e National Electrical C o d e 10 50 9,900
(1953) states that the m a x i m u m resistance shall not 0 (water) 32 13,800
exceed 25 ohms. 0 (ice) 32 30,000
—5 23 79,000
—15 14 330,000
Resistivity of Soils

It is r e c o m m e n d e d that the resistivity of the earth Calculation of Resistance to Earth


at the desired location of the c o n n e c t i o n b e investi-
Resistance t o earth m a y b e calculated a n d / o r
gated. T h e resistivity o f soils varies with the depth
measured. Calculation is considerably involved, but
from the surface, with the moisture content, and with
has been simplified to a great extent into the formulas
the temperature of the soil. Presence of surface water
d e v e l o p e d b y Prof. H . B. D w i g h t . T h e s e formulas
4

does not necessarily indicate l o w resistivity. R e p r e - appear in T a b l e 4.4.


sentative values of resistivity for general types of soils
are s h o w n in T a b l e 4.1. T h e effects of moisture and
Current-Loading Capacity
temperature are s h o w n in T a b l e s 4.2 and 4.3.
O n e factor w h i c h should not be o v e r l o o k e d in de-
signing a g r o u n d i n g system is the current-loading
T A B L E . 4.1
capacity of a c o n n e c t i o n to earth. T h e temperature
THE RESISTIVITY OF DIFFERENT SOILS and moisture conditions immediately surrounding the
electrode have a direct effect o n the resistivity of this
Resistance (Ohms) Resistivity p
}i inch x 5 foot rods (Ohms per cm cube) section of the g r o u n d i n g "circuit". Currents passing
Soil Avg. Min. Max. Avg. Min. Max. from the electrode into the earth will have a definite
Fills
Ashes, Cinders, Brine effect on these t w o factors. T h e r e f o r e , the current-
Waste 14 3.5 41 2370 590 7000 loading capacity of a c o n n e c t i o n must be analyzed
Clay, Shale, Gumbo, from the standpoint of the nature of the grounding
Loam 24 2 98 4060 340 16300 circuit and the types o f loading w h i c h it can normally
Same — with varying be e x p e c t e d t o carry.
proportions of sand
and gravel 93 6 800 15800 1020 135000
Currents of l o w magnitude, even if of long dura-
Gravel, sand, stones, tion, will result in relatively little heating. T h e effect
with little clay or
loam 554 35 2700 94000 59000 458000 of heat c o n d u c t i o n and the m o v e m e n t of moisture

35

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
T A B L E 4.4

Formulas for the Calculation of Resistances to Ground

( A p p r o x i m a t e formulas including effects of images. D i m e n s i o n s must b e in centimeters


to give resistance in o h m s . )
p = Specific resistance o f earth in o h m s per c m 3

Hemisphere p _ P
Radius a R
2 ^

• One G r o u n d R o d
Length L, radius a

• • Two Ground R o d s
s > L; spacing s
«-^(^-0 ^0-8 !F-) + +

Two Ground Rods


s < L; spacing s

— Buried Horizontal Wire


Length 2L, depth s/2

i_ Right-Angle Turn of Wire


Length of arm L, depth s/2 R =
4^1 ( I O G ,
"T 1 + LOG
*T~ 0 2 3 7 3 +
°- 2 1 4 6
ZT + 0 1 0 3 5
T>~ 0 0 4 2 4
£i- • ' )

A Three-Point Star
Length of arm L, depth s/2 R
= dl ( LOG
<T-+ I O G
' 1
- 0 7 1
" A 2 0 9
T+ 0 2 3 8
IT" 0 0 5 4
£• •)

+ Foixr-Point Star
Length of arm L, depth s/2 ^ =
SjtE ( <^ +
LOG LOG
'
2
-T+ 2-912 - 1.071-*-+ 0.645^ - 0.146^...)

* Six-Point Star
Length of arm L, depth s/2
R =
ihh ( *1T
LOG + IOG
* T" + 6 8 5 1 _
3 1 2 8 - 1 - + 1.758-^- - 0.490-j;.. )

* Eight-Point Star
Length of arm L, depth s/2 * - ih. ( LOG
' 1 T + '<*• T-+ 1 0 9 8
" 5 5 1
T +
»-«^~ 1 1 7
T< )

O
R i n g o f Wire
Diameter o f ring D , diameter
of wire d, depth s/2

— Buried Horizontal Strip


Length 2L, section a by 6,
depth s / 2 , 6 < c / 8
R
= 4*L ( *< a 2 ( a
l0 +
+ 6)« + 1
^ , 1 +
I T " iSB + BHD'' )

Buried Horizontal R o u n d Plate R - P ± * I\ 7


<* + 83<* \
R a d i u s a, depth s/2 5a" " 4 « \
1
12 5* 4 0 s«* * 7

Buried Vertical R o u n d Plate /? - P 4. P /i 4. * 4. ° \ 7 A 9 9 4

Radius a, depth s/2 8a ^ 4 « V 24 s* ^ 320 * * ' " / 4

"Calculation of Resistance to Ground," by H . B. Dwight, Electrical Engineering, vol. 55, p. 1319, December, 1936.

due to capillary action will maintain, in m o s t cases, ductivity. T h e permissible current density for a given
the resistivity o f the earth at the electrode to a temperature rise is inversely proportional to the square
value close to that considered desirable. r o o t o f the soil resistivity. T h e effective resistance
of the earth c o n n e c t i o n w o u l d , therefore, depend o n
W h e r e the earth must dissipate high currents for the number o f such situations w h i c h c o u l d o c c u r in
short durations, n o appreciable a m o u n t o f heat can succession before stable conditions in the earth w e r e
be dissipated b y the normal p r o c e s s o f thermal c o n - re-established.

36

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
Ground currents of high magnitude and l o n g dura- cost. T h e y also require the least amount o f buried
tion are unusual, but could o c c u r as the result of material per o h m of g r o u n d c o n d u c t a n c e . Buried plates
ground faults w h i c h are not cleared promptly. If have not been used extensively in recent years
ground currents of this type are anticipated, the sys- because of the higher c o s t as c o m p a r e d to r o d s or
tem must c o v e r a relatively large area in o r d e r to strips. A l s o , w h e n used in small numbers, they are
keep the current density in the earth to a l o w value. 9
the least reliable type o f m a d e electrode. T h e counter-
poise is a f o r m of buried cable electrode used to
Soil Treatment
g r o u n d transmission line t o w e r s and structures.
Soil resistivity m a y b e reduced anywhere from 15
to 90 percent, depending upon the kind and texture W h e n multiple electrodes are used, spacings o f less
of the soil, b y chemical treatment. T h e r e are a n u m - than ten feet d o not p r o v i d e the m o s t economical use
ber o f chemicals suitable for this purpose, including of materials.
sodium chloride, m a g n e s i u m sulphate, c o p p e r sulphate, In selecting the number and size of grounding termin-
and calcium chloride. C o m m o n salt and magnesium als, their current discharge limitations must be recognized.
sulphate are m o s t c o m m o n l y used. If these are exceeded, the earth around the electrode may
Chemicals are generally applied b y placing them be exploded by steam generation, or may be dried out to
in the circular trench around the electrode in such the extent of becoming nonconductive.
a manner as to prevent direct contact with the elec-
D r i v e n R o d or P i p e
trode. W h i l e the effects o f treatment will not b e c o m e
apparent for a considerable period, they m a y be ac- D r i v e n electrodes m a y b e either r o d s o r pipes, al-
celerated b y saturating the area with water. A l s o , such though r o d s are generally m o r e economical. W h e r e
treatment is not permanent and must b e r e n e w e d soil conditions permit, a f e w deep r o d s are usually
periodically, depending on the nature of the chemical m o r e satisfactory than a multiplicity o f short r o d s
treatment and the characteristics o f the soil. since the v o l u m e o f soil affected increases directly
with the length o f e l e c t r o d e b e l o w the surface and
the soil resistivity generally decreases with depth
GROUND ELECTRODES
due to the increased moisture content. A n article
Existing Electrodes b y J. Z a b o r s z k y and J. W . R i t t e n h o u s e presents a
6

Basically all g r o u n d electrodes m a y b e divided into number o f design charts for determination o f o p t i m u m
t w o groups. T h e first c o m p r i s e s u n d e r g r o u n d metallic g r o u n d r o d dimensions and spacings for a given in-
piping systems, metal building f r a m e w o r k s , well cas- stallation.
ings, steel piling, and other u n d e r g r o u n d metal struc-
B u r i e d Strip, W i r e and Cable
tures installed for purposes other than g r o u n d i n g .
W h e r e b e d r o c k is near the surface, o r w h e r e sand
T h e s e c o n d c o m p r i s e s m a d e electrodes specifically
is encountered, the soil is apt t o b e v e r y dry and
designed for g r o u n d i n g purposes.
of high resistivity and it is necessary to have an
T h e National Electrical C o d e states that continuous earthing c o n n e c t i o n o f considerable extent. U n d e r
underground water o r gas piping systems generally such conditions, buried metal strips, wires o r cables
have a resistance to earth o f less than 3 o h m s , and offer the m o s t e c o n o m i c a l solution. Since the effec-
that metal building frames, local metallic u n d e r g r o u n d tiveness o f this type o f electrode for lightning dis-
piping systems, metal w e l l casings, and the like, have charges is a function o f its inductance, the use o f a
in general a resistance t o earth o f substantially less n u m b e r o f w e l l spaced shorter strips in parallel is
than 25 o h m s . F o r safety g r o u n d i n g and for small preferable to o n e o r m o r e l o n g strips. T h e depth at
distribution systems w h e r e the g r o u n d currents are w h i c h the strips are buried is n o t critical. Tests b y
of relatively l o w magnitude, such electrodes are usually the Bureau o f S t a n d a r d s s h o w that the decrease in
1

preferred because they are e c o n o m i c a l in first cost. resistance f r o m the m i n i m u m depth for cultivation
H o w e v e r , before reliance can b e placed on any elec- to the m a x i m u m practicable — about 18 to 36 inches
trodes of this g r o u p , it is essential that their resistance — is o n l y about 5 percent, based o n uniform soil
to earth be measured to insure that s o m e unforeseen resistivity. Similarily, the effect o f c o n d u c t o r size is
discontinuity has n o t seriously affected their suit- e x t r e m e l y small.
ability. A l s o , care should b e exercised t o insure that
all parts w h i c h m i g h t b e c o m e disconnected are effec- Grid Systems
tively b o n d e d together. Grid systems usually extend o v e r the entire station
yard and m a y extend s o m e distance b e y o n d the
Made Electrodes
b o u n d a r y fence. T h e y consist o f c o n d u c t o r s buried
M a d e electrodes m a y b e subdivided into driven a m i n i m u m o f 6 inches in the g r o u n d o r stone fill
electrodes, buried strips or cables, grids, buried plates, and f o r m i n g a n e t w o r k o f squares T h e size of
and counterpoises. T h e type selected will depend upon squares will v a r y with the v o l t a g e class o f the station
the type o f soil encountered and the available depth. but cable spacings o f 10 to 12 feet are c o m m o n l y
Driven electrodes are generally m o r e satisfactory and used. A l l cable c r o s s i n g s should b e securely b o n d e d
economical w h e r e b e d r o c k is ten feet o r m o r e b e l o w and the system c o n n e c t e d t o the n o r m a l g r o u n d sys-
the surface, while grids, buried strips o r cables are tem as well as t o all equipment and structural steel
preferred for lesser depths. Grids are frequently used w o r k . In r o c k g r o u n d w h e r e driven g r o u n d s are i m -
for substations o r generating stations to p r o v i d e equi- practical, it is s o m e t i m e s m o r e e c o n o m i c a l and desir-
potential areas t h r o u g h o u t the entire station w h e r e able t o use a g r i d s y s t e m in p l a c e o f buried strips,
hazards to life and p r o p e r t y w o u l d justify the higher in w h i c h case the cables are usually buried at a depth

37

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
of one to t w o feet. A n article b y E . T . B . Gross, B. V . at a point not far from the g r o u n d line, thus per-
Chitnis and L . J. S t r a t t o n gives the basic charac-
6
mitting r o d s to be driven to greater depths than
teristics and design elements for extensive grid s y s - w o u l d be possible b y hand sledging. If r o d s are to
tems. be driven o n a comparatively large scale, it is desir-
able to p r o v i d e p o w e r driving equipment. Electric,
Plates
pneumatic, and gasoline driven hammers are avail-
T h e preferred practice with plate electrodes is to able, the first t w o requiring sources of p o w e r . R e -
bury them on e d g e since a minimum o f excavation gardless of the type of driving tool used, precautions
is required and it is possible to obtain better c o n - should be taken to prevent "mushrooming*' o f the
tact with the soil w h e n backfilling. T h e r e appears t o head.
be little difference between the effective resistance
L o c a t i n g W a t e r M a i n ( N e w Construction)
of horizontal and vertical plates. F o r c o m m o n l y used
plates o f 10 to 20 square feet, the o p t i m u m burial Prior to n e w construction, analysis of the soil c o n -
depth is 5 t o 8 feet. dition and location o f the g r o u n d i n g point m a y per-
mit locating a water pipe nearby. T h i s w o u l d eliminate
a l o n g g r o u n d i n g line ( t o a distant water main) with
METHODS A N D TECHNIQUES OF
its inherently high inductance. T h e e c o n o m i c ad-
CONSTRUCTION
vantage o f such an arrangement should not be over-
Choice of Rods looked.

Ground rods are manufactured in J^, % Connecting to Electrodes


and 1 inch diameters and in lengths o f from 5 to 40 Connections to electrodes are usually made in
feet. F o r m o s t applications the A, $A and ^4 inch
Z

t w o principal manners. T h e first o f these methods


diameters, in lengths o f 8, 10, 12 and 16 feet, are involves the use of mechanical ( b o l t e d ) fittings which
satisfactory. T h e National Electrical C o d e specifies are readily available, simple to install, disconnectable
that rods of steel o r iron shall be at least Y% inch for measurements o f resistance to earth, and have
in diameter, and that r o d s of non-ferrous materials a l o n g history of satisfactory usage. A l t h o u g h cor-
shall not be less than inch in diameter. C o p p e r - rosion has sometimes presented a p r o b l e m , considera-
clad steel, one o f the m o s t c o m m o n types o f rod, tion o f the joint as a standard electric connection in
permits driving t o considerable depth without d e - a c o r r o s i v e element, and treatment accordingly, elimi-
struction of the r o d itself, while the c o p p e r coat makes nates m o s t o f the p r o b l e m s in this respect. Mechani-
possible direct c o p p e r - t o - c o p p e r connection between cal connections should, if at all possible, be accessible
the ground wire and the rod. In addition to the for inspection and servicing.
copper-clad steel, galvanized steel r o d s are available.
F o r ease of driving the rods, s o m e r o d s are available T h e s e c o n d m e t h o d , a thermit p r o c e s s of connect-
in sections threaded at b o t h ends. A s the sections ing to the electrode, has increased in usage in recent
are driven, the rods are c o n n e c t e d b y the couplings into years because o f the savings in time and costs when
a continuous conductor. A r e m o v a b l e stud will take m a n y c o n n e c t i o n s must be m a d e . T h i s m e t h o d will
the driving b l o w s and avoid d a m a g e to the threads provide a permanent c o n n e c t i o n eliminates contact
of the joint. resistance, is relatively c o r r o s i o n free, and permits
the use o f smaller cable because o f the 450 C maxi-
T h e effect of the r o d diameter o n the resistance o f m u m temperature limitation as c o m p a r e d to the
the connection t o earth is small. T h e diameter of m a x i m u m o f 250 C usually permitted for mechanical
ground rod will be determined mainly b y the mechani- connections. It does, h o w e v e r , have certain inherent
cal rigidity required for driving. It is advantageous limitations. It requires separate disconnecting means,
to select the smallest diameter r o d which meets the such as a b o v e g r o u n d bolted joints, for measurements
driving requirements. A v e r a g e soil conditions will of resistance t o earth. It also requires the use of a
permit the use o f the ^2 inch r o d ; the % inch r o d certain amount of training, and it cannot be used
can be driven in nearly all types o f soil, and the in the presence o f volatile o r explosive mixtures, or
Y± inch diameter r o d m a y be reserved for exceptionally w h e r e the gaseous p r o d u c t s of the operation w o u l d
hard driving conditions, o r for deep driven rods. interfere with nearby operations.

F o r ordinary soil condition, the 10 f o o t length o f A third m e t h o d that ultilities are presently experi-
rod has b e c o m e fairly well established as a m i n i m u m menting with involves the use o f a c o p p e r o r copper
standard length to meet the c o d e requirement o f a alloy c o n n e c t o r w h i c h is squeezed o n to both ground
minimum o f 8 buried feet. r o d and cable simultaneously b y a hydraulic press.
T h i s m e t h o d is e c o n o m i c a l , presents m o s t o f the ad-
vantages o f the thermit process, and eliminates m o s t
Methods of Driving Rods
of the o b j e c t i o n s t o that p r o c e s s .
Sledging requires a m i n i m u m o f driving equipment, O t h e r m e t h o d s o f joining, such as brazing or w e l d -
but m a y require considerable time per f o o t of r o d . ing, are satisfactory if p r o p e r l y d o n e .
A modification of the s l e d g i n g process, consisting
of a chuck and sliding hammer, permits the w o r k to
Joining to Underground Piping Systems
be carried on at a level convenient to the w o r k m a n
without a ladder o r auxiliary platform. A n additional Joining to pipe presents several p r o b l e m s . Clamp
advantage is that the b l o w is delivered to the r o d type fittings are relatively expensive, since they must

38

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
obviously a c c o m m o d a t e large pipe in addition to the MEASUREMENT OF RESISTANCE
relatively small c o n d u c t o r . W e l d i n g or brazing to the TO EARTH
pipe will cause localized- stress w h i c h m a y impair
the function of the pipe, particularly if it contains Need for M e a s u r e m e n t
fluid under high pressure. A typical w e l d e d c o n n e c - In any formula for the determination of the re-
tion to water pipe is s h o w n in Figure 4.1. sistance to earth there are m a n y indeterminate
factors, and t o o m u c h reliance should not be placed
u p o n the calculated results. T h e o n l y certain w a y
is to measure the resistance after the system has
been c o m p l e t e d . A desirable refinement w o u l d be to
measure the resistance of each electrode during in-
stallation.
Methods for Measuring

T h e principles used in the measurement of resist-


ance to earth are essentially the same as those used
for measuring other types of electrical resistances.
T h e various m e t h o d s available all make use of t w o
auxiliary electrodes in addition to the o n e under test,
and m a y be g r o u p e d into the following theree general
classes:

1. T h e three point m e t h o d , in w h i c h the resistance


to earth of the electrode under test and the
auxiliary electrodes are measured t w o at a time
in series. T h i s m e t h o d is suitable for measuring
the resistance to earth of isolated g r o u n d elec-
trodes or small g r o u n d i n g installations. It is
not suitable for the measurement of low-resist-
ance installations.

2. T h e fall-of-potential m e t h o d , which involves the


passing of a k n o w n alternating current through
the electrode under test and one of the auxiliary
electrodes, and measuring the potential d r o p b e -
tween the former electrodes and a secondary
auxiliary electrode set at various distances be-
tween the t w o fixed electrodes. T h i s method
m a y be subject to considerable error if stray
g r o u n d currents are present, o r if pipes or other
c o n d u c t o r s are buried near the test electrode.

3. T h e ratio m e t h o d , which involves measurements


Figure 4.1 of the ratio of the resistance to earth of an
Typical method of grounding to a large ungrounded
water pipe using welding method. auxiliary test electrode to the series resistance
to earth of the electrode under test and a second
auxiliary electrode.
Joining to Structural Steel Multiplying this ratio b y the series resistance
gives the effective resistance of the ground
Bolted fittings lend themselves best to structural
electrodes. T h i s m e t h o d is m o r e satisfactory than
steel w h i c h can b e field drilled but not welded. T h e s e
triangulation m e t h o d s , since ratios of test elec-
are available in a n u m b e r o f shapes and sizes t o a c -
trode resistance to the resistance of the electrode
c o m m o d a t e the range o f c o n d u c t o r s . Material for the
under test m a y be as high as 300:1.
clamps, or protective finishes applied to the clamps
should be chosen s o as to b e satisfactory, from the A m o r e c o m p l e t e treatment of the details of these
corrosion standpoint, to b o t h the g r o u n d i n g wire and three m e t h o d s m a y be found in the Standard H a n d -
the steel o r iron. Brazing and the thermit process are b o o k for Electrical Engineers, and other standard
also used in connecting to structural steel, but should w o r k s . C o m m e r c i a l l y available portable testing in-
be restricted to applications which will not affect the struments p r o v i d e the m o s t convenient and satis-
structural properties o f the steel. factory means for measuring the resistance of connec-
tions to earth. Instruments used for measuring in-
Preparing the Joint sulation resistance are n o t suitable, h o w e v e r , because
they cannot measure sufficiently l o w resistance values.
It is important that the surface of any c o n n e c t i o n Precision in measurements of resistance to earth is
be cleaned of any insulating medium, such as insula- difficult t o obtain and is usually n o t required. Meas-
tion, grease, paint, o r dirt, before making the c o n n e c - urements in the o r d e r of one, ten, or 100 o h m s are
tion. generally indicative of the adequacy of the connection.

39

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.
It is desirable, in measuring the resistance of the 2. A n Investigation o f Earthing Resistance, b y P. J.
completed system, to a l l o w s o m e time to elapse before H i g g i n s , I . E . E . Journal, V o l . 68, p. 736, Feb. 1930.
measurements are made, so that the earth around
the electrodes will be consolidated. 3. Lightning Arrester G r o u n d s , Parts I, I I , and I I I ,
b y H . M . T o w n e , General Electric R e v i e w , March,
A p r i l and M a y , 1932.
Periodic Testing
4. Calculation o f Resistance to Ground, b y H . B.
T e s t s should be m a d e periodically after the original D w i g h t , A I E E Transactions, V o l . 55, 1936, page
installation and test, so that it can be determined 1319.
whether the resistance is remaining constant or is 5. D e s i g n Charts for D e t e r m i n i n g O p t i m u m Ground
increasing. If later tests s h o w that the resistance R o d Dimensions, b y J. Z a b o r s z k y and J. W .
is increasing to an undesirable value, steps should Rittenhouse, A I E E Trans., Power A p p . & Systems,
be taken to reduce the resistance either b y additional V o l . 72, 1953, pgs. 810-17.
electrodes or b y increasing the moisture content or
by chemical treatment. 6. G r o u n d i n g Grids for H i g h - V o l t a g e Stations, by
E. T . B . G r o s s , B . V . Chitnis and L . J. Stratton,
A I E E Trans., Power A p p . & Systems, V o l . 72, 1953,
CATHODIC PROTECTION pgs. 799-810.

A n y discussion o f c a t h o d i c protection is b e y o n d the 7. Earth Resistivity and G e o l o g i c a l Structure, by


scope of this publication. T h e reader is referred to R. H . C o r d , A I E E Transactions, V o l . 55, 1935,
the conference paper "Electrical G r o u n d i n g and page 1153.
Cathodic Protection at the Fairless W o r k s " b y W . E. 8. G r o u n d i n g Electric Circuits Effectively, b y J. R.
Coleman and H . Frostick, U . S. Steel Corporation, Eaton, General Electric R e v i e w , June, July and
presented b y the A I E E S u b c o m m i t t e e o n Cathodic A u g u s t , 1941. ( R e p r i n t e d b y James G. Biddle C o . ) .
Protection at the 1954 A I E E W i n t e r General Meeting.
A n article in the M a r c h 1954 issue o f I r o n and Steel 9. Fundamental Considerations o f G r o u n d Currents,
Engineer, "Cathodic P r o t e c t i o n for Steel Mill G r o u n d - b y R e i n h o l d R u d e n b e r g , Electrical Engineering,
ing System", b y J. F. H e a d l e e , U . S. Steel C o r p o r a - January 1945, page 1.
tion, is also r e c o m m e n d e d . 10. Establishing G r o u n d s , b y Claude Jensen, Elec-
trical Engineering, F e b r u a r y 1945, page 69.
11. Analytical E x p r e s s i o n s for the Resistance of
BIBLIOGRAPHY
G r o u n d i n g Systems, b y S. J. S c h w a r z , A I E E
1. Ground Connections for Electric Systems, b y Transactions 1954, p a g e 1011.
O . S. Peters, National Bureau of Standards T e c h - 12. Lets L o o k to Station G r o u n d i n g , b y S. J-
nical Bulletin N o . 108. S c h w a r z , Electrical W o r l d , M a y 2, 1955, page 55

40

Authorized licensed use limited to: University of Wollongong. Downloaded on May 12,2016 at 07:10:29 UTC from IEEE Xplore. Restrictions apply.

Das könnte Ihnen auch gefallen