Beruflich Dokumente
Kultur Dokumente
3, MAY/JUNE 1973
Abstract-Over the years, various approaches including both thermal ing. Chart 430-37 is provided which outlines the number and
magnetic breakers and several types of fusible devices have been used location of overcurrent devices in various types of supply
in motor circuit protection schemes with acceptable results. Evidence systems.
reported in the trade magazines indicated that the level of protection
from these types of devices was not totally effective. For the first Motor branch circuit, short-circuit, and ground fault protec-
tion is covered in paragraph 430-D. This paragraph outlines
time, with the printing of the 1968 National Electric Code, the applica-
tion of instantaneous trip circuit breakers (without time delay) was the various types of devices that may be applied as well as the
allowed provided the pickup could be adjusted above 700 percent to a maximum setting allowed for each type device. Requirements
maximum of 1300 percent of the motor full-load ampere rating. After are given for individual motors, multispeed motors, and
extensive testing the first product complying with these requirements
was introduced to the market in 1969. Experience in motor failures multiple motors on one branch circuit. Table 430-152 con-
veniently summarizes the recommended maximum settings of
indicates that most faults occur at relatively low levels of fault current
just above lock rotor values rather than at higher levels. With rapid motor branch circuit protective devices in terms of percent of
clearing of faults in the low-level range such as can be accomplished motor full-load currents.
with the use of instantaneous trip circuit breakers, extensive damage to With the passing of the new Federal Occupational Safety
motors as well as to control equipment can be greatly reduced. By
combining low-level protection obtained with the high interrupting and Health Laws-better known as O.S.H.A.-more emphasis
capabilities of specially designed current limiters, a full range of than ever before will be placed on compliance with the NEC.
Since the Law was originally passed, it has been amended and
coordinated protection is available for both high- and low-level faults.
announced in the Federal Register dated 72-2-16 to specify
the applicable Code to be in the 1971 NEC. As of 72-3-15 all
INTRODUCTION new electrical construction work shall be in accordance with
W7, [ ITH RECENT changes in the National Electric Code the 1971 NEC.
AY [(NEC), new avenues of motor circuit protection have The Underwriters' Laboratories (UL), Inc., Standard for
been opened so that better, closer protection than ever before Safety Number UL 508 [2] covers the specific design and test
can now be achieved. requirements for industrial control equipment. This standard
This paper will briefly cover the requirements of adequate outlines the specific design and testing requirements for the
motor circuit protection, review the components used in motor components of a combination motor controller-unless specifi-
circuit protection, discuss the levels of motor circuit fault cally covered by another standard such as UL 489 for molded
currents, and present a new method of achieving a better case circuit breakers-as well as the enclosure itself.
approach to motor circuit protection. In general, the NEC outlines the minimum application re-
quirements for the protection of a motor branch circuit in
REQUIREMENTS OF ADEQUATE MOTOR CIRCUIT terms of running overload protection and short-circuit protec-
PROTECTION tion while the appropriate applicable UL Standard defines the
Article 430 of the 1971 Edition of the NEC [1] adequately design, performance, and test requirements of the components
outlines the minimum requirements for motors, motor circuits, employed. The Standard outlines the types of tests to be
and controllers. Article 430 is subdivided into several alpha- performed, the parameters of the tests, the number of test
betical subsections according to the function involved. This samples involved, and gives the levels of performance accepted.
paper will concentrate mainly oni subsections 430-C and The users of motor circuit control and protection equip-
430-D. ment have many individual application requirements and
Motor and branch-circuit running overcurren t protection is standards that they adhere to that often surpass the minimums
covered in paragraph 430-C. This section in general defines outlined in the NEC. The objects of these many individual
the meaning of overloads and proceeds to outline the various requirements that are specified by these users include: maxi-
levels of overcurrent protection that are to be provided for mum continuity of production, minimum downtime, protec-
motors having either integral overcurrent protectors or separate tion of original investment, and personnel safety. The best
overcurrent devices. Separate requirements are outlined for way to achieve all of these goals is to provide coordinated
motors over and/or under one horsepower as well as for con- motor circuit protection where each component in the system
tinuous duty, intermittent duty, manual and automatic start- performs its intended function in the proper manner and time.
Motor failures will continue to occur for a variety of reasons.
Paper TOD-72-153, approved by the Petroleum and Chemical Industry The purpose of proper motor circuit protection is to clear the
-ommittee of the IEEE Industry Applications Society for presentation motor circuit from these faults as rapidly as possible upon the
at the Industry Petroleum and Chemical Industry Technical Conference,
senver, Colo., September 18-20, 1972. Manuscript released for publi- detection of the fault thus reducing the level of damage to the
-ation December 22, 1972. minimum. This will most likely be achieved when the circuit
The author is with Westinghouse Electric Corporation, Beaver, Pa.
15009. components are properly designed and coordinated.
WHITT: MOTOR CIRCUIT PRORECTION 279
Coordinated protection could also include ground fault pro- mately trip on 100-percent of the current element rating, and
tection which is not ordinarily achieved through normal over- in not more than 8 min on 200-percent of the element rating,
load and short-circuit protection devices used in motor control and in not more than 30 s on 600-percent of the element
circuits. For the first time, in the 1971 NEC under paragraph rating. Thermal elements were required to be used in only
230-95, ground fault protection is required under certain two of the three-phase conductors on any three phase, three
conditions on service entrance equipment. When ground fault or four wire, grounded or ungrounded system per Table 430-37.
protection is required, the maximum pick-up setting allowed With the release of the 1968 NEC, several changes were
in the Code is 1200 A. At the present, ground fault protection introduced in the area of motor running overload and branch
is only required on the main disconnect, but a fine print note circuit protection. The most significant change that was in-
in the Code indicates the further need for additional ground cluded in the 1968 Code occurred in paragraph 430-52. This
fault protection on feeders and branch circuits to insure maxi- change allowed for the first time the use of an instantaneous
mum continuity of service. With this consideration in mind, trip circuit breaker (without time delay) provided the breaker
the addition of proper ground fault protective devices to motor was adjustable and if part of a combination controller having
branch circuits will be necessary to achieve the overall coordi- overcurrent protection in each conductor and the combination
nated protection required to satisfy both phase overload was especially approved for the purpose. The setting of the
and/or ground fault conditions. breaker should be adjustable over 700-percent to a maximum
of 1300 percent of the motor full-load current.
COMPONENTS USED IN PROTECTION OF MOTOR Prior to this change as stated previously, the only policy
CONTROL CIRCUITS which was universally accepted as a safety selling feature was
Prior to the introduction of the 1968 NEC, the most popular the inclusion of UJL listed components within the combination
type of circuit breaker used in motor control circuits was the controller. We have known for some time that this policy
thermal-magnetic type which, as the name implies, includes alone has not provided the ultimate in motor circuit protection
both a thermal element designed to function on overloads and especially in the area of motors having full-load current in
a magnetic element designed to function on short circuits. the range of 6 A and less. Data are available that indicate as
The thermal magnetic circuit breaker is described in the Code late as 1970 that approximately 16 percent of all electrical fires
as a time limit breaker. Time limit circuit breakers were applied recorded in the United States were caused as a result of motor
in line with Tables 430-152 and/or 430-153. As an example, failures [3]. This figure was a 3-percent reduction over the
for squirrel-cage motors, time limit circuit breakers were figures given for 1969.
applied at a maximum of 250-percent motor full-load cur- In the 1968 NEC on three-phase systems, three heaters were
rent rating. required to be used when part of a combination controller
In the lower ratings of thermal magnetic breakers, the mag- employing an instantaneous trip circuit breaker. With the
netic circuit is nonadjustable and could be in the range of 20 introduction of the 1971 NEC, this requirement in Table
to 40 times the continuous rating of the breaker. With devices 430-37 was extended to all three-phase systems unless pro-
of this type properly applied in accordance with the 250- tected by other approved means.
percent application rule, the magnetic trip could vary from
50 to 200 times actual motor full-load current. For smaller NORMAL OVERLOAD PROTECTION
motors, the percentage of magnetic trip could increase greatly In general, motor overload running protection is provided by
since the minimum UL listed thermal magnetic breaker is one of two major classes of protectors: 1) integral with the
rated IS A. motor or 2) remote from the motor. In the first class, motor
The most commonly used fuse for motor branch circuit overheating is detected by temperature sensors imbedded
protection was the one time or so-called NEC fuse. One time directly in the motor winding. When the winding reaches a
fuses also were applied in accordance with Tables 430-152 predetermined temperature level indicative of an unsafe condi-
and 430-153 for a squirrel-cage motor as the preceeding but, at tion which could lead to motor failures, the sensing device
300-percent of motor full-load current. Under specific condi- operates to de-energize a remote controller which removes the
tions, both the one-time fuse and the time limit circuit motor from service. This method is perhaps the most positive
breakers could be applied up to 400-percent of motor full- since the actual temperature of the winding is measured
load current per paragraph 430-52-(a). directly, and no compensation for ambient temperature or
The most common device used for motor running over- other considerations need be made. While it is the best method
current protection is the noncompensating thermal overload to use in theory, it is not in widespread general usage because
relay. Overload relay heater elements are applied on the basis of the high cost and nonavailability of the special motors.
of a code designation with a range from minimum to maxi- The second major class of overload protection and by far the
mum motor full-load amperes for each code designation. The most common method in use, employs current sensing devices
44must trip" rating of the element is 125-percent of the mini- located remotely from the motor. This type protection may
mum application value of the range and 115-percent of the take the form of fuses, dashpot overload relays, or thermal
maximum application value of the range. The operating overload relays. Thermal relays depend on the heating ability
performance for thermal overload relays is outlined in para- of the motor current to actuate their protective mechanisms.
graph 109 of UL 508 which requires that an overload relay Currents that exceed the motor full-load ampere rated values
when tested at an ambient temperature of 400C shall ulti- cause insulation failures due to overheating. Current levels
280 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, MAY/JUNE 1973
480 VOLT
SOURCE
v AVAILABLE SHORT
CC IRCUIT CURRENT
18,000 AMPS
NSTANTANEOUS
TRIP CIRCUIT I 277V 0.0154
BREAKER (MCP) 1) 18,000 Fig. 2. Locked rotor test oscillogram.
'IABLE It
MCP CONTINUOUS AMPERE RATING AND PIN POSITIONS
TABLE V
PHASE
CURRENT LIMITER/MCP APPLICATION CROSS REFERENCE
PHASE
3) locking pin for limiting trip setting to a maximum of
1300 percent of motor full-load amperes;
4) available with internally mounted shunt trip and/or
auxiliary contacts for control and indicating circuitry.
In addition to the preceding, the MCP has several distinct
advantages when compared to other types of devices that could
be used for motor branch short-circuit protection including the
following:
Fig. 4. Clearing time for typical dual element fuse.
1) simultaneous opening of all three phases-single phase
protection;
thought in mind, combination controllers utilizing MCPs have 2) fast operation on low level faults;
been assigned application ratings in line with Table IV. 3) resettable;
The MCP is designed to open instantaneously in one cycle for 4) insensitive to ambient temperatures;
fault currents that exceed the trip setting. Because of this 5) can be field tested;
design, the MCP provides the fastest means known to clear 6)
safety;
low-level faults. Dual element fuses are perhaps the most 7)
uniform size for all ratings-allows for common operat-
common type of fuse used today to provide redundant motor ing mechanisms;
running protection as well as motor branch circuit short-circuit 8) compact size;
protection. Pei Table 430-152 of the NEC, dual element fuses 9) low-operating cost, minimum downtime, replacement
may be applied as high as 175 percent of motor full ampere not required;
load rating, but per exception 430-52.(b) this may be extended 10) can be opened with remote control devices.
to 225 percent.
Extensive comparison tests have been conducted on simnilarly For systems capable of delivering high levels of fault current
rated low-level test circuits to study the clearing times of both in excess of the rating of the combination controller utilizing
the MCP and dual element fuses. In the case of the dual ele- the MCP alone, a new three-pole current limiter has been
ment fuses, the application level has been at 125 percent-not
developed. The current limiter is a unique design of a three-
175 percent. The MCP has in all cases been set oni a pin phase silver, sand, current limiting fuse that is designed to be
used in conjunction with and connected to the load side of
position corresponding to 1300 percent of motor full-load a type MCP motor circuit protector. With the addition of the
rating. In every case, the MCP has cleared the circuit in one current limiter, the MCP/current
cycle as shown in Fig. 3. The dual element fuses have always be applied on all circuits with faultlimiter combination can safely
capabilities up to 100 000 A
taken longer varying anywhere from a low of 12 cycles-on
one phase-to a high of 80-90 cycles. One such oscillogram
rms symmetrical.
is illustrated in Fig. 4. In this case, phase two fuse cleared in The current limiter is a compact three-phase assembly avail-
12 cycles while phases one and three cleared after 22 cycles. able in seven continuous current ratings including: 3, 7, 15, 30,
The level of fault current available was approximately 35 50, 100, and 150 A. Complete catalog references of the
times rated motor full load. Test results depicted in the current limiters along with associated MCPs to be used there-
with
preceding figures illustrate the distinct advantage of the MCP limiter is shown
are in Table V. Each of the three poles of the
equipped with a spring loaded indicator that wfll
in clearing low-level faults.
The motor circuit protector has several features that must extend beyond the limiter housing when a fault is interrupted
be mentioned, including the following: by the limiter identifying the faulted phases. A blown current
limiter is an indication of a serious circuit problem that must
1) compact, single frame size for all starters through size 4; be corrected before restoring service.
2) single adjusting cam for adjusting trip setting of all three The design of the individual MCP and current limiter is
poles simultaneously; coordinated so that normal fault currents up to 50 or more
284 IEEE TRANSACTIONS ON INDUSTRY APPLICATIONS, MAY/JUNE 1973
Raymond 0. D. Whitt (SM'62), for a photograph and biography-please see page 155 of the
March/April 1973 issue of this TRANSACTIONS.