Consider the following items before configuring a Radial Vibration Channel:

� When "No Keyphasor" is selected, the 1X Amplitude (Ampl) and Phase Lag,
2X Amplitude (Ampl) and Phase Lag, Not 1X Amplitude (Ampl), and Smax
Amplitude (Ampl) are not available.
� If a Keyphasor channel is selected, a Keyphasor Module must be installed in
the rack.
� The full scale options allowed for each proportional value is dependent upon
the transducer type.
� Internal Barrier I/O and External Barriers are not currently supported with
7200 11 mm, 14 mm, or 3000 Proximitors or the 3300 16 mm HTPS.
� If a Non-Standard transducer is selected, the setpoint OK limits are set to � 1
volt from the Upper and Lower OK limits that are selected.
� There are two selections for 3000 Series transducers:
3000 (-24V) Proximitor
Select this option when connecting a 3000 Series proximitor directly to a
3500 monitor. A default scale factor of 285 mV/mil will be selected. This
may be adjusted � 15 %. Note that the buffered transducers on the front
of the monitors and to the Data Manager are not compensated and
should be interpreted at 285 mV/mil.
3000 (-18V) Proximitor
Select this option when connecting a 3000 Series proximitor directly to a
3500 monitor, but supplying proximitor power from an external 18 volt
source. A default scale factor of 200 mV/mil will be selected. This may
be adjusted � 15 %. Note that the buffered transducers on the front of
the monitors and to the Data Manager are not compensated and should
be interpreted at 200 mV/mil.
� Setpoints may only be set on proportional values which are enabled.
� Monitors must be configured in channel pairs (for example Channels 1 and 2
may be configured as Radial Vibration and Channels 3 and 4 may be
configured as Thrust Position).
� When a full-scale range is modified, the setpoints associated with this
proportional value should be readjusted.
� It is best to set the Scale Factor value and the Trip Multiply value before the
Zero Position value.
� 3000 (-18V), 3000 (-24V), and 3300 RAM Proximitors have limited linear
ranges. Therefore, you should use caution when selecting the Full-scale
range of the Direct, 1X Amplitude (Ampl), 2X Amplitude (Ampl), Not 1X
Amplitude (Ampl) and Smax Amplitude (Ampl) PPLs. Full-scale value x Trip
Multiply should not exceed the linear range of the transducer.