Testing whole measurement system!
Accuracy of all kind of CT/PT burden,
Electricity Meters ε[%] ratio, phase shift
Electromechanical error
Meters
Connection
errors
Electronic (static)
Meters
4-Quadrants
Meters
1 3 4 6 7 9 10 12 1 3 4 6 7 9 10 12
L1 L1
L2 L2
L3 L3
N N
Electricity meter (CT) testing – direct connection Electricity meter testing (CT) – connection with clamps
1 2 3 4 5 6 7 8 9 11 1 2 3 4 5 6 7 8 9 11
P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 P1 P2
L1 L1
L2 L2
L3 L3
N N
TE30 Electricity Meter Tester and Power Quality 5
www.calmet.com.pl Analyzer
RMS measurement results and TE30 Analyzer configuration:
3-Phase Star or Voltage direct connection Automatic or Costant range used Actual Date and
Delta connection Current mesured by flexible clamps for measurements Time
← TABLE
CHART →
TE30 Electricity Meter Tester and Power Quality 8
www.calmet.com.pl Analyzer
Energy meter Register testing on site and laboratory
function of energy measurement with method of
setting time periods for verification of energy meter
Register directly in percent [%],
function of energy measuremnt for
power P, P+, P-, Q, Q+, Q-, S,
function of energy measurement for
the first (fundamental) harmonic of
active power PH1 and reactive power
QH1
Connection diagram
CT Ratio error and phase error testing
1 2 3 4 5 6 7 8 9 11
function of computing
S1 S2 S1 S2 S1 S2
transformer ratio error
L1
P1
P
P1
P
P1
P
directly in percent [%]
2 2 2
L2
L3
N
function of computing phase
shift error [°]
TE30 Electricity Meter Tester and Power Quality 10
www.calmet.com.pl Analyzer
CT, PT Transformers testing (LV i MV, voltage and current, simultaneously in
three phases) directly on site: CT / PT burden testing
1 2 3 4 5 6 7 8 9 11
S1 S2 S1 S2
Why the tranformer burden
S1 S2
L1
P1
P
P1
P
P1
P
(load) is so important?!
2 2 2
L2
L3
N
TE30 Electricity Meter Tester and Power Quality 11
www.calmet.com.pl Analyzer
CT Transformer testing: burden testing
CT – current transformer can operate with
ε – ratio error [%]
stated accuracy only between 25% - 100% of
burden (load). In case of too long, or too thin
Limit of
wire dimension or too small load, the result,
accuracy secondary current can be out of accuracy limits
[%] transformer power rating Sn
25% 100%
Normal work
area
Sn=5VA 1 2 3 4 5 6 7 8 9 11
Ip Is Connection wires
L=10m
Example (power loss in cables):
Us1 Us2 mm2
ρCU ⋅ l 0,0175Ω m ⋅ 2 ⋅10m
RP = = = 0,35Ω
S 1mm2
Current transformer PP = I 2 2 ⋅ RP = 52 A ⋅ 0,35Ω = 8, 75VA
TE30 Electricity Meter Tester and Power Quality 12
www.calmet.com.pl Analyzer
Function of power quality analyser + recording
analyzing of measurement
results for EN 50160
compatibility or individual
requirements of user
recording of power network parameters in the SD Flash 4-32GB memory, which gives
(8÷64)x106 sets of network parameters or long-term registration of power quality
TE30 Electricity Meter Tester and Power Quality 13
www.calmet.com.pl Analyzer
Function of power quality analyser + recording